Résumé du contenu de la page N° 1
SMV 3000
Smart Multivariable Transmitter
User’s Manual
34-SM-25-02
3/04
Résumé du contenu de la page N° 2
Copyright, Notices, and Trademarks © Copyright 1999 by Honeywell Inc. Revision 0 – January 18, 1999 While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer. In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and
Résumé du contenu de la page N° 3
About This Publication This manual is intended as a detailed “how to” reference for installing, piping, wiring, configuring, starting up, operating, maintaining, calibrating, and servicing Honeywell’s SMV 3000 Smart Multivariable Transmitter. It is based on using the SCT 3000 Smartline Configuration Toolkit software version 2.0 or greater as the operator interface. While this manual provides detailed procedures to assist first time users, it also includes summaries for most procedures as a qui
Résumé du contenu de la page N° 4
iv SMV 3000 Transmitter User’s Manual 1/99
Résumé du contenu de la page N° 5
Table of Contents References .................................................................................................................................... xii Technical Assistance ................................................................................................................... xii SECTION 1 OVERVIEW - FIRST TIME USERS ONLY ................................................................ 1 1.1 Introduction ................................................................
Résumé du contenu de la page N° 6
SECTION 7 STARTUP ................................................................................................................. 79 7.1 Introduction .................................................................................................................. 79 7.2 Startup Tasks............................................................................................................... 80 7.3 Running Output Check ........................................................................
Résumé du contenu de la page N° 7
Figures and Tables Figure 1 SMV 3000 Transmitter Handles Multiple Process Variable Measurements and Calculates Flow Rate ................................................................ 4 Figure 2 Functional Block Diagram for Transmitter in Analog Mode of Operation.................. 5 Figure 3 Functional Block Diagram for Transmitter in Digital DE Mode of Operation. ................................................................................................................. 6 Figure 4 Smart
Résumé du contenu de la page N° 8
Figures and Tables, Continued Table 1 Start-up Tasks Reference....................................................................................... 14 Table 2 Operating Temperature Limits ................................................................................ 19 Table 3 Transmitter Overpressure Ratings.......................................................................... 19 Table 4 Thermocouple Types for Process Temperature Sensor......................................... 20 Table
Résumé du contenu de la page N° 9
Figures and Tables, Continued Table A-9 Conversion Values for PV1 and PV2 Pressures................................................... 172 Table A-10 Conversion Values for PV3 Temperature ............................................................. 172 Table A-11 Conversion Values for PV4 as Volumetric Flow Rate........................................... 174 Table A-12 Conversion Values for PV4 as Mass Flow Rate ................................................... 176 Table A-13 Additional IOP
Résumé du contenu de la page N° 10
Acronyms A.G.A. ......................................................................................................... American Gas Association AP ............................................................................................................................ Absolute Pressure APM ......................................................................................................... Advanced Process Manager AWG ....................................................................
Résumé du contenu de la page N° 11
Parameters A’ ................................................................................................................................... Area of orifice d A’ ......................................................................................................................................Area of pipe u C .................................................................................. Flow coefficient or orifice discharge coefficient d ...............................................
Résumé du contenu de la page N° 12
References Publication Publication Binder Binder Title Number Title Number SCT 3000 Smartline Configuration 34-ST-10-08 Toolkit Start-up and Installation Manual ST 3000 Smart Field Communicator 34-ST-11-14 Model STS103 Operating Guide For R400 and later: PM/APM Smartline Transmitter PM12-410 Implementation/ TDC 2045 Integration Manual PM/APM Optional Devices Technical Assistance If you encounter a problem with your SMV 3000 Smart Multivariable Transmitter, check to see how your transmitter is cu
Résumé du contenu de la page N° 13
Section 1 Overview - First Time Users Only 1.1 Introduction Section Contents This section includes these topics. Topic See Page 1.1 Introduction..............................................................................1 1.2 CE Conformity (Europe) ...........................................................3 1.3 SMV 3000 Smart Multivariable Transmitters ............................4 1.4 Smartline Configuration Toolkit (SCT 3000) .............................7 1.5 Smart Field Communicator (SF
Résumé du contenu de la page N° 14
1.2 CE Conformity (Europe) About Conformity This product is in conformity with the protection requirements of 89/336/EEC, the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed. Deviation from the installation conditions specified in this manual may invalidate this product’s conformity with the EMC Directive. ATTENTION ATTENTION The emission limits of EN 50081-2 are designed to provide reasonable protection against harmful interference when this
Résumé du contenu de la page N° 15
1.3 SMV 3000 Smart Multivariable Transmitters About the Transmitter The SMV 3000 Smart Multivariable Transmitter shown in Figure 1 measures three separate process variables and calculates volumetric or mass flow rate for gases, steam or liquids for output over a 4 to 20 milliampere, two-wire loop. Its general design is based on the field proven technology of our ST 3000 Smart Pressure Transmitter and meets the same high performance standards. Figure 1 SMV 3000 Transmitter Handles Multiple Proces
Résumé du contenu de la page N° 16
1.3 SMV 3000 Smart Multivariable Transmitters, Continued SMV Operating Modes The SMV 3000 can transmit its output in either an analog 4 to 20 milliampere format or a Digitally Enhanced (DE) protocol format for direct digital communications with our TPS/TDC 3000 control system. In the analog format, only a selected variable is available as an output which can be any one of the following: Differential Pressure PV1, Static Pressure PV2, Process Temperature PV3, or Calculated Flow Rate PV4
Résumé du contenu de la page N° 17
1.3 SMV 3000 Smart Multivariable Transmitters, Continued SMV Operating In the digital DE protocol format, all four process variables are available Modes, continued for monitoring and control purposes; and the meter body temperature is also available as a secondary variable for monitoring purposes only - See Figure 3. Figure 3 Functional Block Diagram for Transmitter in Digital DE Mode of Operation. Factory Characterization Data Electronics Housing Meter Body PROM ∆ P Sensor
Résumé du contenu de la page N° 18
1.4 Smartline Configuration Toolkit (SCT 3000) Smartline Honeywell’s SCT 3000 Smartline Configuration Toolkit is a cost-effective Configuration Toolkit means to configure, calibrate, diagnose, and monitor the SMV 3000 and other smart field devices. The SCT 3000 runs on a variety of Personal Computer (PC) platforms using Windows 95 Window 98 and Windows NT . It is a bundled Microsoft Windows software and PC-interface hardware solution that allows quick, error-free configuration of SMV tra
Résumé du contenu de la page N° 19
1.5 Smart Field Communicator (SFC) About SFC The portable, battery-powered SFC serves as the common communication Communications interface device for Honeywell’s family of Smartline Transmitters. It communicates with a transmitter through serial digital signals over the 4 to 20 milliampere line used to power the transmitter. A request/response format is the basis for the communication operation. The transmitter’s microprocessor receives a communication signal from the SFC, identifies the request
Résumé du contenu de la page N° 20
1.5 Smart Field Communicator (SFC), Continued Using the SFC with Change Mode the SMV 3000, of Operation: Tell transmitter to operate in either its analog (4-20 continued mA) mode or its digital enhanced (DE) mode. Check Current Output: Use the transmitter to supply the output current desired for verifying analog loop operation, troubleshooting, or calibrating other components in the analog loop. Simulate Input: Use the transmitter to simulate a desired input value for the selected PV f