Résumé du contenu de la page N° 1
www.regency-fi re.com
P121 / P121LC / P121RC / P131
Owners &
Zero Clearance Direct Vent Gas Fireplace
Installation Manual
STYLE MODEL
See Thru P121-NG2 Natural Gas P121-LP2 Propane
Left Corner P121LC-NG2 Natural Gas P121LC-LP2 Propane
Right Corner P121RC-NG2 Natural Gas P121RC-LP2 Propane
Pier P131-NG2 Natural Gas P131-LP2 Propane
WARNING:
FOR YOUR SAFETY
If the information in these instructions are not followed exactly, a
What to do if you smell gas:
fi
Résumé du contenu de la page N° 2
To the New Owner: Congratulations! ® You are the owner of a state-of-the-art Gas Fireplace by REGENCY . The P121 / P121LC / P121RC / P131 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P121 / P121LC / P121RC / P131 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many tro
Résumé du contenu de la page N° 3
TABLE OF CONTENTS SAFETY LABEL OPERATING INSTRUCTIONS Serial No. Decal ............................................................4 Operating Instructions .................................................34 Lighting Procedure ......................................................34 Shutdown Procedure ...................................................34 REQUIREMENTS First Fire ......................................................................34 Aeration Adjustment .........................
Résumé du contenu de la page N° 4
SAFETY LABEL This is a copy of the label that accompanies each P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open. ® NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one. For the State of Massachusetts, in
Résumé du contenu de la page N° 5
REQUIREMENTS MA Code - CO Detector 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, includ
Résumé du contenu de la page N° 6
INSTALLATION IMPORTANT MESSAGE GENERAL SAFETY INSTALLATION INFORMATION CHECKLIST SAVE THESE INSTRUCTIONS 1) The appliance installation must conform with local codes or, in the absence of Note: These units are The Panorama P121/P121LC/P121RC/P131- local codes, with the current Canadian or non-load bearing. NG1 or P121/P121LC/P121RC/P131-LP1 Direct National Gas Codes, CAN1-B149 or ANSI Vent Fireplace must be installed in accordance Z223.1 Installation Codes. with these instructions. Ca
Résumé du contenu de la page N° 7
INSTALLATION SPECIFICATIONS P121-2 See Thru Note: These units are non-load bearing. P131-2 Pier ® Regency P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace 7
Résumé du contenu de la page N° 8
INSTALLATION P121LC-2 Left Corner Unit Note: These units are non-load bearing. P121RC-2 Right Corner Unit ® 8 Regency P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Résumé du contenu de la page N° 9
INSTALLATION LOCATING YOUR A) P121-2 See Thru GAS FIREPLACE 1) When selecting a location for your fi replace, ensure that the clearances are met as outlined in the "Clearances" section. 2) Provide adequate clearances for servicing. 3) The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. If the appliance is going to be installed on carpeting, combustible linoleum ti
Résumé du contenu de la page N° 10
INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams in the "Locating Your Fireplace" section): Clearance to Combustibles from: Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm) CAUTION REQUIREMENTS: The top, back and sides of the fi replace are defi ned by standoffs. WARNING: The metal ends of the standoffs may NOT be recessed into combustible construction. Fire hazard is an extreme risk if these clearances (air space) Determine
Résumé du contenu de la page N° 11
INSTALLATION FRAMING AND FINISHING 1) For ease of installation, frame your fi replace after it is positioned and Framing Dimensions the vent system is installed. Remember to install the top standoffs. See the "Unit Assembly Prior to Installation" section. Use 2x4's and P121-2 (See Thru) P131-2 (Pier) P121LC-2 / P121RC-2 frame to local building codes. (Corner Unit) A 25"(635mm) 25"(635mm) 26-13/16" CAUTION: Verify your fi replace dimensions, framing methods and minus two times
Résumé du contenu de la page N° 12
INSTALLATION Facing & Finishing Requirements This fi replace is supplied with a 3" metal extension trim above the fi replace. The extension trim may be replaced if the framing is faced with a non- combustible material placed fl ush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.) UNIT ASSEMBLY VENTING PRIOR TO INTRODUCTION INSTALLATION The P121-2/P121LC-2/P121RC-2/P131-2 uses the "balanced fl ue" technology Co -Axial system. The 4 Top
Résumé du contenu de la page N° 13
INSTALLATION EXTERIOR VENT TERMINATION LOCATIONS ® Regency P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace 13 Minimum Vent Height Roof Pitch B-Vent Only: If vent is less than 10 ft. Feet Meters (3m) from wall - locate rain cap not less flat to 7/12 2 0.61 than 2 ft. (600mm) above wall. over 7/12 to 8/12 2 0.61 over 8/12 to 9/12 2 0.61 over 9/12 to 10/12 2.5 0.76 over 10/12 to 11/12 3.25 0.99 G over 11/12 to 12/12 4 1.22 over 12/1
Résumé du contenu de la page N° 14
INSTALLATION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI. ® Description Simpson Dura-Vent Selkirk Amerivent Security ® TM ® Direct VentGS Direct-Temp Direct Vent Secure Vent 6" Pipe Length, Galvanized 908 4DT-6 N/A SV4L6 6" Pipe Length, Black 908B 4DT-6B N/A SV4LB6 7" Pipe Length, Galvanized N/A N/A 4D7 #N/A 7" Pipe Length, Black
Résumé du contenu de la page N° 15
INSTALLATION VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS ® Regency Direct Vent System (Flex) Horizontal Terminations Only These venting systems, in combination with the P121-2/P121LC-2/P121RC-2/P131-2 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent Termination Locations" section. ® Regency Direct Vent (Flex)
Résumé du contenu de la page N° 16
INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations The minimum components required for a basic horizontal termination are: 1 Simpson Duravent Adaptor 1 Horizontal Termination Cap o 1 45 Elbow 1 Rigid Pipe Adaptor Vertical 1 Wall Thimble Terminal 1 Length of pipe to suit wall thickness Storm Collar (see chart) Part # 953 Vinyl Siding Wall thickness is measured from the back standoffs to the inside Standoff (Optional) (Part #950) mounting surface of termination
Résumé du contenu de la page N° 17
INSTALLATION RIGID PIPE VENTING ARRANGEMENTS HORIZONTAL TERMINATIONS REGENCY DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas) o o o The diagram below shows examples of horizontal termination arrangements using one, two, or three 90 elbows (two 45 elbows equal one 90 elbow). Note: All Rigid Pipe Systems o 1) A maximum of three 90 elbows are permitted. 4" inner diameter 2) Minimum distance between elbows is 1 ft. (305mm). 6-5/8" outer diameter • Maintain clearances to combustibles as listed
Résumé du contenu de la page N° 18
INSTALLATION o o Horizontal Venting with Three (3) 90 Elbows Horizontal Venting with Two (2) 90 Elbows Option V H H + H1 + H2 Option V H + H1 A) 2' (610mm) Min. 1' (305mm) Max. 3'(914mm) Max. A) 1' (305mm) Minimum 2' (610mm) Maximum B) 3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max. B) 2' (610mm) Minimum 5' (1.5m) Maximum C) 4' (1.22mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. C) 3' (914mm) Minimum 8' (2.4m) Maximum D) 5' (1.5m) Min. 7' (2
Résumé du contenu de la page N° 19
INSTALLATION RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS (Propane & Natural Gas) • Vent must be supported at offsets • Maintain clearances to combustibles as listed in the "Clearances" section. • Firestops are required at each fl oor level and whenever passing through a wall. • Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part# 510-994). The P121-2/P121LC-2/P121RC-2/P131-2 is approved for a maximum 35 ft. (10.7m) straight vertical, with rigid pipe vent sys
Résumé du contenu de la page N° 20
INSTALLATION o o Vertical Venting with Two (2) 90 Elbows Vertical Venting with Two (2) 90 Elbows Option V H + H1 Option V + V1 H A) 1' (305mm) Minimum 2' (610mm) Maximum A) 1' (305mm) Minimum 4' (1.22m) Maximum B) 2' (610mm) Minimum 4' (1.22m) Maximum B) 2' (610mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 9' (2.7m) Maximum D) 4' (1.22m) Minimum 8' (2.4m) Maximum D) 4' (1.22m) Minimum