Résumé du contenu de la page N° 1
CANADIAN GAS ASSOCIATION
58MXA
4-Way Multipoise Fixed-Capacity
Direct-Vent Condensing Gas Furnace
Visit www.carrier.com
Service and Maintenance Instructions
→ For Sizes 040—140, Series 130
®
ama
A93040
APPROVED
R
NOTE: Read the entire instruction manual before performing any
service or maintenance.
This symbol → indicates a change since the last issue.
Index Page
As an ENERGY STAR®
SAFETY CONSIDERATIONS..................................................1-2
Partner, Carrier Corporation
has det
Résumé du contenu de la page N° 2
GENERAL These instructions are written as if the furnace is installed in an The ability to properly perform maintenance on this equip- upflow application. An upflow furnace application is where the ment requires certain expertise, mechanical skills, tools, and blower is located below the combustion and controls section of the equipment. If you do not possess these, do not attempt to furnace, and conditioned air is discharged upward. Since this perform any maintenance on this equipment other than
Résumé du contenu de la page N° 3
WASHABLE
FILTER FILTER
RETAINER WASHABLE
FILTER FILTER
FILTER
RETAINER SUPPORT A93046 A93045 Fig. 3—Bottom Filter Arrangement Fig. 4—Filter Installed for Side Inlet Step 1—Cleaning and/or Replacing Air Filter All factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their The air filter arrangement may vary depending on the application length and routing. or orientation. 4. Position control box, transformer, and door switch assembly t
Résumé du contenu de la page N° 4
11. Reinstall condensate trap and tubing if previously removed. 5. Remove wires from gas valve. Note location for reassembly. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 8 or tubing diagram on main furnace door for proper tube location. Label all wires prior to disconnection when servicing con- (1.) Connect 1 tube (blue or blue and white striped) from trols. Wiring errors can cause improper and dangerous collector box. operation. (2.) Co
Résumé du contenu de la page N° 5
PRIMARY HX
INLET OPENINGS Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death. 19. Replace main furnace door. Step 4—Cleaning Heat Exchangers The following items should be performed by a qualified service technician. PRIMARY HEAT EXCHANGERS If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the f
Résumé du contenu de la page N° 6
TUBE ROUTING Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below. Condensate Trap on LEFT Condensate Trap; Factory Installed Tube location when used in UPFLOW application Side Optional in Blower Shelf BURNER ENCLOSURE BURNER ENCLOSURE (Blower access panel removed) PRESSURE REFERENCE PRESSURE REFERENCE TUBE ASSEMBLY TUBE ASSEMBLY CAP CAP COLLECTOR BOX TUBE (PINK) PLUG PLUG COLLECTOR BOX TUBE COLLECTOR BOX TUBE (PINK) COLLECTO
Résumé du contenu de la page N° 7
4. Disconnect pressure switch tubes. 14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and → 5. Disconnect vent pipe from inducer housing outlet by loosen- condensate trap to ensure no condensate leaks occur. If leaks ing coupling clamp on inducer outlet. are found, correct the problem. 6. Disconnect drain tube from inducer housing. (See Fig. 8.) 15. Check for gas leaks. 7. Remove inducer housing assembly by removing 4 bolts attach
Résumé du contenu de la page N° 8
10. Replace main furnace door. The control center stores 1 status code (representing the last fault to occur) for a period of 48 hr or until the 115- or 24-v power is Step 7—Electrical Controls and Wiring interrupted. NOTE: Removing blower access panel will open blower access panel door switch and terminate 115-v power to control center. The status code will be erased. Look into blower access panel sight There may be more than 1 electrical supply to the unit. Check glass for current LED status B
Résumé du contenu de la page N° 9
BLOWER OFF DELAY
ADJUSTMENT SWITCH 24V THERMOSTAT
G
TERMINALS R
Y
W TEST/TWIN HUMIDIFIER TERMINAL
Com
24V
(24-VAC 0.5 AMP MAX)
HUM LED OPERATION &
STATUS LIGHT HARNESS CONNECTOR SEC-1 24V TRANSFORMER SEC-2 3-AMP FUSE SPARE 1 COOL BLOWER SPEED
HEAT SELECTION TERMINALS SPARE 2 EAC 1 (BLACK) EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX) 115-VAC (L1)
EAC 2 (WHITE) POWER
115-VAC (L2) NEUTRAL
SUPPLY CONNECTION HOT SURFACE
INDUCER MOTOR
IGNITOR
CONNECTOR CONNECTOR A93052
Résumé du contenu de la page N° 10
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc. 2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape. 3. Check that heat tape power supply circuit is on. Step 10—Winterizing 32°F MINIMUM INSTALLED
Freezing condensate left in the furnace will damage the AMBIENT OR FREEZE
PROTECTION REQUIRED equipment. If the furnace will be off for an extended period of time in a structure w
Résumé du contenu de la page N° 11
TO 115VAC FIELD DISCONNECT SCHEMATIC DIAGRAM (WHEN USED) SW2 G NOTE #4 LGPS BLOWER PRS NEUTRAL R (NATURAL GAS & PROPANE) PCB SEE NOTE #10 OFF L1 Y GND EQUIPMENT GROUND ORN DELAY W SW1 (NOT ON ALL MODELS) L2 COM ILK LO HUM BLOWER OFF DELAY SPARE-2 MED LO SELECTION CHART TEST/TWIN NOTE #6 YEL HEAT MED HI LED L1 90 SEC BLU HI START SPARE-1 HI/LO OL NOTE #8 135 SEC BLWR RED RED 1-M 3-P COOL CAP-1 COM PL1 180 SEC 32 1 LS FRS COM GV BLWM EAC-1 WHT 6 4 225 SEC 5 FSE WHT HSIR 9 87 2-C EAC-2 RED GRN 1 G
Résumé du contenu de la page N° 12
TEST STATUS 3 2 1 6 5 4 9 7 8 SERVICE If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code. LED CODE STATUS CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24V power. RAPID FLASHING - Line voltage (115V) polarity reversed. If twinned, refer to twinning kit instructions. EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIR
Résumé du contenu de la page N° 13
13 → Troubleshooting Guide START NO NO NO Is red LED status light on? Is there 115v at L1 and L2? Is door switch closed? Close door switch and go to start. YES YES YES NO NO NO Is there 24v at SEC-1 and SEC-2? Is there 115v going to switch? Is circuit breaker closed? YES YES YES Replace control center. Replace door switch. Close circuit breaker and go back to start. Replace transformer. Check for continuity in wire from circuit Is red LED status light blinking Check for correct line voltage brea
Résumé du contenu de la page N° 14
14 31 PRESSURE SWITCH WILL NOT CLOSE OR REOPEN - If 11 NO PREVIOUS FAULT - Faults open longer than 5 minutes, Unplug ignitor harness from control are erased after 48 hrs or inducer shuts off for 15 minutes center and inititate another whenever power (115v or 24v) is before retry. component test sequence. Check NO Replace control center. interrupted. Run system through Check for: for 115v between pins 1 and 2 on a heating or cooling cycle to • Proper vent sizing or pitch or the control center.
Résumé du contenu de la page N° 15
15
Résumé du contenu de la page N° 16
SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean