Air-Cooled Condenser
Installation & Operation
Bulletin No. H-IM-90 August 2008 Part Number 25007301
Replaces.H-IM-90,.March.2006
Table of Contents
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 . . . . . . . . . . . . . .
System.Warranty .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Resumen del contenido incluido en la página 2
Inspection Unit Location Responsibility.should.be.assigned.to.a.dependable.individual.at. Units.are.designed.for.outdoor.application.and.may.be.mounted. the.job.site.to.receive.material ..Each.shipment.should.be.carefully. on.a.roof.or.concrete.slab.(ground.level.installation) ...Roof. mounted.units.should.be.installed.level.on.steel.channels.or.an. checked.against.the.bill.of.lading .. The.shipping.receipt.should. not.be.signed.until.all.items.listed.on.the.bill.of.lading.have.been. I-beam.
Resumen del contenido incluido en la página 3
Drawing 1. Rigging Instructions 3
Resumen del contenido incluido en la página 4
Space and Location Requirements The.most.important.consideration.which.must.be.taken. Another.consideration.which.must.be.taken.is.that.the.unit. into.account.when.deciding.upon.the.location.of.air-cooled. should.be.mounted.away.from.noise.sensitive.spaces.and.must. equipment.is.the.provision.for.a.supply.of.ambient.air.to.the. have.adequate.support.to.avoid.vibration.and.noise.transmission. condenser,.and.removal.of.heated.air.from.the.condenser.area .. into.the.building ..Units.should.be.mount
Resumen del contenido incluido en la página 5
Notes: Typical Arrangements Figure.1.illustrates.a.typical.piping.arrangement.involving.a. 1 .. All.oil.traps.are.to.be.as.short.in.radius.as.. . remote.condenser.located.at.a.higher.elevation,.as.commonly. . possible ..Common.practice.is.to.fabricate.the.. . encountered.when.the.condenser.is.on.a.roof.and.the.compressor. . trap.using.three.90.degrees.ells . . and.receiver.are.on.grade.level.or.in.a.basement.equipment. room .. 2 .. Pressure.relief.valves.are.recommended.at.the.. . . . condenser.
Resumen del contenido incluido en la página 6
Discharge Lines The.proper.design.of.discharge.lines.involves.two.objectives:. 1 .. To.minimize.refrigerant.pressure.drop,.since.high.. . 2 .. To.maintain.sufficiently.high.gas.velocity.to.carry.oil.. pressure.losses.cause.increased.compressor.. . . . through.to.the.condenser.coil.and.receiver.at.all.loading.. horsepower.per.ton.of.refrigerant . . conditions . Table 1. Tons of Refrigeration Line Size Discharge Line Drain Line Type L Copper Velocity 100 FPM Refrigerant R-22 Sat. Suction Temp
Resumen del contenido incluido en la página 7
Diagram 1. Typical Condenser Wiring Diagram with Fan Cycle Controls 7
Resumen del contenido incluido en la página 8
Start-Up Fan Cycling Check.for.proper.fan.rotation ...Air.is.drawn.through.the.coil.on.all. A.decrease.in.ambient.air.temperature.results.in.a.capacity. units ...Be.sure.the.fans.turn.freely . . increase.in.the.air-cooled.condenser .. This.capacity.increase.is. . directly.proportional.to.the.temperature.difference.between.the. Rotation.of.the.motors.and.blades.should.be.in.a.“CW”.direction. condensing.temperature.and.the.temperature.of.the.ambient. looking.at.the.unit.from.the.blade.side ..
