Résumé du contenu de la page N° 1
FortiGate-5050
Chassis Guide
USB
CONSOLE 1 2 3 4 5 6 7 8
STA IPM
PWR ACC
5
USB
CONSOLE 1 2 3 4 5 6 7 8
PWR ACC STA IPM
4
USB 1 2 3 4 5 6 7 8
CONSOLE
ACC STA IPM
PWR
3
2 POWER
1
ShMC
ShMC
Critical
Hot Swap
Major
Status
Minor
Alarm Alarm Console Ethernet
2 Reset 1
A detailed guide to the FortiGate-5050 chassis. This FortiGate-5050 Chassis Guide describes FortiGate-5050
hardware features, how to install the FortiGate-5050 chassis, and how to install FortiGate-5000 boards in the chassis.
The most r
Résumé du contenu de la page N° 2
Warnings and cautions Warnings and cautions Only trained and qualified personnel should be allowed to install or maintain FortiGate-5000 series equipment. Read and comply with all warnings, cautions and notices in this document. CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries According to the Instructions. Caution: You should be aware of the following cautions and warnings before installing FortiGate-5000 series hardware • Turning off all pow
Résumé du contenu de la page N° 3
Contents Contents Warnings and cautions................................................................................................... 2 FortiGate-5050 chassis............................................................................ 5 FortiGate-5050 front panel ............................................................................................. 6 FortiGate-5050 back panel ............................................................................................. 6 Physical des
Résumé du contenu de la page N° 4
Contents FortiGate-5050 Chassis Guide 4 01-30000-87211-20090106 http://docs.fortinet.com/ • Feedback
Résumé du contenu de la page N° 5
FortiGate-5050 chassis FortiGate-5050 chassis You can install up to five FortiGate-5000 series boards in the five slots of the FortiGate-5050 ATCA chassis. The FortiGate-5050 is a 5U 19-inch rackmount ATCA chassis that contains two redundant DC power connections that connect to -48 VDC Data Center DC power. The FortiGate-5050 chassis also includes a hot swappable cooling fan tray. If all five slots contain FortiGate-5005FA2, FortiGate-5001SX, or FortiGate-5001FA2 boards, the FortiGate-5050
Résumé du contenu de la page N° 6
FortiGate-5050 front panel FortiGate-5050 chassis FortiGate-5050 front panel Figure 1 shows the front of a FortiGate-5050 chassis. Two FortiSwitch-5003 boards are installed in slots 1 and 2. Three FortiGate-5001SX boards are installed in slots 3, 4, and 5. The FortiGate-5050 primary Shelf Manager is also visible. The factory-installed shelf managers provide power distribution, cooling, alarms, shelf status, and a telco alarm interface for the FortiGate-5050 chassis. For more information abou
Résumé du contenu de la page N° 7
FortiGate-5050 chassis Physical description of the FortiGate-5050 chassis Figure 2: FortiGate-5050 chassis back panel 5 4 RTM slot filler 3 panels 2 RTN RTN 1 INPUT A INPUT B DC VOLTAGE RANGE DC VOLTAGE RANGE Ground -48V -48V TO -58V -48V -48V TO -58V RTN (-DC IN) RTN (-DC IN) 25 25 Connector AMP AMP (green) -48V to -58V -48V to -58V Positive Positive (-DC in) (-DC in) (RTN) (RTN) (black) (black) Power (red) (red) wire ESD k t The back panel includes the FortiGate-5050 chassi
Résumé du contenu de la page N° 8
FortiGate-5050 shelf manager FortiGate-5050 chassis FortiGate-5050 shelf manager The FortiGate-5050 chassis includes one or two identical redundant hot-swappable shelf managers (also called shelf manager cards (SMCs)), located in the dedicated shelf manager slots on the bottom of the FortiGate-5050 front panel. The primary shelf manager is installed on the right (SMC 1) the secondary shelf manager is installed on the left (SMC 2). The FortiGate-5050 shelf manager supports alarm and shelf man
Résumé du contenu de la page N° 9
FortiGate-5050 chassis FortiGate-5050 shelf manager Shelf manager command line interface (CLI) You can use the shelf manager CLI to communicate with the intelligent management controllers of the chassis, with boards in the chassis, and with the shelf manager itself. The CLI is an IPMI-based set of commands that can be accessed directly or through a higher-level management application or a script. Using the CLI, you can access information about the current state of the chassis including curre
Résumé du contenu de la page N° 10
FortiGate-5050 shelf manager FortiGate-5050 chassis 7 At the login prompt enter the shelf manager user name and password. The default user name is root with no password. When you log into the shelf manager CLI you are logging into a Linux shell as root. The following message appears. You can begin entering commands at the # prompt: Welcome to ____ _ _ / __| ||_| _ _| | | | _ ____ _ _ _ _ | | | | | | || | _ \| | | |\ \/ / | |_| | |__| || | | | | |_| |/
Résumé du contenu de la page N° 11
