Résumé du contenu de la page N° 1
Models:
Installers Guide
QV32-A
QV36-A
Underwriters
Laboratories Listed
READ THIS MANUAL BEFORE INSTALLING OR
OPERATING THIS APPLIANCE. THIS INSTALLERS
WARNING: IF THE INFORMATION
GUIDE MUST BE LEFT WITH APPLIANCE FOR
FUTURE REFERENCE.
IN THESE INSTRUCTIONS IS NOT
FOLLOWED EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUS-
WARNING: IMPROPER INSTALLA-
ING PROPERTY DAMAGE, PER- TION, ADJUSTMENT, ALTERATION,
SONAL INJURY, OR DEATH. SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAM-
- Do not store
Résumé du contenu de la page N° 2
SAFETY AND WARNING INFORMATION These units MUST use one of the vent systems READ and UNDERSTAND all instructions carefully described in the Installing the Fireplace section of ! ! before starting the installation. FAILURE TO the Installers Guide. NO OTHER vent systems or FOLLOW these installation instructions may result components MAY BE USED. in a possible fire hazard and will void the warranty. This gas fireplace and vent assembly MUST be Prior to the first firing of the fireplace, READ the !
Résumé du contenu de la page N° 3
TABLE OF CONTENTS Safety and Warning Information .......................................................... 2 u Service Parts Lists .................................................................................. 4 Section 1: Approvals and Codes ........................................................... 8 Appliance Certification ............................................................................... 8 Installation Codes .................................................................
Résumé du contenu de la page N° 4
Service Parts u QV32-A (NG, LP) Exploded Parts Diagram / Vue éclatée des pièces 4 1 5 2 7 6 16 8 Log Set Assembly 3 12 9 13 11 10 14 15 Part number list on following page. * La liste des numéros de pièce se trouve * à la page suivante. 4
Résumé du contenu de la page N° 5
QV32-A (NG, LP) Service Parts List / Liste des pièces de rechange IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts. / IMPORTANT : L'information fournie dans cette brochure n'est valide que pendant une courte période. Les sites VIP des distributeurs disposent des renseignements les plus récents. Lors d'une commande, veuillez fournir les numéros de série et de modè
Résumé du contenu de la page N° 6
Service Parts u QV36-A (NG, LP) Exploded Parts Diagram / (GN, PL) Vue éclatée des pièces 4 1 2 16 5 6 7 8 Log Set Assembly 3 9 12 14 15 Part number list on following page. 11 * 13 La liste des numéros de pièce se trouve à la 10 * page suivante. 6
Résumé du contenu de la page N° 7
QV36-A (NG, LP) Service Parts List / Liste des pièces de rechange IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When order- ing, supply serial and model numbers to ensure correct service parts. / IMPORTANT : L'information fournie dans cette brochure n'est valide que pendant une courte période. Les sites VIP des distributeurs disposent des renseignements les plus récents. Lors d'une commande, veuillez fournir les numéros de série et de m
Résumé du contenu de la page N° 8
Approvals and Codes Appliance Certification High Altitude Installations The Village Collection fireplace models discussed in this U.L. Listed gas fireplaces are tested and approved for Installers Guide have been tested to certification standards elevations from 0 to 2,000 feet in the U.S.A. and from 0 to and listed by the applicable laboratories. 4,500 feet in Canada. When installing this fireplace at an elevation above 2,000 feet (in the United States), it may be necessary to decrease Certifica
Résumé du contenu de la page N° 9
Getting Started Introducing the Village Collection The Aladdin Hearth Products Warranty will be voided by, and Aladdin Hearth Products disclaims any responsibility Gas Fireplaces for, the following actions: The Village Collection direct vent gas fireplaces are designed • Installation of any damaged fireplace or vent system to operate with all combustion air siphoned from outside of component. the building and all exhaust gases expelled to the outside. • Modification of the fireplace or direct ve
Résumé du contenu de la page N° 10
30 3/4 (781mm) 15 3/8 (390mm) 16 1/4 (413mm) 8 3/4 (222mm) 6 5/8 (168mm) DIAMETER VENT COLLARS 8 5/8 (219mm) DIAMETER VENT GAS COLLARS LINE ACCESS ELECTRICAL ACCESS 37 3/4 34 1/2 22 (960mm) (876mm) (560mm) 26 7/8 (683mm) 2 1/4 (56mm) 36 3 1/2 (913mm) (90mm) 8 (203mm) 5 3/8 (138mm) 41 (1040mm) TOP STANDOFFS GAS CONTROLS RATING PLATE/ ELECTRICAL GAS LABELS ACCESS ACCESS Figure 1. Diagram of the QV36-A u 10
Résumé du contenu de la page N° 11