Resumen del contenido incluido en la página 9
Fan Cycling Head Pressure Controls Flooding Head Pressure Controls Condenser.fans.are.cycled.to.maintain.adequate.head.pressure .. Another.means.of.head.pressure.control.is.to.change.the. Ambient.and.pressure.fan.cycling.are.available.as.optional. condenser.capacity.by.filling.the.inside.of.the.condenser.with. equipment . . liquid.refrigerant ..Flooding.controls.are.ideal.for.condensers. . operating.in.low.ambient.conditions.(beyond.the.limits.of.fan. Ambient.fan.cycling.cycles.fans.in.respo
Resumen del contenido incluido en la página 10
Table 3. Minimum Ambient for Fan Cycling Numb er of Fans Single Double Design T.D.* Row Row 30 25 20 15 10 . 2. 4. 35. 45. 55. 60. 70 . 3. 6. 15. 30. 40. 55. 65 . 4. 8. 0. 15. 30. 45. 60 . 5. 10. 0. 10. 20. 35. 55 . 6./.7. 12./.14. 0. 0. 10. 30. 50 *.Based.on.maintaining.90°F.minimum.condensing.temperature . Table 4. Mechanical Fan Cycling Thermostat Settings ......... . Number of Fans Single Double Design Thermostat Setting Row Rows T.D. 1 2 3 4 5 . 2. 4. 30. 60 . .
Resumen del contenido incluido en la página 11
Table 5. Electronic Fan Cycling Thermostat Settings * Number of Fans A350 S350 Temperature Stage Modules Single Double Design Set Offset Settings Row Rows T.D. Point 2 3 4 5 . . . 30. 60 . . . 25. 65 . 2. 4. 20. 70 . . . 15. 75 . . . 10. 80 . . . 30. 60. 20 . . . 25. 65. 10 . 3. 6. 20. 70. 10 . . . 15. 75. 10 . . . 10. 80. 15 . . . 30. 60. 10. 30 . . . 25. 65. 10. 25 . 4. 8. 20. 70. 5. 20 . . . 15. 75. 5. 15 . . . 10. 80. 5. 10 . . .
Resumen del contenido incluido en la página 12
Table 7. Refrigerant Charge for Fan Cycling plus Flooded Condenser (lbs. R-22) 25° TD 20° TD 15° TD 10° TD Summer Model* Charge 40°F 20°F 0°F -20°F 40°F 20°F 0°F -20°F 40°F 20°F 0°F -20°F 40°F 20°F 0°F -20°F 1 8 7 8 9 9 8 9 10 10 9 10 11 11 13 12 12 12 2 10 9 12 13 14 11 13 14 15 13 14 15 16 17 18 17 18 3 10 1 6 8 10 4 8 10 11 7 10 12 13 10 13 14 14 4 15 2 9 12 15 7 12 15 17 12 16 18 19 17 19 21 22 5 29 4 17 24 29 14 24 30 34 24 31 36 39 33 38 41 43 6 22 0 3 10 15 0 10 16 20 0 17 22 25 0 24 27
Resumen del contenido incluido en la página 13
Table 9. Flooded Charge Temperature Difference Factor Design T.D. Ambient, °F 30 25 20 15 10 +60 – 0 .38 1 .0 1 .74 2 .46 +40 0 .59 0 .80 1 .0 1 .19 1 .40 +20 0 .76 0 .88 1 .0 1 .13 1 .25 0 0 .84 0 .91 1 .0 1 .07 1 .16 -20 0 .88 0 .93 1 .0 1 .05 1 .13 Table 10. Model Cross Reference Model Reference *NH *NL *NX *NQ *NE 1 *NH-S01-A007 *NL-S01-A007 *NX-S01-A006 *NQ-S01-A005 *NE-S01-A008 2 *NH-S01-A009 *NL-S01-A008 *NX-S01-A008 *NQ-S01-A006 *NE-S01-A009 3 *NH-S02-A011 *NL-S02-A010 *NX-S02-A010 *NQ-S
Resumen del contenido incluido en la página 14
In-Warranty Return Material Procedure Material.may.not.be.returned.except.by.permission. of.authorized.factory.service.personnel.of.Heatcraft. Refrigeration.Products.in.Stone.Mountain,.Georgia ..A. “Return.Goods”.tag.will.be.sent.to.be.included.with.the. returned.material ..Enter.the.required.information.on.the. tag.in.order.to.expedite.handling.at.our.factories.and. prompt.issuance.of.credits ...All.parts.shall.be.returned. to.the.factory.designated.on.the.“Return.Goods”.tag,. transportation
Resumen del contenido incluido en la página 15
E Series Motors with Integrated Variable Speed E.Series.units.use.an.EC.motor/fan.blade.combination.to.provide.variable.speed.condenser.control ...All.components.required. to.run.the.motor.at.variable.speeds.are.built.into.the.motor . Warning! When.connecting.the.unit.to.the.supply.power,.. . dangerous.voltages.occur ..Do.not.open.the.motor.within.. . the.first.5.minutes.after.disconnection.of.all.phases . Be sure that the unit is isolated. Warning! Dangerous.external.voltages.can.be.present..
