Owner’s Manual
Liquid-cooled, Prepackaged
Standby Generators
Model Number: ASPAS1CCL015
Not intended for use in critical life support applications.
! !
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT
INSTALLATION!!
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
This manual should remain with the unit.
Resumen del contenido incluido en la página 2
The operator is responsible for proper and safe use INTRODUCTION of the equipment. Carrier strongly recommends that Thank you for purchasing a Carrier home standby the operator read this Owner's Manual and thor- generator system. oughly understand all instructions before using this Every effort was expended to make sure that the equipment. Carrier also strongly recommends information and instructions in this manual are both instructing other users to properly start and operate accurate and curre
Resumen del contenido incluido en la página 3
Table of Contents Carrier Liquid-cooled 15 kW Generators INTRODUCTION ..................................IFC Section 3 — OPERATION....................12 3.1 Control Console Components......................12 SAFETY RULES ......................................2 3.2 Manual Transfer and Startup......................13 Section 1 — GENERAL 3.3 Automatic Operation ..................................13 INFORMATION..................4 3.4 Weekly Exercise Cycle..................................13 1.1 Genera
Resumen del contenido incluido en la página 4
IMPORTANT SAFETY INSTRUCTIONS Carrier Liquid-cooled 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all ! ! operators, potential operators, and service and repair technicians for this equipment. SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. ! ! In
Resumen del contenido incluido en la página 5
IMPORTANT SAFETY INSTRUCTIONS Carrier Liquid-cooled 15 kW Generators place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface EXPLOSION HAZARDS to reduce shock hazard. Properly ventilate any room or building housing the gener- Do not handle any kind of electrical device while standing ator to prevent build-up of explosive gas. in water, while barefoot, or while hands or feet are wet. Do not smoke around the generator. Wipe up a
Resumen del contenido incluido en la página 6
Section 1 - General Information Carrier Liquid-cooled 15 kW Generators 1.1 GENERATOR 1.3 AUTOMATIC SYSTEM OPERATION This equipment is a liquid-cooled, engine-driven gen- When this generator, along with its transfer switch, has erator set. The generator is designed to supply elec- been installed and interconnected, a circuit board in trical power that operates critical electrical loads the generator panel constantly monitors utility power during utility power failure. The unit has been facto- sou
Resumen del contenido incluido en la página 7
Section 1 - General Information Carrier Liquid-cooled 15 kW Generators 1.7.1 LOW OIL PRESSURE SWITCH 1.6 GENERATOR FUEL SYSTEM The generator has been factory tested and adjusted This switch is normally-closed (N.C.), but is held using a natural gas fuel system. If propane (LP open by engine oil pressure during engine running. requirements) gas is preferred, refer to Section 1.12. Should operating oil pressure drop below about 8-10 psi (55-68 kPa), the switch contacts close and the Recommended f
Resumen del contenido incluido en la página 8
R24 R84 R83 R76 R23 R75 CR13 R88 R R77 CR14 R62 R9 CR15 R87 CR36 R37 CR20 CR17 R43 R38 R32 R42 R39 CR18 R48 R44 R35 R52 R33 R46 R36 R74 R41 R51 R29 R47 R40 CR3 R27 R8 R7 R86 R65 R30 R85 CR30 R31 R61 R19 CR32 R4 CR12 R59 R5 R22 R26 R6 R21 R25 R57 R20 CR2 CR16 R53 CR38 R18 R72 R17 R71 R16 R70 R78 CR8 CR21 R63 CR19 R13 R69 R15 CR24 R14 CR29 R81 R50 R54 R3 R2 R66 R67 CR34 CR35 R82 CR40 CR33 J1 17 1 Section 1 — General Information Carrier Liquid-cooled 15 kW Generators LED 3 is GREEN. This LED will
Resumen del contenido incluido en la página 9
Section 1 — General Information Carrier Liquid-cooled 15 kW Generators 1.10.2 ENGINE SPECIFICATIONS 1.12 RECONFIGURING THE FUEL Make..............................................................................Mitsubishi SYSTEM 3 Displacement ..............................................92 inches (1.5 liters) NOTE: Cylinder Arrangement......................................................4, in-line All models are configured for natural gas from the Valve Arrangement............................