25 3/4 (653mm) 12 7/8 (327mm) 16 1/4 (413mm) 6 5/8 (168mm) DIAMETER 8 3/4 (222mm) VENT COLLARS 8 5/8 (219mm) DIAMETER VENT GAS LINE COLLARS ACCESS ELECTRICAL ACCESS 18 3/8 32 1/2 (468mm) (826mm) 31 3 1/2 2 1/4 (788mm) 23 3/8 (90mm) (56mm) (594mm) 31 (786mm) 5 3/8 8 (138mm) (203mm) 36 (913mm) TOP STANDOFFS GAS CONTROLS ELECTRICAL GAS RATING PLATE/ ACCESS ACCESS LABELS u Figure 2. Diagram of the QV-32-A 11
Résumé du contenu de la page N° 12
3” MIN. (76mm) B Installing the Fireplace A Constructing the Fireplace Chase A chase is a vertical box-like structure built to enclose the gas fireplace and/or its vent system. Vertical vents that run E on the outside of a building may be, but are not required to D be, installed inside a chase. CAUTION: TREATMENT OF FIRESTOP SPACERS AND C CONSTRUCTION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT 1/2 “ MIN. (13mm) SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING C
Résumé du contenu de la page N° 13
Step 2. Framing the Fireplace CAUTION: MEASURE FIREPLACE DIMENSIONS AND Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommo- VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING. date wall coverings and fireplace facing material. The dia- gram below shows framing reference dimensions. NON-COMBUSTIBLE ZONE IS DEFINED BY 3” ABOVE THE ELBOW FOR THE ENTIRE WIDTH AND DEPTH (BEHIND THE FRONT HEADER) OF THE FIREBOX. 3” WALL
Résumé du contenu de la page N° 14
6 7/16” 6 5/32” (164mm) (156mm) 8 1/2” (216mm) 8 1/2” 11 5/8” (216mm) (295mm) 11 1/16” 7 3/8” 5 7/8” (281mm) (149mm) (187mm) 6 1/2” 5 1/16” (165mm) (129mm) 8 5/8” 8 5/8” (220mm) (220mm) 11 15/16” (303mm) DV-90D DV-48D DV-36D DV17/24D DV-12/17D 12-17 (305-432mm) 17-24 (432-610mm) 35 3/4” (908mm) 47 3/4” (1.2m) 11 3/4” 8 3/4” (298mm) (222mm) 5 3/4” (146mm) DV-09D DV-12D DV-06D DV-FLEX-10 120” (3048mm) DV-FLEX-2 DV-FLEX-5 60” 24” (1524mm) (610mm) DV-FLEX-3 NOTE: PIPES OVERLAP 1-3/8 INCHES (34.93m
Résumé du contenu de la page N° 15
6 1/2 6 3/8 9 1/4 6 1/2 9 5/8 6 3/8 6 5/8 SL-45D 6 5/8 9 5/8 SL-90D SL-09D SL-12/17D (SL12-17D) SL-24D SL-36D SL-48D 8 3/4 12-17 23 3/4 35 3/4 47 3/4 17-24 6 1/2 11 3/4 5 3/4 6 5/8 SL-17/24D SL-12D (SL17-24D) SL-06D SL-FLEX-10 120” (3048mm) SL-FLEX-2 SL-FLEX-5 60” 24” (1524mm) (610mm) SL-FLEX-3 NOTE: PIPES OVERLAP 1-3/8 INCHES (34.93mm) AT EACH JOINT. 36” (914mm) Figure 7. SL D-Series Direct Vent Component Specifications (4-inch inner pipe / 6 5/8-inch outer pipe) 15
Résumé du contenu de la page N° 16
Step 3. Installing the Vent System Identifying Vent Components Approved vent system components are labeled for identifica- A. Vent System Approvals tion. This pipe is tested and listed as an approved compo- These models have vent starting collars on both the top nent of the fireplace. The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection open- and the back of the unit. Depending upon the installation, ings at each joint within the wall. There is no requir
Résumé du contenu de la page N° 17
Flex Vent The flex vent must be supported with the spacing between STRAIGHT UP support intervals not exceeding 4 feet, with no more than ½ VERTICAL VENTING inch sag between supports. V (FT.) A support is required at each change in venting direction, 45' MAX. (13.7m) and in any location where it is necessary to maintain the necessary clearance to combustibles. A simple “up and out” installation (Figure 9) requires only enough support to main- tain the necessary clearance to combustibles. However,
Résumé du contenu de la page N° 18
V H 1' MIN. (305mm) 2' MAX. (610mm) 2' MIN. (610mm) 4' MAX. (1.22m) 3' MIN. (914mm) 6' MAX. (1.86m) 4' MIN. (1.22m) 8' MAX. (2.4m) V+H=40' MAX. (12.4m) H = 8' MAX. (2.4m) Use D-Series components only. V Note: There MUST be a 25% reduction in total H when using flex vent, except H when using the simple up and out installation (see Figure 9). Figure 12. Venting with One 90° Elbow H Use SL D-Series components only. V o VENTING WITH ONE (1) 90 ELBOW
Résumé du contenu de la page N° 19
V H H + H 1 1' MIN. (305 mm) 2' MAX. (610 mm) 4' MAX. (1.22m) 2' MIN. (610 mm) 4' MAX. (1.22 m) 8' MAX. (2.4m) 3' MIN. (914 mm) 6' MAX. (1.86 m) 12' MAX. (3.6m) 4' MIN. (1.22 m) 8' MAX. (2.48 m) 16' MAX. (4.8m) V+H+H1 = 40' MAX. (12.4 m) H = 8' MAX. (2.48 m) H+H = 16' MAX. (4.8m) 1 H1 V Use D-Series components only. H Note: There MUST be a 25% reduction in total H when using flex vent, except V (FT) H + H (FT) 1 when using the simple up and out 1' MIN. (305 mm)
Résumé du contenu de la page N° 20
o VENTING WITH TWO (2) 90 ELBOWS NATURAL GAS V (MIN.) H + H1 (MAX.) o 90 Elbow on Top 2 FT (610mm) 1 FT (305mm) 3 FT (914mm) 4 FT (1.22m) 2 FT (610mm) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m) H + H MAX. = 16 FT (4.8m) V + H + H MAX. = 40 FT (12.2m) 1 1 o VENTING WITH TWO (2) 90 ELBOWS PROPANE V (MIN.) H + H1 (MAX.) o 90 Elbow on Top NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT