Résumé du contenu de la page N° 1
FILE NO. SVM-10019
!""#!
Indoor Unit Outdoor Unit
RAS-09LKV-UL RAS-09LAV-UL
RAS-12LKV-UL RAS-12LAV-UL
R410A
Feburary, 2010
Résumé du contenu de la page N° 2
FILE NO. SVM-10019 CONTENTS 1. SAFETY PRECAUTIONS .......................................................................... 3 2. SPECIFICATIONS ..................................................................................... 6 3. REFRIGERANT R410A ............................................................................. 8 4. CONSTRUCTION VIEWS ........................................................................ 16 5. WIRING DIAGRAM ..................................................
Résumé du contenu de la page N° 3
FILE NO. SVM-10019 1. SAFETY PRECAUTIONS Installing, staring up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start-up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
Résumé du contenu de la page N° 4
FILE NO. SVM-10019 DANGER · FOR USE BY QUALIFIED PERSONS ONLY. · TURN OFF MAIN POWER SUPPLY BEFORE.ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. · CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED. · CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION. · DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
Résumé du contenu de la page N° 5
FILE NO. SVM-10019 CAUTION CAUTION · Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. · After unpacking the unit, examine it carefully for possible damage. Report any damages to your distributor. · Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might d
Résumé du contenu de la page N° 6
FILE NO. SVM-10019 2. SPECIFICATIONS Unit model Indoor RAS-09LKV-UL RAS-12LKV-UL Outdoor RAS-09LAV-UL RAS-12LAV-UL Cooling capacity (Btu/h) 9000 12000 Cooling capacity range (Btu/h) 3750 -10580 2750 - 13950 Heating capacity (Btu/h) 10800 14200 Heating capacity range (Btu/h) 3070 - 16350 3070 - 19000 1Ph, 60Hz, 208V/230V 1Ph, 60Hz, 208V/230V Power supply Electric Indoor Operation mode Cooling Heating Cooling Heating characteristic Running current (A) 0.22 0.20 0.25 0.23 Power consumption (W) 35 4
Résumé du contenu de la page N° 7
FILE NO. SVM-10019 2-2. Operation Characteristic Curve 8 8 RAS-12LKV-UL 7 7 RAS-09LKV-UL 6 6 RAS-12LKV-UL 5 5 4 4 RAS-09LKV-UL 3 3 Conditions Conditions o o 2 2 Indoor : DB 80 F/WB 67 F o o Indoor : DB 70 F/WB 60 F o o (DB 26.7 C/WB 19.4 C) o o (DB 21.1 C/WB 15.6 C) o o Outdoor : DB 98 F/WB 75 F o o Outdoor : DB 47 F/WB 43 F o o (DB 35 C/WB 23.9 C) o o 1 (DB 8.3 C/WB 6.1 C) 1 Indoor Air Flow : High Indoor Air Flow : High
Résumé du contenu de la page N° 8
FILE NO. SVM-10019 3. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC 6. When an air conditioning system charged with a (R410A) which does not damage the ozone layer. large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, The working pressure of the new refrigerant R410A even when refrigerant leaks, its concentration is 1.6 times higher than conventional refrigerant does not exceed the marginal level. (R22). The refrigerating o
Résumé du contenu de la page N° 9
FILE NO. SVM-10019 Table 3-2-1 Thicknesses of annealed copper pipes Thickness in. (mm) Nominal diameter (in.) Outer diameter (mm) R410A R22 1/4 6.35 0.0315 (0.80) 0.0315 (0.80) 0.0315 (0.80) 3/8 9.52 0.0315 (0.80) 0.0315 (0.80) 0.0315 (0.80) 1/2 12.70 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter
Résumé du contenu de la page N° 10
FILE NO. SVM-10019 d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare A processing correctly. Use either a flare tool for R410A or conven- tional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a con- ventional flare tool, be sure to secure “dimen- sion A” by using a gauge for size adjustment. Fig. 3-2-1 Flare processing dimensions Table 3-2-3 Dimensions related to
