Résumé du contenu de la page N° 1
POWER AVAILABILITY
UPStation GXT 2U
USER MANUAL
2700VA
208V
Résumé du contenu de la page N° 2
Résumé du contenu de la page N° 3
TABLE OF CONT ENTS IMPORTANT SAFETY INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . 1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 MAJOR COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters . . . 5 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . 5 In
Résumé du contenu de la page N° 4
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Pins 4 & 5 - Remote Shutdown on Battery . . . . . . . . . . . . . . . . . . . . . 19 Pins 5 & 6 - Any-Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Auto-Enable Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Pin 6 Logic. . . . . . . . . . . . . . .
Résumé du contenu de la page N° 5
IMPORTANT SAFETY INSTRUCTIONS WARNING ! Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone. SAVE THESE INSTRUCTION
Résumé du contenu de la page N° 6
This UPS contains no user serviceable parts except the internal battery pack. The UPS ON/Standby push buttons do not electrically isolate inter- nal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accor- dance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert
Résumé du contenu de la page N° 7
GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual i Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Standby 3
Résumé du contenu de la page N° 8
INTRODUCTION Congratulations on your choice of the Liebert UPStation GXT 2U Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during trans- mission and distribution it may be subject to voltage sags, spikes, or com- plete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT 2U protects equip- men
Résumé du contenu de la page N° 9
MAJOR COMPONENT S Input Output Dynamic Bypass TVSS & Rectifier Inverter L1 EMI/RFI L1 /PFC Filters DC to DC Converter Battery Battery Charger L2 L2 G G TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide surge protection and filter both electro- magnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected. RECTIFIER/POWER FACTOR
Résumé du contenu de la page N° 10
BATTERY CHARGER The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the UPStation GXT 2U is plugged in, even when the UPS is not turned on. DC TO DC CONVERTER The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency
Résumé du contenu de la page N° 11
GXT 2U (REAR VIEW) ® Intellislot Port DB-9 Communications Port Cooling Fans AC Input (L6-20) Input Circuit External Breaker Battery (20 amp) Connector Output Receptacle (L6-20R) Support Base Output Receptacles (L6-15R) 7
Résumé du contenu de la page N° 12
INSTALLATION PREPARATION 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative. CAUTION ! The UPS is heavy (see Specifications section). Take proper precautions when lifting or moving it. 2. Decide where to place the GXT 2U. Install the UPS indoors in a con- trolled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids,
Résumé du contenu de la page N° 13
UPStation GXT –+ AC INPUT BATTERY UPS ON BYPASS RACK-MOUNT UPS CONVERSION AND INSTALLATION NOTE When rack mounted, the UPS must be supported by a shelf, brackets or slide rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack. 1. For slide rail installations, first remove the top/side fin. Slide the top/side fin forward, then lift it up to remove. If desired, install the optional rack mount handles that were s
Résumé du contenu de la page N° 14
3. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet. CAUTION ! Reduce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position. Install rear member of each M5 screws Front rack bracket assembly into rack mounting rails enclosure with two (2) M5 screws provided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mount- ing rails. Insert s
Résumé du contenu de la page N° 15
5. Prepare the UPS or battery cab- M4 inet (the equipment) for rack Retaining screws latch mounting by following instruc- tions in the equipments user manual. The equipment may require additional parts to be added or parts to be removed UPS or battery cabinet for rack mounting. After it is pre- pared, lay equipment in rack- mounting position. Fasten inner members from Step 2 to the equipment on both sides as Front shown in the figure at right with (8) M4 screws provided in this ki
Résumé du contenu de la page N° 16
8. Secure front of the equipment to rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on front of the equipment that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment. Otherwise, the equip- ment should be secured to front of rack mounting rails with four (4) customer-supplied fasteners. 9. To orient the display for horizon- Vertical Horiz
Résumé du contenu de la page N° 17
EXTERNAL BATTERY CABINET INSTALLATION Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. There is no limit to the number of external battery cabinets that can be used but each cabinet will increase the battery recharge time. CAUTION ! The external battery cabinet(s) are heavy (see Specifications section). External battery cabi
Résumé du contenu de la page N° 18
CONTROLS AND INDICATORS All LEDs illuminated for illustrative purposes only. ON/Alarm Silence/Manual Battery Test Button This button controls output power to connected load(s) and has three functions: ON Alarm Silence Manual Battery Test ON - Pressing this button will start up the UPS in order to provide condi- tioned and protected power. Alarm Silence - To silence alarms, press this button for at least one sec- ond. After the alarm is silenced, the UPStation GXT 2U will reactivate th
Résumé du contenu de la page N° 19
Standby/Manual Bypass Button This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass. CAUTION ! While the UPS is in Normal Mode operation, pressing the Standby/ Manual Bypass button once will put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press the Standby/ Manual Bypass button two distinct times (for about one second each time) to turn off the UPS. Perform all necessary shutdown procedures on connected loads before
Résumé du contenu de la page N° 20
AC Input Indicator LED (Green) The AC Input indicator LED is illuminated when utility power is available and within the input specifications. Output Voltage Selection The Output Voltage is user configurable and is designed to allow select- ing or changing the desired output voltage to match the utility via the GXT 2U Configuration Program provided with the UPS. The settings to choose from are 200, 208, 220, 230, and 240 VAC output. The factory default setting is 208 VAC. CAUTION ! Never cha