Résumé du contenu de la page N° 1
RAV-SP1100UT-E
RAV-SP560AT-E, RAV-SP800AT-E
RAV-SP1100AT-E, RAV-SP1400AT-E
R410A
The type of all the indoor units described in this Service Manual is a new model, RAV-SP1100UT-E only.
For the other indoor units to be combined, refer to the Service Manuals for the following models.
Indoor unit Service Manual No.
RAV-SM560UT-E A02-013
4-way Air Discharge Cassette type RAV-SM800UT-E A02-013
RAV-SM1400UT-E A03-003
RAV-SM
Résumé du contenu de la page N° 2
ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer. – 2 –
Résumé du contenu de la page N° 3
Indoor Unit (4-Way Air Discharge Cassette Type) –––––––––––––––––––––––– RAV-SP1100UT-E OWNWE’S MANUAL ACCESSORIES (SOLD SEPARATELY) ............................... 4 ADJUSTMENT OF WIND DIRECTIONd ............................11 PRECAUTIONS FOR SAFETY ............................................4 TIMER OPERATION ...........................................................12 PARTS NAME ....................................................................... 6 MAINTENANCE.............................
Résumé du contenu de la page N° 4
1 PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. The precautions described below include the important items regarding safety. Observe them without fail. After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer. Turn off the main power supply switch (or breake
Résumé du contenu de la page N° 5
When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. Install the air conditioner securely in a location where the base can sustain the weight adequately. Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit. If refrigerant gas has le
Résumé du contenu de la page N° 6
3 SELECTION OF INSTALLATION CAUTION Length of refrigerant pipe connected to Item indoor/outdoor unit When using an air conditioner under low outside Addition of refrigerant is temperature condition (Outside temp.:–5°C or 20m or shorter unnecessary at the local site. lower) with COOL mode, prepare a duct or wind shield so that it is not affected by the wind. 21m to 50m Add 20g of refrigerant for every * 1m of pipe which exceeds 20m
Résumé du contenu de la page N° 7
500 Installation Place Necessary Space for Installation A place which provides a specified space around the Obstacle at rear side outdoor unit. A place where the operation noise and discharged air are not given to your neighbors. 1. Single unit installation A place that is not exposed to a strong wind. A place that does not block a passage. When the outdoor unit is installed in an elevated position, be sure to secure its feet. There must be sufficient space for c
Résumé du contenu de la page N° 8
3 SELECTION OF INSTALLATION Installation of Outdoor Unit Before installation, check strength and horizontality of the base so that abnormal sound does not generate. 1000 or more According to the following base diagram, fix the base firmly with the anchor bolts. (Anchor bolt, nut: M10 x 4 pairs) 90 600 90 115 Obstacles at both front and rear sides Open the upper side and both right and left sides. The height of obstacle at both front and rear sid
Résumé du contenu de la page N° 9
Refrigerant Piping Connection CAUTION TAKE NOTICE THESE IMPORTANT Waterproof rubber cap 4 POINTS BELOW FOR PIPING WORK 1. Keep dust and moisture away from inside the connecting pipes. 2. Tightly connect the connection between pipes Base plate and the unit. 3. Evacuate the air in the connecting pipes using Drain nipple VACUUM PUMP. 4. Check gas leak at connected points. Knockout hole Capacity Liquid side Gas side rank Outer Oute
Résumé du contenu de la page N° 10
3 SELECTION OF INSTALLATION How to remove the front panel Knockout of Pipe Cover 1. Remove screws of the front panel. 2. Pull the front panel downward. Removing the front panel, the electric parts appear at the front side. The metal pipes are attachable to the piping holes. If the size of the used power pipe does not match Rear direction with the hole, adjust the hole size to match with pipe size. Pipe cover Be sure to fix the power cable and indoor/outdoor
Résumé du contenu de la page N° 11
