Résumé du contenu de la page N° 1
®
ALTIVAR 58 TRX
AC DRIVES
File 8806 / 8839 / 8998
Catalog
03
CONTENTS
Description Page
Drives Product Support and Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
®
Altivar 58 TRX AC Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Class 8839 58M Enclosed AC Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Class 8839 Econoflex™ AC Drives. . . . . . . . . . . . . . . . . . . . . .
Résumé du contenu de la page N° 2
DRIVES PRODUCT SUPPORT AND CONTACTS Drives Product Support Group Customer Information Center The Product Support Group is available 24 Serving all Square D authorized distributors hours a day, 365 days a year. We will work with and customers in the U.S., Monday through you over the telephone to diagnose application Friday, 8:00 a.m. to 8:00 p.m. EST. or product problems and to advise the correct course of action. Telephone: 888-SquareD (1-888-778-2733) Telephone: 919-266-8600 Fax: 919-217-650
Résumé du contenu de la page N° 3
® Altivar 58 TRX AC Drives Contents DESCRIPTION PAGE PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 USER INTERFACE OPTIONS AND ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ATV58 TRX TYPE H DRIVE CONTROLLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 ATV58 TRX TYPE E DRIVE CONTROLLERS . . . . . . . . . . . . . . . . . . . . . . . . . . .
Résumé du contenu de la page N° 4
® Altivar 58 TRX AC Drives Product Overview PRODUCT OVERVIEW ® Altivar 58 (ATV58) TRX AC drive controllers offer superior performance in a compact package. ATV58 TRX drive controllers are designed for modularity, allowing you to customize the product to your exact needs. A variety of multilingual operator interface options, I/O extension cards, communication cards, and hardware options are available. ATV58 TRX drive controllers incorporate sensorless flux vector control for three-phase as
Résumé du contenu de la page N° 5
® Altivar 58 TRX AC Drives User Interface Options and Accessories USER INTERFACE OPTIONS AND ACCESSORIES Keypad Display The operator keypad display can be mounted directly to the drive or connected via a remote mounting kit. It can be used to operate the drive, or to display, configure, and adjust parameters. It can also be used to upload and download configurations. Keypad Display (Left) and Remote Mounting Kit (Right) PowerSuite™ Software ® This Windows -based PC and Pocket PC software c
Résumé du contenu de la page N° 6
® Altivar 58 TRX AC Drives User Interface Options and Accessories Ventilation Kits Ventilation fan kits are available for packaging the drive in a smaller enclosure. The ventilation fan is powered internally and mounts on top of the ATV58 TRX drive controller without requiring additional panel space. Ventilation Kits Conduit Entrance Kits Conduit entrance kits are available for wall-mount applications. The kits attach to the bottom of the ATV58 TRX drive controller and are provided with m
Résumé du contenu de la page N° 7
® Altivar 58 TRX AC Drives Type H Drive Controllers ATV58 TRX TYPE H DRIVE CONTROLLERS Features The ATV58 TRX Type H drives are used for controlling three-phase asynchronous motors ranging from: 1 to 350 hp CT (1 to 500 hp VT), 400/460 Vac, three-phase input 0.5 to 7.5 hp CT (0.5 to 30 hp VT), 208/230 Vac, single-phase input 2 to 40 hp CT (2 to 50 hp VT), 208/230 Vac, three-phase input The ATV58 TRX Type H drive controller uses the latest in AC drive technology. Power modules are used
Résumé du contenu de la page N° 8
® Altivar 58 TRX AC Drives Type H Drive Controllers Ratings ATV58 TRX Type H drive controllers may be rated for constant torque (CT), variable torque (VT), and variable torque low noise (VTLN) applications. CT applications usually require 100% of motor-rated torque through the entire speed range, high transient torque capability, and speed regulation. VT applications, such as centrifugal fans and centrifugal pumps, do not require high transient torque capability. This typically allows a
Résumé du contenu de la page N° 9
® Altivar 58 TRX AC Drives Type H Drive Controllers Ratings for ATV58 TRX Type H Constant Torque 208/230 Vac, 3-Phase Input with 3-Phase Output Switching Frequency: ATV58HU29M2–D23M2 at 4 kHz, ATV58HD28M2–D46M2 at 2 kHz Motor Power Rated Transient Total Dissipated Drive Controller 208/230 V Output Current Output Current Power at Rated Load Frame Size ▼ Catalog Number kW HP A A W 2 ATV58HU29M2ZU 1.5 2 7.8 10.6 107 2 ATV58HU41M2ZU 2.2 3 11 15 160 3 ATV58HU54M2ZU 3 4 13.7 18.6 190 3 ATV58HU72M
Résumé du contenu de la page N° 10
® Altivar 58 TRX AC Drives Type H Drive Controllers Ratings for ATV58 TRX Type H Constant Torque 400 /460 Vac, 3-Phase Input with 3-Phase Output Switching Frequency: ATV58HU18N4–D46N4 at 4 kHz, ATV58HD54N4–D79N4 at 2 kHz Motor Power Rated Transient Total Dissipated Drive Controller 400/460 Vac Output Current Output Current Power at Rated Load Frame Size ▼ Catalog Number kW HP AAW 2 ATV58HU18N4ZU 0.75 1 2.3 3.1 57 2 ATV58HU29N4ZU 1.5 2 4.1 5.6 97 2 ATV58HU41N4ZU 2.2 3 5.8 7.9 120 3 ATV58HU54N
Résumé du contenu de la page N° 11
