CRESTRON GREEN LIGHT™ Architectural Dimming
Introduction
CRESTRON GREEN LIGHT architectural dimming cabinets come pre-configured with GLX architectural dimming
and switching modules already installed. In addition, branch circuit breakers come preinstalled and prewired to the
modules. The cabinets only require installation and wiring of feed and load circuits.
Industry Compliance
The cabinet and modules are Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc
Résumé du contenu de la page N° 2
Architectural Dimming CRESTRON GREEN LIGHT™ Physical Description This section shows the exterior and interior dimensions of the CRESTRON GREEN LIGHT Architectural Dimming cabinet. External Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets W1 7 Ø " (11 mm) MOUNTING 16 W2 HOLES W3 1 21 " 2 (547 mm) 1 21 2" (547 mm) H2 1 21 2" (547 mm) 1 21 " 2 (547 mm) H1 CONCENTRIC TECHNICAL KNOCKOUTS, 3 1 31 TOTAL (FOR " (19 mm) & " (13 mm) CONDUIT) 4 2 TYPICAL TOP AND BOTTOM KNOCKOUTS, 4
Résumé du contenu de la page N° 3
CRESTRON GREEN LIGHT™ Architectural Dimming Interior Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets (GLE-XXX-Xx2, left; GLE-XXX-Xx4, right) W4 W5 W1 W3 W3 W1 W3 W3 W3 W3 W2 W2 H1 H1 GROUND LUG GROUND LUG GROUND BARS GROUND BARS SERVICE SERVICE SCREWDRIVER SCREWDRIVER Interior Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets GLE-120 GLE-277 DIMENSION 2X2 3X2 2X4 3X4 2X2 3X2 2X4 3X4 H1 14 7/8” 18 1/4” 14 7/8” 14 7/8” 11 11/16” 15 1/16 11 11/16” 11 11/16”
Résumé du contenu de la page N° 4
Architectural Dimming CRESTRON GREEN LIGHT™ Installation Observe the following when installing the cabinet: • The cabinet must be mounted by a licensed electrician in accordance with all national and local codes. Refer to the diagram below for specific requirements. • Allow adequate clearance in front of the cover for servicing. • The cabinet is designed for surface mounting on a wall. • Cabinets are intended for indoor use only. • The ambient temperature range should be 32 °F to 104
Résumé du contenu de la page N° 5
CRESTRON GREEN LIGHT™ Architectural Dimming Wiring NOTE: All wiring must be installed in accordance with all local and national electrical codes. NOTE: Refer to the torque settings specified on pages 6, 7 and 8. CRESTRON GREEN LIGHT cabinets are shipped with GLX modules installed and prewired to the branch circuit breakers. The following must be performed after installation: • Connect incoming feed conductors to the breaker panel (section A of the following diagram) • Connect load wiri
Résumé du contenu de la page N° 6
Architectural Dimming CRESTRON GREEN LIGHT™ Feed Wiring (Section A) Feed Wiring for MLO and MCB Applications MLO BREAKER DETAIL MCB BREAKER DETAIL NEUTRAL LUG "A" PHASE "B" PHASE "C" NEUTRAL LUG PHASE NEUTRAL BUS "A" NEUTRAL BUS PHASE "B" PHASE "C" PHASE GROUND LUG GROUND LUG GROUND BARS GROUND BARS Refer to the following table for information on wiring the feed to the panel. Feed Wire Information 120 Volt Models 277 Volt Models TERMINAL CONNECTOR MAX TORQUE Max CONNECTOR MAX TORQUE M
Résumé du contenu de la page N° 7
CRESTRON GREEN LIGHT™ Architectural Dimming Load Wiring (Section B) CAUTION: Bypass jumpers are provided on each output to allow testing and to protect the module during installation. The jumper shorts the L, SW and DM terminals so that the load circuit is energized when the branch breaker is on. Do not remove the bypass jumper until all feed and load wiring has been completed, and the circuits have been tested for electrical faults. NOTE: Use copper conductors only – rated 75 °C. Wire
Résumé du contenu de la page N° 8
Architectural Dimming CRESTRON GREEN LIGHT™ The GLX-DIMFLV8 also requires wiring the terminals for 0-10 VDC control wire. Refer to the following diagram when connecting the dimmable ballast. Each control wire terminal accepts one 12 – 28 AWG wire. 0-10 VDC Control Wiring for GLX-DIMFLV8 Only TO "+" ON 4-WIRE LOADS (PURPLE) TO "-" ON 4-WIRE LOADS (GRAY) 2. Test the circuit for electrical faults by turning on each circuit breaker, checking that the breakers do not trip, and that power is
