Résumé du contenu de la page N° 1
FB-USER Rev B
User’s Information Manual
Models: 1.5 - 5.0
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing property
damage, personal injury or death.
-- Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
� Do not try to light any appliance.
� Do not touch any electrical switch; do not use any phone in your
building.
� Immediately c
Résumé du contenu de la page N° 2
Contents HAZARD DEFINITIONS ..................................................... 2 3. OPERATING INSTRUCTIONS ..................................... 9 PLEASE READ BEFORE PROCEEDING ......................... 3 4. SMART TOUCH CONTROL MODULE 1. PREVENT COMBUSTION AIR CONTAMINATION ..... 4 Crest Control Module .................................................. 10 2. MAINTENANCE SCHEDULE ....................................... 5 Home Screen .................................................
Résumé du contenu de la page N° 3
User’s Information Manual Please read before proceeding The Crest Installation and Operation Boiler service and maintenance – NOTICE Manual along with the Crest Service � To avoid electric shock, disconnect electrical supply Manual are for use only by a qualified before performing maintenance. heating installer/service technician. � To avoid severe burns, allow boiler to cool before Refer only to this User’s Information performing maintenance. Manual for your reference. Improp
Résumé du contenu de la page N° 4
User’s Information Manual 1 Prevent combustion air contamination If the boiler combustion air inlet is located WARNING Table 1A Corrosive Contaminants and Sources in any area likely to cause contamination, or if products which would contaminate Products to avoid: the air cannot be removed, you must have the combustion air and vent re-piped Spray cans containing chloro/fluorocarbons and terminated to another location. Permanent wave solutions Contaminated combustion air will
Résumé du contenu de la page N° 5
User’s Information Manual 2 Maintenance schedule Service technician Owner maintenance (see the Crest Service Manual) (see pages 6 - 8 for detailed instructions) General: • Address reported problems, if any • Check boiler area • Inspect interior; clean and vacuum if Daily • Check pressure/temperature necessary; gauge • Clean condensate trap and fill with fresh water • Check for leaks (water, gas, flue, condensate) • Verify flue and air lines in good condition
Résumé du contenu de la page N° 6
User’s Information Manual 2 Maintenance schedule Read the list of potential materials listed in Table 1A on Maintenance procedures page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they Boiler must be serviced and maintained must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another The boiler must be inspected and started WARNING area. annually at the beginni
Résumé du contenu de la page N° 7
User’s Information Manual 2 Maintenance schedule (continued) The condensate trap (FIG. 2-1) must Use materials approved by the authority NOTICE WARNING be filled with water during all times having jurisdiction. In the absence of of boiler operation to avoid flue gas other authority, PVC and CPVC pipe emission from the condensate drain line. must comply with ASTM D1785 or D2845. Failure to fill the trap could result in Cement and primer must comply with severe personal
Résumé du contenu de la page N° 8
User’s Information Manual 2 Maintenance schedule Test low water cutoff (if installed) 1. If the system is equipped with a low water cutoff, test the 2. Read the boiler pressure/temperature gauge to make low water cutoff periodically during the heating season, sure the system is pressurized. Lift the relief valve following the low water cutoff manufacturer’s top lever slightly, allowing water to relieve through instructions. the valve and discharge piping. 3. If water flows f
Résumé du contenu de la page N° 9
User’s Information Manual 3 Operating instructions FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance does not have a pilot. It is � Immediately call your gas supplier from a equipped with an ignition device which neighbor’s phone. Follow the gas supplier’s automatically lights the burner. Do not try instructions. to light
Résumé du contenu de la page N° 10
User’s Information Manual 4 SMART TOUCH control module Crest control module The Home Screen displays status, modulation rate, outlet water temperature, inlet water temperature, flue temperature, system supply temperature, system return temperature, outdoor air temperature, and domestic hot water tank temperature. The boiler can be started and stopped by pressing the ON/OFF button. The Boiler Status Screen and Main Menu Screen can be accessed by pressing the appropriate button. Fig
Résumé du contenu de la page N° 11
User’s Information Manual 4 SMART TOUCH control module (continued) Use the Main Menu Screen (FIG. 4-2) to access the screens necessary to set temperatures, operating conditions, and monitor boiler operation. The Crest is equipped with a SMART TOUCH control system. All menu options are accessed by touching the screen with your finger or a stylus from a PDA. Figure 4-2 Main Menu Screen The Main Menu Screen allows navigation to nine (9) Reference the Crest Service Manual for more inf
Résumé du contenu de la page N° 12
Revision Notes: Revision A (ECO #C07970) initial release. Revision B (ECO C11613) reflects the addition of models 4.0 and 5.0. FB-USER Rev B 11/12