Résumé du contenu de la page N° 1
POWER AVAILABILITY
™
2UPOD
USER MANUAL
Power Output
Distribution
230 Volt
Résumé du contenu de la page N° 2
Résumé du contenu de la page N° 3
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INTRODUCTION AND SYSTEM DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Résumé du contenu de la page N° 4
Résumé du contenu de la page N° 5
IMPORTANT SAFETY INSTRUCTIONS WARNING ! DO NOT ATTEMPT TO SERVICE THIS PRODUCT YOURSELF. OPENING OR REMOVING THE COVER MAY EXPOSE YOU TO DANGEROUS VOLTAGES, EVEN WHEN THE AC CORD IS DISCONNECTED FROM THE ELECTRICAL SOCKET. REFER ALL SERVICING TO QUALIFIED SERVICE PERSONNEL. SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and ™ operation of the 2U POD . This product is designed for commercial / industrial use only, with Lieber
Résumé du contenu de la page N° 6
GLOSSARY OF SYMBOLS • Indicates AC Input. Indicates AC Output. Consult the manual for additional information. i MAINS lamp indicates local power is available and the load may be MAINS transferred to bypass the UPS. UPS lamp indicates UPS power is available and the load may be UPS transferred to the UPS to provide computer-grade power to the load. 2
Résumé du contenu de la page N° 7
INTRODUCTION AND SYSTEM DESCRIPTION ™ Congratulations on your choice of the Liebert 2U POD . The Liebert 2U POD provides main- tenance bypass capability as well as power output distribution. The Liebert 2U POD can be used on UPSs in the rack mount or tower configuration. The Liebert 2U POD provides an isolated path of power for your UPS system for preventive maintenance or service. System Description The 2U POD has two modes of operation: UPS (UPS available) and MAINS (maintenance bypass).
Résumé du contenu de la page N° 8
INSTALLATION ON GXT 2U UPS NOTE This manual provides instructions for the 2U POD only. Refer to your UPS manual for UPS operation and installation instructions. 1. Unpack the 2U POD carefully, noting the packing method. Retain the box and packing material for possible future shipments. 2. Visually inspect the 2U POD for freight damage. Report damage to the carrier and your local dealer or Liebert representative. 3. Verify that the 2U POD input cord, UPS input cord, and socket for the UPS ar
Résumé du contenu de la page N° 9
6. Next attach the POD to the securing brackets (see Figure 5). The POD can be installed to face one of three different directions utilizing the same mounting procedures. Figure 5 Attaching POD to securing brackets 7. Make sure the 2U POD rotary switch is in the MAINS position. Use the mains input cord originally used with the UPS. Plug the mains input cord from the mains input socket to the mains wall socket. WARNING: The 2U POD is now electrically live. The MAINS lamp (orange) should now
Résumé du contenu de la page N° 10
RACK MOUNT INSTALLATION 1. Rack mount installation of the 2U POD is possible with the use of the rack mounting brackets (shipped with the POD). See Figure 6. 2. The rack mount brackets allow you to rack mount the POD in a 19" enclosure (23" to 19" rack adapters would have to purchased separately if you are using our 23" Foundation or equivalent cabinet). 3. The POD can be mounted to face one of four directions depending on your application, and utilizing the rack mount brackets provided. 4
Résumé du contenu de la page N° 11
INDICATOR LAMPS MAINS Indicator Lamp This orange lamp is illuminated when mains power is present (see Figure 7). It signals that you may transfer the loads to maintenance bypass (MAINS mode) operation via the rotary switch. During a mains power outage, this lamp will be off and the UPS will supply battery back-up power to the connected loads. UPS Indicator Lamp This green lamp is illuminated when there is output power available from the UPS (see Figure 7). It signals that it is safe to tra
Résumé du contenu de la page N° 12
OPERATION Transfer to Maintenance Bypass To transfer to maintenance bypass (mains) from UPS, use the following steps: 1. Ensure the MAINS lamp (orange) is illuminated. If the lamp is not illuminated, refer to Troubleshooting section. 2. Transfer the rotary switch from UPS to MAINS, provided the MAINS lamp is illuminated on the 2U POD. 3. Turn the UPS off. 4. Disconnect the two cables connecting the UPS to the 2U POD. 5. You may now service the UPS. Transfer to UPS To transfer to UPS from m
Résumé du contenu de la page N° 13
SPECIFICATIONS Transfer Time (to and from maintenance bypass) < 6 milliseconds Operating Ambient Temperature 0°C to +40°C (32°F to 104°F) Storage Ambient Temperature -20°C to +60°C (-4°F to 140°F) Dimensions W x D x H: mm (in.) 88 x 77 x 394 (3.5 x 3.0 x 15.5) Weight: kg (lbs) 4.5 (10) Humidity 0 to 95% non-condensing Agency/Standards CE, EN 60950, ISTA Procedure 1A Electrical Rating See Model Label on MicroPOD This 2U POD is intended for use with a UPS meeting all the following requirements:
Résumé du contenu de la page N° 14
TROUBLESHOOTING Problem Cause Solution MAINS lamp (orange) not Mains not present. Call qualified service personnel to restore illuminated. power to socket. 2U POD input cord not Refer to 2U POD installation instructions in connected to mains. this manual: • Installation on GXT 2U UPS and • Rack Mount Installation. UPS Available lamp (green) not UPS output power not Turn on UPS. Refer to UPS user manual. illuminated. present. UPS input and/or output cord Refer to 2U POD installation instruct
Résumé du contenu de la page N° 15
Résumé du contenu de la page N° 16
POWER AVAILABILITY ™ 2UPOD USER MANUAL Technical Support The Company Behind the Products United States With over a million installations around the globe, 1050 Dearborn Drive Liebert is the world leader in computer protection P.O. Box 29186 systems. Since its founding in 1965, Liebert has Columbus, OH 43229 developed a complete range of support and protection systems for sensitive electronics: Single-Phase UPS • Environmental systems—close-control air 800-222-5877 conditioning from 1 to 60 tons