Résumé du contenu de la page N° 1
®
BACnet Option Module
Instruction Manual
TR200
Literature Order Number BAS-SVX24A-EN
Date June 2009
Supersedes
www.trane.com
Trane has a policy of continous product and product data improvement and reserves the right to
For more information, contact your local Trane
office or e-mail us at comfort@trane.com change design and specifications without notice.
November
Résumé du contenu de la page N° 2
Table of Contents 1-1 Safety Copyright, limitation of liability and revision rights 1-1 High Voltage Warning 1-3 Before Commencing Repair Work 1-8 Special Conditions 1-8 2-1 Introduction 2-1 Introduction 3-1 How to Install 3-1 The BACnet Option 3-5 System Specifications 4-1 How to Configure the System 4-1 Configuring BACnet 4-2 BIBBs 4-3 Example of a simple set-up of BACnet 5-1 How to Control the Adjustable Frequency Drive Network Adjustable Frequency Drive Control Inputs and Out- 5-2 puts 5-15
Résumé du contenu de la page N° 3
7-4 LED Status -2 TR200 BACnet
Résumé du contenu de la page N° 4
Safety Copyright, limitation of liability and revision rights This publication contains information proprietary to Trane. By accepting and using this manual, the user agrees that the information contained herein will be used solely for operating equipment from Trane or equipment from other vendors provided that such equipment is intended for communication with Trane equipment over a serial communication link. This publication is protected under the copyright laws of most countries. Trane does n
Résumé du contenu de la page N° 5
Safety Warnings, Cautions and Notices Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property damage-only accidents. Your personal safety and the proper ope
Résumé du contenu de la page N° 6
Safety High Voltage Warning WARNING The voltage of the adjustable frequency drive is dangerous whenever it is connected to line power. Incorrect installation of the motor or adjustable frequency drive could result indeath, serious injury or damage to the equipment. Conse- quently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations. Safety Note WARNING The voltage of the adjustable frequency drive is dangerous whenever conne
Résumé du contenu de la page N° 7
Safety Installation at high altitudes WARNING Installation at high altitude: 380–500 V, enclosure A, B and C: At altitudes above 6,561 ft [2 km], please contact Trane regarding PELV/Class II. 380–500 V, enclosure D, E and F: At altitudes above 9,842 ft [3 km], please contact Trane regarding PELV/Class II. If the drive is to be installed over 6,561 ft [2 km] altitude, then the PELV specifications are not fulfilled anymore, i.e., the distances between components and critical parts become too small
Résumé du contenu de la page N° 8
Safety Voltage (V) Min. Waiting Time (Minutes) 4 15 20 30 40 200 - 240 1.5–5 hp 7.5–60 hp [1.1–3.7 kW] [5.5 –45 kW] 380 - 480 1.5–10 hp 15–125 hp 150–350 hp 450–1350 hp [1.1–7.5 kW] [11–90 kW] [110–250 kW] [315–1000 kW] 525-600 1.5–10 hp 15–125 hp [1.1–7.5 kW] [11–90 kW] 525-690 15–125 hp 60–550 hp 600–1875 hp [11–90 kW] [45–400 kW] [450–1400 kW] Be aware that there may be high voltage on the DC link even when the LEDs are turned off. TR200 BACnet 1-5
Résumé du contenu de la page N° 9
Safety Safety Precautions WARNING The voltage of the adjustable frequency drive is dangerous whenever connected to line power. Incorrect installation of the motor, adjustable frequency drive or serial communication bus could cause death, serious personal injury or damage to the equipment. Consequently, the instructions in this manual, as well as national and local rules and safety regula- tions, must be complied with. WARNING Safety Regulations 1. The line power supply to the adjustable frequenc
Résumé du contenu de la page N° 10
Safety Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout pro- cedures to ensure the power cannot be inadvertently energized. Failure to follow recommendations could result in death or serious injury. 1. Control signals from, or internally within, the adjustable frequency drive may in rare cases be activated in error, be delayed or fail to occur entirely. When used in situations where safety is critical, e.g., when con- trolling the electro
Résumé du contenu de la page N° 11
Safety Before Commencing Repair Work WARNING Hazardous Voltage! 1. Disconnect the adjustable frequency drive from line power. 2. Disconnect DC bus terminals 88 and 89 3. Wait at least the time mentioned above in the section General Warning. 4. Remove motor cable Failure to follow recommendations could result in death or serious injury. Special Conditions Electrical ratings: The rating indicated on the nameplate of the adjustable frequency drive is based on a typical 3-phase line power supply w