Resumen del contenido incluido en la página 10
Section 2 — Installation Carrier Liquid-cooled 15 kW Generators 1.14 ENGINE OIL RECOMMENDATIONS 1.16 BEFORE INSTALLATION The unit has been filled with 15W-40 engine oil at the Before installing this equipment, check the ratings of factory. Use a high-quality detergent oil classified “For both the generator and the transfer switch. Read Service SJ or latest available.” Detergent oils keep the “Emergency Isolation Method” and “Total Circuit engine cleaner and reduce carbon deposits. Use oil Isolat
Resumen del contenido incluido en la página 11
Section 2 — Installation Carrier Liquid-cooled 15 kW Generators NOTE: Where strong prevailing winds blow from one direction, face the generator air inlet openings into It is essential to use the latest version of any stan- the prevailing winds. dard to ensure correct and current information. Install the generator as close as possible to the NFPA No. 37, STATIONARY COMBUSTION transfer switch. This reduces the length of wiring ENGINES AND GAS TURBINES. and conduit. NFPA No. 76A, ESSENTIAL E
Resumen del contenido incluido en la página 12
Section 2 — Installation Carrier Liquid-cooled 15 kW Generators Proper grounding helps protect personnel against 2.5 EMERGENCY CIRCUIT ISOLATION electrical shock in the event of a ground fault condi- METHOD tion in the generator or in connected electrical This prevents overloading the generator by keeping devices. In addition, grounding helps dissipate static electrical loads below the wattage/amperage capacity electricity that often builds up in ungrounded of the generator. If the generator is
Resumen del contenido incluido en la página 13
Section 2 — Installation Carrier Liquid-cooled 15 kW Generators Spilled electrolyte is to be washed down with an 2.10 BATTERY INSTALLATION acid-neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon- DANGER ate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until Standby generators installed with automatic the evidence of reaction (foaming) has ceased. The ! transfer switches will crank and start automati- result
Resumen del contenido incluido en la página 14
Section 3 — Operation Carrier Liquid-cooled 15 kW Generators Before starting the generator for the first time, the 2.11.7 ELECTRICAL SYSTEM installer must complete the following procedures. For Make sure the generator is properly connected to an follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.” approved earth ground and/or ground rod. Make sure the generator battery is fully charged, 2.11.2 TRANSFER SWITCH properly installed and interconnecte
Resumen del contenido incluido en la página 15
Section 3 - Operation Carrier Liquid-cooled 15 kW Generators 3.1.2 FAULT INDICATOR LAMP 3.4 WEEKLY EXERCISE CYCLE The generator will start and exercise once every seven The lamp goes ON when one or more of the following days. During this weekly exercise, the unit runs for engine faults occurs and when engine shuts down. about 20 minutes and shuts down. Transfer of loads Low oil pressure Overcrank to generator output does not occur during the exer- High coolant temperature Overspeed ci
Resumen del contenido incluido en la página 16
Section 4 — Maintenance Carrier Liquid-cooled 15 kW Generators 4.1 MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES The exhaust system parts from this product get extremely hot and remains hot after shutdown. A. EVERY THREE MONTHS High grass, weeds, brush, leaves, etc. must 1.Check battery state of charge and condition. remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust 2.Inspect and test fuel system. system. 3.Check transfer switch. 4.Inspect ex
Resumen del contenido incluido en la página 17
Section 4 — Maintenance Carrier Liquid-cooled 15 kW Generators 4.4.2 BATTERY FLUID 4.5.7 INSPECT EXHAUST SYSTEM Check battery electrolyte fluid at least once a month. Inspect the exhaust system at least once every three Fluid should cover separators in all battery cells. If months. Check all exhaust system pipes, mufflers, fluid level is low, add distilled water to cover tops of clamps, etc. for condition, tightness, leaks, security, separators. DO NOT USE TAP WATER IN BATTERY. damage. 4.4.3 E
Resumen del contenido incluido en la página 18
Section 4 — Maintenance Carrier Liquid-cooled 15 kW Generators Figure 4.2 - Oil Filter 4.5.12 SPARK PLUGS Reset the spark plug gap or replace the spark plugs as necessary. See Section 4.7. 1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is que
Resumen del contenido incluido en la página 19
Section 4 — Maintenance Carrier Liquid-cooled 15 kW Generators Once each year, have the generator cleaned and DANGER inspected by a dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside Storage batteries give off explosive hydrogen the control console should be cleaned and inspected gas. This gas can form an explosive mixture at this time as well. around the battery for several hours after Finally, have the insulation resistance of stator and charging. The s
Resumen del contenido incluido en la página 20
Section 4 — Maintenance Carrier Liquid-cooled 15 kW Generators 4.7 SCHEDULED MAINTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe applica- tion. Use the unit hour meter or calendar time, whichever occurs first, from the