Résumé du contenu de la page N° 11
43 to 45 FILE NO. SVM-10019 Table 3-2-6 Flare and flare nut dimensions for R22 Dimension in. (mm) Nominal Outer diameter Thic kness Flare nut width diameter (mm) in. (mm) in. (mm) A B C D in. 1/4 6.35 0.0315 (0.8) 0.354 (9.0) 0.362 (9.2) 0.256 (6.5) 0.669 (17) 0.512 (13) 3/8 9.52 0.0315 (0.8) 0.512 (13.0) 0.531 (13.5) 0.382 (9.7) 0.787 (20) 0.866 (22) 1/2 12.70 0.0315 (0.8) 0.630 (16.0) 0.508 (12.9) 0.945 (24) 0.638 (16.2) 0.787 (20) B A C
Résumé du contenu de la page N° 12
FILE NO. SVM-10019 3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For ∅ 1/2 in. 12.7mm) copper pipe) of the refrigerant piping are lengthened. The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sl
Résumé du contenu de la page N° 13
FILE NO. SVM-10019 3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated - 14.7 Psi (–0.1 Mpa) or - 29.9 inHg (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump's power switch. Connect the charge hose to packed valve service p
Résumé du contenu de la page N° 14
FILE NO. SVM-10019 1. Be sure to make setting so that liquid can be charged. 2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon. [ Cylinder with siphon ] [ Cylinder wi
Résumé du contenu de la page N° 15
FILE NO. SVM-10019 2. Characteristics required for flux 3-5-3. Brazing • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. • Due to a wide effective temperature range, flux is hard to carbonize. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to • It is easy to remove slag after br
Résumé du contenu de la page N° 16
FILE NO. SVM-10019 4. CONSTRUCTION VIEWS 4-1. Indoor Unit – 16 –
Résumé du contenu de la page N° 17
FILE NO. SVM-10019 4-2. Outdoor Unit Unit : Inch (mm) 4-1/4 (108) 4-15/16 (125) 1 ( 25) Water Drain Outlet A 23-5/8 (600) 1-31/32 (50) R19/32 1-27/64 (36) (R15) 1/4-Hole ( 6)-Hole R19/32 (R15) 1-27/64 (36) R7/32 7/16x9/16 Oval-Hole (R5.5) 1-31/32 (50) ( 11x14) Oval Hole 1/4 Hole 23-5/8 (600) ( 6) Hole B Detail-B (Front Leg) Detail-A (Rear Leg) WIRE GUARD 17-5/32 ( 436) COVER PACKED VALVE View Z 11-7/16 (290) 3-17/32 (90) 23-5/8 (600) 13-1/2 (342) 3-17/32 (90) 2-23/32 (69) Liquid side
Résumé du contenu de la page N° 18
FILE NO. SVM-10019 5. WIRING DIAGRAM 5-1. 09LKV-UL / RAS-09LAV-UL RAS- COMPRESSOR RED P04 CN300 BLK 1 1 3 3 WHI P05 WHI 2 2 2 2 FM CM Q200~205 Q300~305 BLK P06 RED 3 3 1 1 IGBT MOS-FET P.C.BOARD R221 R321 FAN MOTOR P25 (MCC-5009) 6 6 YEL P24 R220 5 5 R320 P23 4 4 YEL P22 PMV 3 3 CN700 R219 R319 P21 2 2 BRW P20 1 1 PULSE MOTOR VALVE F03 P35 L03 C13 FUSE L01 VARISTOR YEL T3.15A 3 3 AC250V 2 P34 DB01 CN603 1 1 TS SURGE (SUCTION PIPE TEMP. SENSOR) ABSORB
Résumé du contenu de la page N° 19
FILE NO. SVM-10019 RAS-12LKV-UL /RAS-12LAV-UL COMPRESSOR RED P04 CN300 BLK 1 1 3 3 WHI P05 WHI 2 2 2 2 CM Q200~205 Q300~305 FM BLK P06 RED 3 3 1 1 IGBT MOS-FET P.C.BOARD R221 R321 FAN MOTOR P25 (MCC-5009) YEL P24 6 6 R220 R320 5 5 P23 4 4 YEL P22 3 3 PMV CN700 R219 R319 P21 2 2 BRW 1 1 P20 PULSE MOTOR VALVE P35 F03 L03 C13 FUSE L01 VARISTOR YEL 3 3 T3.15A AC250V 2 P34 DB01 CN603 1 1 TS SURGE (SUCTION PIPE TEMP. SENSOR) ABSORBER C12 C14 2 2 CN602 1
Résumé du contenu de la page N° 20
FILE NO. SVM-10019 6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit Type Specifications No. Parts name RAS-09LKV-UL AFS-220-20-4D AC240V, 20W Fan motor 1 (for indoor) RAS-12LKV-UL ICF-340U30-2 AC220V, 20W 2 Room temp. sensor (TA-sensor) ( - ) 10kW at 25°C 3 Heat exchanger temp. sensor (TC-sensor) ( - ) 10kW at 25°C 4 Louver motor MP24Z3T Output (Rated) 1W, 16 poles, DC12V 6-2. Outdoor Unit Model name No. Parts name Rating 1 Reactor CH