Resumen del contenido incluido en la página 16
Integration constant The.integration.constant.switch.provides.ability.to.change. controller.from.a.proportional.only.control.to.a.proportional. plus.integral.control .. To.provide.the.most.responsive.system. to.maintain.a.stable.head.pressure,.it.is.recommended.this. setting.be.left.on.“fast . ” . Head Pressure Setpoint The.head.pressure.setpoint.potentiometer.is.adjustable. from.90-250.psig ...A.typical.setpoints.are.from.170-200.psig ... Reverse acting or direct acting mode of operation Note:.
Resumen del contenido incluido en la página 17
Master/Slave Configuration EC Motor Wiring The.EC.motor.control.signals.are.wired.in.a.Master/ Slave.configuration ... This.configuration.allows.for.the. All.EC.motor.wiring.is.done.at.the.factory ...If.any.motor. maximum.sound.and.energy.reduction.as.well.as.the. wiring.needs.to.be.done.in.the.field,.the.diagram.below. most.stable.head.pressure.control ... The.control.signal.is. indicates.the.terminal.pin.configurations.inside.the. delivered.to.the.master.motor.(located.at.the.header.end. motor
Resumen del contenido incluido en la página 18
Diagram 2. Typical 1 x 4 EC M TYPICAL ot 1X4 EC MOT or Wiring with 0-10V DC C OR WIRING ontrol Signal WITH 0-10V DC CONTROL SIGNAL CONTROL WIRING POWER WIRING 0 - 10V DC L1 CONTROL 3Ø POWER SIGNAL L2 SUPPLY L3 PE KL3 KL2 KL1 PE 12 11 10 9 8 7 6 5 4 3 2 1 3 2 1 3 2 1 FAN 1 (HEADER FAN) L1 3Ø POWER L2 SUPPLY BLK L3 RED PE KL3 KL2 KL1 PE 12 11 10 9 8 7 6 5 4 3 2 1 3 2 1 3 2 1 FAN 2 L1 3Ø POWER L2 SUPPLY BLK L3 RED PE KL3 KL2 KL1 PE 12 11 10 9 8 7 6 5 4 3 2 1 3 2 1 3 2 1 FAN 3 L1 3Ø POWER L2 SUPPLY
Resumen del contenido incluido en la página 19
KL3 KL3 KL3 KL3 KL3 KL3 KL3 KL3 KL3 KL3 SENSOR BLK BLK BLK BLK BLK BLK BLK BLK BLK BLK RED RED RED RED RED RED RED RED RED RED Diagram 3. Typical EC Condenser Wiring Diagram with External Signal 3ÿ/60Hz FAN MOTOR IDENTIFICATION 5 4 3 2 1 USE COPPER CONDUCTORS ONLY FACTORY WIRING FIELD WIRING DISCONNECT SWITCH L1 L2 L3 FAN SPEED CONTROL CIRCUIT 0 to 10V DC T1 T2 T3 TERMINAL T1 T2 BOARD 1 TERMINAL BOARD 2 M1 8 - GND 7 - 0-10V PWM 2 - GND 1 - OUT M2 8 - GND 7 - 0-10V PWM 2 - GND F5 F4 F3 F2 F1 1 -
Resumen del contenido incluido en la página 20
Installation Check List Condenser Start Up Date Model # Serial # Electrical Voltage Amperage Installer: Name & Address Telephone: Please retain this information with the condenser. Since.product.improvement.is.a.continuing.effort,.we.reserve.the.right.to.make.changes.in. specifications.without.notice . ™ The name behind the brands you trust. CLIMATE Commercial Refrigeration Parts CONTROL 20 H-IM-90-0808.