FortiGate-5050 chassis FortiGate-5050 shelf manager For example, you can enter the following command to list the most commonly used CLIA commands: clia help You can also the help command to get more information about specific CLIA commands. For example, use the following command display help for the shelf pwrreorder command: clia help shelf pwrreorder Pigeon Point Shelf Manager Command Line Interpreter Change the order of FRU Activation and Power Descriptors instead of user ma
Résumé du contenu de la page N° 12
FortiGate-5050 shelf manager FortiGate-5050 chassis Table 4: Telco alarm connector pin assignment Pin Name Description 1 AMIR+ MinorReset+ 2 AMIR- MinorReset- 3 AMAR+ MajorReset+ 4 AMAR- MajorReset- 5 ACNO CriticalAlarm - NO 6 ACNC CriticalAlarm - NC 7 ACCOM CriticalAlarm - COM 8 AMINO MinorAlarm -NO 9 AMINC MinorAlarm - NC 10 AMINCOM MinorAlarm - COM 11 AMANO MajorAlarm - NO 12 AMANC MajorAlarm - NC 13 AMACOM MajorAlarm - COM 14 APRCO PwrAlarm - NO 15 APRCOM PwrAlarm - COM Shield Shelf-GND Shel
Résumé du contenu de la page N° 13
Power connection and configuration Power connection and configuration This chapter describes how to connect data center DC power to a FortiGate-5050 chassis. If data center DC power is not available, this document also describes how to use the FortiGate-5053 power converter tray to supply DC power to the FortiGate-5050 chassis. This chapter describes: • About data center DC power • Connecting the FortiGate-5050 chassis to data center DC power and data center ground • Connecting the FortiGate-
Résumé du contenu de la page N° 14
Connecting the FortiGate-5050 chassis to data center DC power and data center ground Figure 6: Connecting a FortiGate-5050 power input connector to data center DC power Data Center -48VDC Data Center connector RTN connector RTN (positive) -48V to -58V red to Data (-DC in) black to Center RTN Data Center -48VDC Power wire fixture -48V to -58V Positive (-DC in) (RTN) (black) (red) To connect a FortiGate-5050 power input connector to data center DC power You need the following tools and equipme
Résumé du contenu de la page N° 15
Power connection and configuration To connect the FortiGate-5050 chassis to data center ground You need the following tools and equipment to connect the FortiGate-5050 chassis to ground: • A number 2 Phillips screwdriver. • An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord. • One green AWG-6 stranded wire with terminal lugs attached. Figure 7: Connecting a FortiGate-5050 chassis to data center ground FortiGate-5050 Data Center Ground ground connector connecto
Résumé du contenu de la page N° 16
Connecting the FortiGate-5050 chassis to AC power using the FortiGate-5053 power converter tray Figure 8: Front panel of the FortiGate-5053 power converter tray with one power supply removed AC Power LED DC Power LED Slot 3 Slot 2 Slot 1 The LEDs for each installed power supply are visible from the FortiGate-5053 power converter tray front panel. Table 5: FortiGate-5020/5050 power supply LEDs LED State Description AC Power Green The power supply is connected to AC power. Off The power supply i
Résumé du contenu de la page N° 17
Power connection and configuration AC input power characteristics: • AC input voltage: 110 to 250 VAC • AC input current: 10A • Frequency: 47 to 63 Hz Selecting the power supplies and power converter trays that you need for your FortiGate-5050 configuration This section provides some basic information for determining how many FortiGate-5053 power converter trays and FortiGate-5020/5050 power supplies that you need, depending on the power requirements of your FortiGate-5050 chassis. This secti
Résumé du contenu de la page N° 18
Connecting the FortiGate-5050 chassis to AC power using the FortiGate-5053 power converter tray Figure 10: Non-redundant power for all FortiGate-5050 chassis slots 1 FortiGate-5053 power convertor tray Slot 3 Slot 2 Slot 1 2 FortiGate-5020/5050 power supplies 2 x 800W = 1600W CONSOLE USB 1 2 3 4 5 6 7 8 PWR ACC STA IPM 5 USB 1 2 3 4 5 6 7 8 CONSOLE ACC STA IPM 4 PWR USB 1 2 3 4 5 6 7 8 CONSOLE STA IPM 3 PWR ACC 1 FortiGate-5050 2 POWER chassis 1 ShMC ShMC Critical Hot Swap Major Status Alarm Min
Résumé du contenu de la page N° 19
Power connection and configuration Figure 12: Redundant FortiGate-5053 power converter trays Slot 3 Slot 2 Slot 1 2 FortiGate-5053 power convertor trays Slot 3 Slot 2 Slot 1 4 FortiGate-5020/5050 power supplies 2 x 800W = 1600W 2 x 800W = 1600W CONSOLE USB 1 2 3 4 5 6 7 8 PWR ACC STA IPM 5 USB 1 2 3 4 5 6 7 8 CONSOLE STA IPM 4 PWR ACC USB CONSOLE 1 2 3 4 5 6 7 8 PWR ACC STA IPM 3 1 FortiGate-5050 2 POWER chassis 1 ShMC ShMC Critical Hot Swap Major Status Alarm Minor 2 Alarm Reset Console Etherne
Résumé du contenu de la page N° 20
Connecting the FortiGate-5050 chassis to AC power using the FortiGate-5053 power converter tray Connecting a FortiGate-5050 chassis to the FortiGate-5053 power converter tray To use a FortiGate-5053 power converter tray with the FortiGate-5050 chassis you need to make DC power connections between the FortiGate-5050 chassis and the FortiGate- 5053 power converter tray. You also need to the connect the FortiGate-5050 chassis to data center ground. To connect a FortiGate-5050 power input connecto