Résumé du contenu de la page N° 9
CRESTRON GREEN LIGHT™ Architectural Dimming Connector Wiring POWER: 24 VDC JUMPERED FROM NET PORT or EXTERNAL SUPPLY. PROVIDES CRESNET POWER TO THE MODULES MODULES: RED TO GLX MODULES WHITE NET: BLUE BLACK TO CONTROL SYSTEM AND RED OTHER CRESNET DEVICES WHITE BLUE BLACK OVERRIDE: FROM OTHER CABINET; FROM ALARM, ETC. (OPTIONAL); TO OTHER CABINET(S) IF NECESSARY NET Port Wiring When wiring the supplied NET connectors for connection to a Crestron control system or other device on the
Résumé du contenu de la page N° 10
Architectural Dimming CRESTRON GREEN LIGHT™ To power the modules externally from a Cresnet 24 VDC power supply, connect the external power supply to the EXT and G pins on the POWER supplied connector as shown in the following diagram. Providing Cresnet Power Externally When properly connected and receiving 24 VDC power externally, the green LED next to the MODULES port will light. Under normal operation, each lighting module will draw power from the line voltage on circuit 1. In this c
Résumé du contenu de la page N° 11
CRESTRON GREEN LIGHT™ Architectural Dimming Testing Manual Control A lighting module can be manually controlled from its front panel. Switch Function The GLX-HSW8 is a power switching module that can be used to turn loads on and off. The GLX-DIM6 and the GLX-DIMFLV8 are dimming modules whose outputs can be set to operate as dimmable or non-dimmable outputs. The state of each output can be manually controlled from the front panel. To use a module’s switch function: • Ensure that the out
Résumé du contenu de la page N° 12
Architectural Dimming CRESTRON GREEN LIGHT™ Save Override Settings The state of each output can be saved as an override setting, which can be automatically recalled when the Override mode is enabled. NOTE: The control system program has a setting that can prevent locally saving the override state. If this setting is enabled, the display shows “Er” when trying to save override states. For more information, refer to the SIMPL Windows help file. To save the state of all of the outputs as a
Résumé du contenu de la page N° 13
CRESTRON GREEN LIGHT™ Architectural Dimming Problem Solving Troubleshooting The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative. Troubleshooting TROUBLE POSSIBLE CAUSE(S) CORRECTIVE ACTION Module(s) does not Power not delivered to the If the module is powered internally, verify that function. module. the circuit breaker connected to the first channel on the module is
Résumé du contenu de la page N° 14
Architectural Dimming CRESTRON GREEN LIGHT™ Appendix A: Setting Module Net IDs The following procedure will normally be performed by an authorized Crestron representative as part of the System Commissioning phase. For system wiring and basic testing as described on pages 5 and 11, it is not necessary to perform this step. Only perform this step if instructed by an authorized Crestron representative, or when replacing modules on a system that have already been commissioned (in the latter ca
Résumé du contenu de la page N° 15
CRESTRON GREEN LIGHT™ Architectural Dimming Appendix B: Module Specifications Specifications for the GLXP modules are listed in the following table. GLXP Module Specifications SPECIFICATION GLX-DIM6 GLX-HSW8 GLX-DIMFLV8 Description 6 Channel Dimming/Switching 8 Channel High-Inrush Switch 8 Channel 0-10V Fluorescent Module Module Dimmer Module Number of Outputs 6 8 8 Cresnet Power 5 Watts 5 Watts 5 Watts Usage* Input Voltage 100 – 277 VAC 50/60 Hz 100 – 277 VAC 50/60 Hz 100 – 277 VAC 5
Résumé du contenu de la page N° 16
Architectural Dimming CRESTRON GREEN LIGHT™ Return and Warranty Policies Merchandise Returns / Repair Service 1. No merchandise may be returned for credit, exchange or service without prior authorization from CRESTRON. To obtain warranty service for CRESTRON products, contact an authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying the nature of the problem, name and pho