Résumé du contenu de la page N° 12
Introduction Introduction About this Manual First time users can obtain the most essential information for quick installation and set-up in these chapters: Introduction How to Install How to Configure the System Application Example For more detailed information including the full range of set-up options and diagnosis tools, refer to the chapters: How to Control the TR200 How to Access TR200 Parameters Parameters Troubleshooting Technical Overview BACnet (Building Automation and Control Network
Résumé du contenu de la page N° 13
Introduction Background information Protocol name: BACnet Technology developer: ASHRAE Year introduced: 1995 Governing standards: ANSI/ASHRAE Standard 135-2004, ISO 16484-5 Openness: Open specification Physical characteristics Network topology: Bus Physical media: Shielded twisted pair Max. Distance at low speed: 3937 ft [1200 m] Transport mechanism Communication methods: Master/slave Baud Rates Supported: 9600, 19200, 38400, 76800 Termination: 120 ohm 2-2 TR200 BACnet
Résumé du contenu de la page N° 14
Introduction Assumptions This manual assumes you are using a Trane BACnet Option Card in conjunction with a Trane TR200 series adjustable frequency drive. It is also assumed that your master is a BMS or PC equipped with a serial commu- nication card supporting all the BACnet communication services required by your application, and that all requirements stipulated in the BACnet standard, as well as those pertaining to the Variable Frequency Drive are strictly observed as well as all limitations t
Résumé du contenu de la page N° 15
Introduction Abbreviations ACI Acyclical Control Interval PCD Process Data AOC Application Orientated Controller PCA Parameter Characteristics AV Analog Variable PCV Parameter-Characteristics-Value BMS Building Management System PDU Protocol Data Unit BV Binary Variable PELV Protected Extra Low Voltage CAN Controller Area Network PLC Programmable Logic Control CTW Control Word PNU Parameter Number EE- Electrical Erasable Programmable Read Only PVA Parameter Value PROM Memory EIA Electronic Indus
Résumé du contenu de la page N° 16
How to Install The BACnet Option Installation of the Option Items required to install a serial communication bus option in the adjustable frequency drive: - The serial communication bus option - Serial communication bus option adaptor frame for the adjustable frequency drive. This frame is deeper than the standard frame, to allow space for the serial communication bus option beneath. - Cable holders TR200 BACnet 3-1
Résumé du contenu de la page N° 17
How to Install Instructions: - Remove the keypad panel from the adjustable frequency drive. - Remove the frame located beneath and discard. - Push the option into place. Two positions are possible, with cable terminal facing either up or down. The cable up position is often most suitable when several adjustable frequency drives are installed side by side in a rack, as this position permits shorter cable lengths. - Push the serial communication bus option adaptor frame for the adjustable frequenc
Résumé du contenu de la page N° 18
How to Install The length statements in the tables above are valid for bus cable with the following properties: - Impedance: 135 to 165 Ohm at a measuring frequency from 3 to 20 MHz - Resistance: <110 Ohm/km - Capacitance: <30 pF/m - Damping: max. 9 dB over the whole wire length - 2 2 Cross section: max. 0.00053 in [0.34 mm ], corresponding to AWG 22 - Cable type: twisted in pairs, 1 x 2, or 2 x 2, or 1 x 4 wires - Shielding: Copper-braided shield or braided shield and foil shield Use of the sam
Résumé du contenu de la page N° 19
How to Install Network Termination Connecting the Bus Line Connect the BACnet Option Card to the bus line via terminals 62, 63 and 66. Terminal 62 is marked red and Terminal 63 is marked green. These two are the RS485 lines. Terminal 66 the signal ground for the RS485 transmitter. Maximum Cable Lengths Maximum total bus cable length: 4000 ft [1200 m] 3-4 TR200 BACnet
Résumé du contenu de la page N° 20
How to Install Cable Routing The BACnet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the other. Normally a distance of 7.9 in (200 mm) is sufficient, but maintaining the greatest possible distance between cables is generally recommended, especially where cables run in parallel over long distances. When crossing is unavoidable, the BACnet cable must cross motor and brake resistor cables at an angle of 90 deg