F220 Series Detectors with
F220-B6RS Base
Installation Manual
en English manual
Résumé du contenu de la page N° 2
F01U029847-01.book Page 2 Thursday, March 1, 2007 9:27 AM 2 en | Legal F220 Series Detectors with F220-B6RS Bases 1Legal 1.1 Trademarks ® CleanMe is a registered trademark of GE Interlogix in the United States and/or other countries. ® Chamber Check is a registered trademark of Bosch Security Systems, Inc. in the United States. Chambermaid™ is a trademark of Bosch Security Systems, Inc. in the United States. ENVI-RO-TECH™ is a trademark of Tech Spray L.P. ® TECHSPRAY is a registered trade
Résumé du contenu de la page N° 3
F01U029847-01.book Page 3 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases General Information | en 3 use a can of clean, dry compressed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores. Shorten the plastic tube that comes with the compressed air to about 2 in. (5 cm). Place the tube or needle valve through the Chambermaid valve in the bottom of the detector (refer to Figure 2.2 on page 6). NOTE! Do not paint the
Résumé du contenu de la page N° 4
F01U029847-01.book Page 4 Thursday, March 1, 2007 9:27 AM 4 en | General Information F220 Series Detectors with F220-B6RS Bases manufacturer’s installation instructions for proper end-of-line (EOL) resistor selection. 2.1.2 Base Features 13 12 11 10 14 12 15 8 13 9 13 7 3 4 2 5 1 12 6 12 13 1. Terminal 1 9. Remote Terminal (c) 2. Terminal 2 10. Tamper Tab (Locking Bar) 3. Terminal 3 11. Tamper Tab (Locking Bar 4. Terminal 4 Mount) 5. Terminal 5 12. Alignment Key (4 places) 6. DIP Switches
Résumé du contenu de la page N° 5
F01U029847-01.book Page 5 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases General Information | en 5 2.2 F220 Series Detectors 2.2.1 About F220 Series Detector Heads The F220 Series Detector Heads listed inTable 2.1 each require an F220-B6 Series Base. WARNING! The F220-PTHC detects carbon monoxide (CO) as a component of a fire. Do not use the F220-PTHC ! as a stand-alone CO detector. Electronic heat detector 135°F (57°C), fixed F220-135 temperature and rate-of
Résumé du contenu de la page N° 6
F01U029847-01.book Page 6 Thursday, March 1, 2007 9:27 AM 6 en | General Information F220 Series Detectors with F220-B6RS Bases 2.2.2 F220 Series Detector Features 1 5 2 6 4 3 1. Front of detector 4. Unlocking port 2. Light-emitting diode (LED) 5. Back of detector 3. Thermistor 6. Chambermaid location (heat detectors only) Fig. 2.2 Detector Features 2.2.3 F220 Series Heat Detector Heads The F220 Heat Detector Heads can be identified by color coding (refer to Table 2.2). F220-135 No circle a
Résumé du contenu de la page N° 7
F01U029847-01.book Page 7 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases General Information | en 7 2.2.4 F220 Series Smoke Detector Heads The F220 Series Smoke Detector Heads are UL Listed, open- area photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to Section 2.1 F220-B6RS Detec
Résumé du contenu de la page N° 8
F01U029847-01.book Page 8 Thursday, March 1, 2007 9:27 AM 8 en | Install the Bases F220 Series Detectors with F220-B6RS Bases 2.3.2 Base Specifications Alarm Current (only base current, detector current excluded) F220-B6RS (with 45 mA at 24 VDC steady sounder and 50 mA maximum at 30 VDC relay): F220-B6RS (with 30 mA at 24 VDC separately powered 35 mA maximum at 30 VDC sounder only): NAC Current 30 mA at 24 VDC Standby Current 10 mA maximum at 30 VDC Voltage 10.0 VDC to 30.0 VDC Table 2.4 F
Résumé du contenu de la page N° 9
F01U029847-01.book Page 9 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 9 Power Supervision Base can be used as the last base on a loop in four-wire systems to provide power supervision. NOTE! Follow NFPA 72 guidelines for mounting locations. For commercial and industrial installations, 30 ft (9 m) i spacing between smoke detectors is recommended. 1. Release the mounting skirt from the mounting base. Use a screwdriver at the location of
Résumé du contenu de la page N° 10
F01U029847-01.book Page 10 Thursday, March 1, 2007 9:27 AM 10 en | Install the Bases F220 Series Detectors with F220-B6RS Bases 3.2 Wire the Bases CAUTION! When wiring bases, all terminal screws including those not wired must be tightened to prevent loose screw heads from making intermitent electrical ! contact with the detector head. 3.2.1 Terminal Connections WARNING! Do not twist or loop the wires around the terminals. In and out wires for terminal connection must be cut, stripped, a
Résumé du contenu de la page N° 11
