OPERATING MANUAL
FIRELARM 2500
4 ZONE
FIRE ALARM CONTROL PANEL
CPG Signals
th
2519 4 Ave., P.O. Box 590, Moline, IL 61265
(800) 577-5758 / (309) 762-0731 / FAX (309) 762-8215
www.cpglifesafety.com CPG #2561255 Rev. A 0209
Resumen del contenido incluido en la página 2
CPG #2561255 FIRELARM 2500 Operating Manual Warranty CPG products are covered by a limited warranty. See CPG’s warranty statement for more information (document #780-0762).
Resumen del contenido incluido en la página 3
Contents CPG #2561255 FIRELARM 2500 Operating Manual Contents 1 Overview...............................................................................1-1 1.1 General description...................................................................................................................1-1 1.2 System features.........................................................................................................................1-1 1.3 Specifications ..............................
Resumen del contenido incluido en la página 4
CPG #2561255 FIRELARM 2500 Operating Manual 4.1.1 B1 Strobe device......................................................................................................................4-1 4.1.2 B1 Temporal pattern ................................................................................................................4-1 4.1.3 Reverse polarity circuits configuration .....................................................................................4-2 4.1.4 Annunciator disconnect.
Resumen del contenido incluido en la página 5
CPG #2561255 FIRELARM 2500 Operating Manual 1 Overview 1.1 General description The FIRELARM 2500 is an economical, conventional Fire Alarm Control Panel (FACP) with an extensive list of features. When installed with an appropriate battery backup supply, the FireLarm 2500 provides a complete fire alarm control system for most applications. Available accessories include liquid crystal display (LCD), zonal digital alarm communicator transmitter (ZDACT), remote annunciators, and NAC Style Z
Resumen del contenido incluido en la página 6
CPG #2561255 FIRELARM 2500 Operating Manual 1.3 Specifications 1.3.1 Electrical specifications Primary (AC) power: 120VAC, 60 Hz, 1.5A max Accessory (battery) voltage 24VDC; (charging current, 1.0A) Control Unit Requirements: Standby current 110mA, 24VDC (not including auxiliary devices and modules)200mA, 24VDC (not including auxiliary devices Alarm current and modules) Output Ratings: 1 System alarm contacts SPDT, 2A, 30VDC, 0.6 power factor System trouble contacts SPDT, 2
Resumen del contenido incluido en la página 7
CPG #2561255 FIRELARM 2500 Operating Manual • Size 18-½" x 14-¼" x 3-¾" • Finish Red. • Knockouts Combination ½" / ¾", 2 on each side, top and back. • Option Bezel trim for semi-flush mounting. 1.3.3 Service use: NFPA-72 • Local • Auxiliary (PPU) • Remote Station (PPU) • Central Station (PPU) • PPU - Protected Premise Unit. 1 1.3.4 Listings and approvals • UL Listed (S6521, Guide UOJZ) 2 • CSFM Listed (7165-0476:154) 3 4 5 A B C D E 1-3
Resumen del contenido incluido en la página 8
CPG #2561255 FIRELARM 2500 Operating Manual 1 1-4 Contents
Resumen del contenido incluido en la página 9
CPG #2561255 FIRELARM 2500 Operating Manual 2 Operation 2.1 Touchpad The touchpad provides user control over the operation of the panel. It is readily accessible when the cover is open. Figure 2-1. FireLarm 2500 Touchpad. 2 3 4 Primary Primary Function Description Function Resets all alarm circuits if condition has been corrected, removes power from initiating 5 device circuit and auxiliary power from smoke detectors for 7 seconds. Disables notification appliance circuit and troub
Resumen del contenido incluido en la página 10
CPG #2561255 FIRELARM 2500 Operating Manual Secondary Secondary Function Description Function Deletes the value at the cursor location when entering numeric values. (DELETE) Numeric entry of 1. Numeric entry of 2. Numeric entry of 3. Numeric entry of 4. Numeric entry of 5. 1 Numeric entry of 6. Numeric entry of 7. Numeric entry of 8. 2 Numeric entry of 9. Numeric entry of 0. Confirm change
Resumen del contenido incluido en la página 11
CPG #2561255 FIRELARM 2500 Operating Manual 2.3 Normal Standby Condition The AC LED indicator is on with all other LED’s off. The fire alarm system is constantly monitoring all circuits for alarm signals, faults and remote communication. The panel optional LCD will display SYSTEM NORMAL when the system is operating as normal. 2.4 Silence and reset operation. 2.4.1 Silencing a non-normal condition (buzzer or NAC) Press . Press again to silence NAC if buzzer was silenced fir
Resumen del contenido incluido en la página 12
CPG #2561255 FIRELARM 2500 Operating Manual 2.5.3 NAC trouble / silence Notification appliance circuit: An increase of current to approximately 3.5mA when not in alarm or a decrease in current to approximately 1.5mA on the notification appliance circuit will result in the following: Operation of the bell trouble LED. Operation of all system trouble indications (section 2.5.11 System trouble). Trouble zone number and name is displayed on the optional LCD. A current in excess of 2
Resumen del contenido incluido en la página 13
CPG #2561255 FIRELARM 2500 Operating Manual With the exception of the loss of the AC-ON LED and transfer of the auxiliary trouble relay contacts, none of the trouble indicators will operate on loss of AC unless an adequately charged battery is connected to the proper terminals. 2.5.8 Auxiliary power output conditions Loss of output of the auxiliary power will result in the following: Operation of the auxiliary power LED. Operation of all system trouble indications (see section 2.5.
Resumen del contenido incluido en la página 14
CPG #2561255 FIRELARM 2500 Operating Manual 1 2 2-6 Contents
Resumen del contenido incluido en la página 15
CPG #2561255 FIRELARM 2500 Operating Manual 3 Installation 3.1 Safety message to installers People's lives depend on your safe installation of our products. It is important to read, understand, and follow all instructions shipped with this product. The Facilities Engineer and the Safety Engineer should make selection of mounting location for this product, its controls, and routing of wire. Listed below are some other important safety instructions and precautions you should follo
Resumen del contenido incluido en la página 16
CPG #2561255 FIRELARM 2500 Operating Manual 3.2.5 Requirements for Central Station Fire Alarm Systems • Connect both phone lines to the optional ZDACT and OPLCD and program the telephone numbers for the reporting station. • Set the AC trouble report delay from 6 to 12 hours. 3.3 Installing the cabinet (and optional bezel) Figure 3-1. Surface mounting dimensions Figure 3-2. Semi-flush mounting dimensions 1 2 3 1. The FIRELARM 2500 unit may be surface mounted or Figure 3-3. Trim be
Resumen del contenido incluido en la página 17
CPG #2561255 FIRELARM 2500 Operating Manual 3.4 Wiring Refer to Figures 3-5 through 3-7 for wiring information. 1. Install all required conduits, external wiring. With the AC power turned off at the circuit breaker panel, connect the 120VAC hot (black), neutral (white) and ground (green) wire to the panel as shown on the power supply connection drawing (Figure 3-7). 2. If not already done, install the main board into the cabinet and connect the transformer secondary leads to connector
Resumen del contenido incluido en la página 18
CPG #2561255 FIRELARM 2500 Operating Manual Table 3-1: Current Requirements. Module/Device Standby mA Alarm mA 2500 with LCD display 170 310* 2500 without LCD display 105 250 CAM (Class A module) 0 25 RALCD (Remote Annunciator) 95 115 ZDACT (Digital Alarm Communicator) 30 50 MBM module 30 15 (250 momentary) PAM-1 or PAM-2 Relay 15 15 *Includes one zone short circuit current. Table 3-2: Secondary Power Requirements. 1 NFPA-72 National Fire Alarm Code Standby Time Alarm Time
Resumen del contenido incluido en la página 19
CPG #2561255 FIRELARM 2500 Operating Manual Figure 3-4. Motherboard. # !" % $ #
Resumen del contenido incluido en la página 20
CPG #2561255 FIRELARM 2500 Operating Manual Figure 3-6. Device Wiring 1 2 3 3-6 Contents TRANSFORMER BATTERY ZONE 1 ZONE 2 SUPERVISORY REMOTE ANNUNCIATOR (SUPERVISED) (SUPERVISED) (SUPERVISED) (SUPERVISED) CONNECTOR CONNECTOR (2 MAX, 100mA PER UNIT) (SUPERVISED) 34 34 56 78 9 10 11 12 13 14 15 16 17 18 E (+) (+) (-) (-) (+) (+) (-) (-) D D* GND +24V EARTH P2 BATT (+) (-) TB1 TB4 (OPTIONAL) SECONDARY WINDING OF REMOTE ANNUNCIATOR TRANSFORMER 5.1K 5.1K POWER RATING 120VAC - 60 HZ TYPIC