4 REFRIGERANT PIPING Flaring size : A (Unit : mm) Pipe Forming/End Positioning +0 A - 0.4 Outer diam. of copper pipe • Forming of pipe R410A R22 Form the pipe along with a marked line of the cabinet. 6.35 9.1 9.0 • End positioning of pipe 9.52 13.2 13.0 Match the ends of both pipes at a distance of 85 mm apart from the marked line. 12.7 16.6 16.2 15.9 19.7 19.4 * In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that of R22 to
Résumé du contenu de la page N° 12
4 REFRIGERANT PIPING Tightening of Connecting Part REQUIREMENT (Unit: N•m) 1. Do not put the spanner on the cap. The valve may be broken. Outer diam. of copper pipe Tightening torque 2. If applying excessive torque, the nut may be 6.35mm (diam.) 14 to 18 (1.4 to 1.8kgf•m) broken according to some installation conditions. 9.52mm (diam.) 33 to 42 (3.3 to 4.2kgf•m) 12.7mm (diam.) 50 to 62 (5.0 to 6.2kgf•m) • After the installation work, be sure to check gas leak of connecting part of the pipes with
Résumé du contenu de la page N° 13
5 EVACUATING Air Purge This air conditioner can be installed up to the connecting pipe length and height difference in the following table. Height difference (m) Max. connecting Hexagonal Capacity rank pipe length (m) wrench size Outdoor unit at upper side Outdoor unit at lower side SM560 type 30 30 15 4mm SM800, SP560, SP800 type 50 30 15 With respect to the preservation of terrestrial environment, adopt “Vacuum pump” for air purge (Evacuate air in the connecting pipes) when installing the unit
Résumé du contenu de la page N° 14
5 EVACUATING How to open the valve Compound pressure gauge Pressure gauge Valve unit –101kPa (–76cmHg) Manifold valve Handle Lo Handle Hi (Keep fully closed) Handle Pull out the handle and Charge hose Charge hose using cutting pliers, etc. (For R410A only) (For R410A only) turn it counterclockwise by 90˚. (Open fully) Vacuum pump adapter for counter-flow prevention Charge port (For R410A only) Flare nut Vacuum Valve unit pump Packed valve (Gas side) Service port (Valve core (Se
Résumé du contenu de la page N° 15
6 ELECTRICAL WORK For the air conditioner that has no power cable, connect How to wire a power cable as mentioned below. 1. Connect the connecting cable to the terminal as identified with their respective numbers on the SM800AT-E Model RAV- SM560AT-E SP560AT-E terminal block of indoor and outdoor unit. 2 SP800AT-E H07 RN-F or 245 IEC 66 (1.0 mm or more) 2. When connecting the connecting cable to the 220 – 240 V Power supply Single phase 50 Hz outdoor unit terminal, prevent water coming in th
Résumé du contenu de la page N° 16
7 FINAL INSTALLATION CHECKS Check and Test Operation Valve cover For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.). Piping The conventional leak detector for HCFC refrigerant (R22, * cover etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40. Flare nut connections • Pressure of R410A is approx. 1.6 times higher than that of (Indoor unit) R22. If installation work is incompletely finished, a gas leakage may occu
Résumé du contenu de la page N° 17
Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged acciden- tally, service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) • In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size of opposite side of flare nuts has been changed. (for copper pipes with nom
Résumé du contenu de la page N° 18
1 PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. The precautions described below include the important items regarding safety. Observe them without fail. After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer. Turn off the main power supply switch (or breake
Résumé du contenu de la page N° 19
When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. Install the air conditioner securely in a location where the base can sustain the weight adequately. Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit. If refrigerant gas has le
Résumé du contenu de la page N° 20
3 SELECTION OF INSTALLATION CAUTION When using an air conditioner under low outside temperature condition (Outside temp.:–5°C or lower) with COOL mode, prepare a duct or wind shield so that it is not affected by the wind. Discharge upward/downward Suction hood (Side) ( ) or leftward is also available. Discharge hood Suction hood (Rear side) Use it at location where a side wind Discharge drives thickly Fin Fin Suctio