® Altivar 58 TRX AC Drives Type H Drive Controllers Ratings for ATV58 TRX Type H Variable Torque 400/460 Vac, 3-Phase Input with 3-Phase Output Switching Frequency: ATV58HU18N4–D23N4 at 8 kHz, ATV58HD28N4-D46N4 at 4 kHz, ATV58HD54N4–C33N4X at 2 kHz Motor Power Rated Transient Total Dissipated Drive Controller 400/460 Vac Output Current Output Current Power at Rated Load Frame Size ▼ Catalog Number kW HP A A W 2 ATV58HU18N4ZU 0.75 1 2.1 2.3 57 2 ATV58HU29N4ZU 1.5 2 3.4 3.7 97 2 ATV58HU41N4ZU
Résumé du contenu de la page N° 12
® Altivar 58 TRX AC Drives Type E Drive Controllers ATV58 TRX TYPE E DRIVE CONTROLLERS The ATV58 TRX family of adjustable-frequency AC drive controllers is used to control three-phase asynchronous motors. The ATV58 TRX Type E model contains an ATV58 TRX Type H drive controller packaged in a compact, Type 1 enclosure. It is for use in mechanical rooms, OEM equipment, and factory floor applications. The following Type E drive controller models are available: 1 to 7½ hp (0.75 to 5.5 kW), 40
Résumé du contenu de la page N° 13
® Altivar 58 TRX AC Drives Type F Drive Controllers ATV58 TRX TYPE F DRIVE CONTROLLERS The ATV58 TRX family of adjustable-frequency AC drive controllers is used to control three-phase asynchronous motors. ATV58 TRX Type F models contain an ATV58 TRX Type H drive controller packaged in a compact Type 12 enclosure. They are for use in mechanical rooms, OEM equipment, and factory floor applications requiring a local load break switch and input line fusing. The following models are available:
Résumé du contenu de la page N° 14
® Altivar 58 TRX AC Drives Type N Drive Controllers ATV58 TRX TYPE N DRIVE CONTROLLERS The ATV58 TRX family of adjustable-frequency AC drive controllers is used to control three-phase asynchronous motors.The ATV58 TRX Type N models contain an ATV58 TRX Type H drive controller packaged in a Type 4/4x stainless steel enclosure. They are for use in food and beverage wash-down applications. The Type N drive controller was tested for corrosion resistance per UL-50 and exceeds this standard. Th
Résumé du contenu de la page N° 15
® Altivar 58 TRX AC Drives Type FVC Drive Controllers ATV58 TYPE FVC DRIVE CONTROLLERS Features The ATV58 Type FVC family of adjustable frequency AC drive controllers are used for controlling three-phase asynchronous motors ranging from 1 to 75 hp (constant torque), 400/460 Vac, 3-phase input. The ATV58 TRX operator interfaces, configuration tools, I/O extension options, and communication options are shared throughout the product range, except the general purpose option card which is not
Résumé du contenu de la page N° 16
® Altivar 58 TRX AC Drives Type FVC Drive Controllers Applications The ATV58 Type FVC product is recommended in place of the ATV58 TRX Type H drive controllers in the following applications: Applications that require encoder feedback and the installation of an I/O extension card or a communication card Applications that require PID regulation of a process loop Applications requiring improved open loop torque performance at low speed Applications requiring high torque performance at
Résumé du contenu de la page N° 17
® Altivar 58 TRX AC Drives Type FVC Drive Controllers Ratings Ratings for ATV58 Type FVC Constant Torque 400 /460 Vac, 3-Phase Input with 3-Phase Output Switching Frequency: ATV58FHU18N4–D46N4 at 4 kHz, ATV58FHD54N4–D79N4 at 2 kHz Motor Power Rated Transient Total Dissipated Drive Controller 400/460 Vac Output Current Output Current Power at Rated Load Frame Size Catalog Number kW HP A A W 2 ATV58FHU18N4KU 0.75 1 2.3 3.1 57 2 ATV58FHU29N4KU 1.5 2 4.1 5.6 97 2 ATV58FHU41N4KU 2.2 3 5.8 7.9 1
Résumé du contenu de la page N° 18
® Altivar 58 TRX AC Drives Terminal Locations for Type H and Type FVC Drives TERMINAL LOCATIONS FOR ATV58 TRX TYPE H AND TYPE FVC DRIVES NOTE: These illustrations show the locations of the major terminal groups. Control Terminals Ground Terminal Ground Terminal Control Terminals Ground Terminal Power Terminals Power Terminals Power Terminals Control Terminals Frame Size 1 Frame Sizes 2 and 3 Frame Sizes 4 and 5 Control Terminals Control Terminals Power Terminals Power Terminals Ground Termin
Résumé du contenu de la page N° 19
® Altivar 58 TRX AC Drives Terminal Locations for Type H and Type FVC Drives TERMINAL LOCATIONS FOR ATV58 TRX TYPE H DRIVES Control Terminals Ground Terminals Control Terminals R/L1 S/L2 T/L3 Power Terminals PB PA PC P0 PA PA PO PC PB U/T1 V/T2 W/T3 Power Terminals R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Ground Terminals Frame Size 8 Frame Size 9 Control Terminals Ground Terminals R/L1 S/L2 T/L3 PC PB PO PA PA U/T1 V/T2 W/T3 Power Terminals Frame Size 10 19 © 2000–2003 Schneider Electric All Rights Rese
Résumé du contenu de la page N° 20
® Altivar 58 TRX AC Drives Description of Power Terminals DESCRIPTION OF POWER TERMINALS As shown in the drawing to the left, the ATV58 TRX power terminal arrangements differ from model to model. The locations of the power terminals are shown on pages 18–19. The following tables describe the characteristics of the power terminals and list maximum wire sizes and tightening torques for the various ATV58 TRX models. ATV58*U09M2 - U18M2 L1 L2 + – U V W ATV58*U29M2 - D12M2 Function of Power T