F01U029847-01.book Page 11 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 11 3.2.4 Four-wire Loop Termination One D275 End-of-Line Module (refer to Figure 3.5 on page 19) or F220-B6E Power Supervision Base (refer to Figure 3.4 on page 18) is required for each loop when using four-wire bases. 3.3 Wire Optional Remote Annunciators If using the optional DRA-5 Remote Alarm Indicator, connect the positive (red) wire to terminal b1 and the nega
Résumé du contenu de la page N° 12
F01U029847-01.book Page 12 Thursday, March 1, 2007 9:27 AM 12 en | Install the Bases F220 Series Detectors with F220-B6RS Bases 3.4.1 NAC Configurations In these configurations, the sounders are controlled and powered from the control panel’s NAC power circuit or a remote NAC power circuit. The positive (+) wire from the NAC or D132B Multi-use Reversing Relay Module connects to Terminal 5 and the negative (-) wire connects to Terminal 4 (refer to Figure 3.2, Item 3 on page 14). The soun
Résumé du contenu de la page N° 13
F01U029847-01.book Page 13 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 13 3.4.2 Local Configurations In these configurations, the sounders are controlled and powered from the control panel’s power circuit (refer to Figure 3.2, Items 1 and 2 on page 14). The initiating device circuit (IDC) wires connect to Terminals 1 and 2 (refer to Figure 3.2, Items 3 and 4 on page 14). The DIP Switches are set for one of the following patterns: Tem
Résumé du contenu de la page N° 14
F01U029847-01.book Page 14 Thursday, March 1, 2007 9:27 AM 14 en | Install the Bases F220 Series Detectors with F220-B6RS Bases _ _ 1 1 + + F220-B6RS b2 b1 4 4 a1/a2c 4 5 C 5 NO 3 2 + + 1 3 3 _ _ + + 2 2 _ _ 1. Base Power: positive (+) powers the sounders from and negative (-) resetta- the control panel so that ble auxiliary power input all sounders follow the from the control panel or control panel’s NAC set- from a previous four-wire ting. base. 4. Optional interconnection 2. Positive
Résumé du contenu de la page N° 15
F01U029847-01.book Page 15 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 15 Position 1 and 2 on; Sounder output configured for steady 3 and 4 either both on signal (continuous tone) or both off. O N D I P 1 23 4 Position 1, 2, and 3 on; Sounder output configured for 4 off. Temporal Code 3 signal O N D I P 12 3 4 Position 1, 2, and 4 on; Sounder output configured for March 3
Résumé du contenu de la page N° 16
F01U029847-01.book Page 16 Thursday, March 1, 2007 9:27 AM 16 en | Install the Bases F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. + First Interconnected Loop 5 _ _ F220-B6RS F220-B6RS + + + + D275 1 + _ a1/a2 c a1/a2 c + 12 VDC + 24 VDC 4 _ _ b2 b1 b2 b1 _ Common (-) 3 _ + _ 3 3 + 4 4 2 2 5 5 1 1 + ++ + 2 _ _ _ _ _ _ _ _ + + + + 5 Last Interconnected Loop _ F220-B6RS F220-B6RS + + + + D275 1 _ + a1/a2 c a1/a2 c + 12
Résumé du contenu de la page N° 17
F01U029847-01.book Page 17 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 17 1. Positive (+) and negative Supervision Base or a (-) resettable auxiliary D275 Power Supervision power either in parallel Module. originating from the same 4. When connecting a D275, power supply or run from connect the positive (+) separate power supplies. wire to the yellow input 2. Positive (+) and negative (24 VDC) and the negative (-) initiating device
Résumé du contenu de la page N° 18
F01U029847-01.book Page 18 Thursday, March 1, 2007 9:27 AM 18 en | Install the Bases F220 Series Detectors with F220-B6RS Bases _ 1 + 4 b2 b1 a1/a2 c F220-B6E* C NO 3 C 5 4 NO 2 5 1 6 3 + 2 _ 1. Power input (positive [+] previous four-wire base. in on terminal b2; negative 3. Jumper connecting [-] in on terminal a1/a2) terminals 2 and 3. from the control panel or 4. Place an appropriate EOL from a previous four-wire resistor (refer to the base. control panel’s installation 2. Initiating
Résumé du contenu de la page N° 19
F01U029847-01.book Page 19 Thursday, March 1, 2007 9:27 AM F220 Series Detectors with F220-B6RS Bases Install the Bases | en 19 The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads. CAUTION! Do not connect relays to inductive or capacitive loads. Use with resistive loads only. ! 3.5.2 Wire D275 Power Supervision Module When a D275 Module is used with 24 VDC systems, connect the yellow wir
Résumé du contenu de la page N° 20
F01U029847-01.book Page 20 Thursday, March 1, 2007 9:27 AM 20 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases 4 Install the Detector Heads 4.1 Mount the Detector Heads CAUTION! Before mounting detector heads, all terminal screws in the base including those not wired must be ! tightened to prevent loose screw heads from making i intermitent electrical contact with the detector head. NOTE! When using F220-B6RS Sounder Bases, set the DIP switches for desired opera