Resumen del contenido incluido en la página 1
TECHNICAL MANU TECHNICAL MANUAL AL
TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL
GPH 13 M Series Multi Position
Package Heat Pump Units
with R410A
• Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.
• All safety information must be followed as provided in the Service Manual.
• Refer to the appropriate Parts Catalog for part number information.
• Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC techni
Resumen del contenido incluido en la página 2
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GP H 13 36 M 4 1 A A BRAND: MINOR REVISION: ® G: Goodman A: Initial Release PRODUCT Brand FAMILY: ® A: Amana H: Heat Pump Brand REFRIGERANT: 4: R-410A PRODUCT PRODUCT TYPE: MAJOR REVISION: SERIES: Package Unit CONFIGURATION: A: Initial Release 13: Up to 13 SEER M: Mult-
Resumen del contenido incluido en la página 3
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GPH1324M41AB GPH1330M41AB GPH1336M41AB GPH1342M41AB GPH1348M41AB GPH1360M41AB The United States Environmental Protection Agency (“EPA”) has issued various regulations re- W WARNI ARNING NG garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow th
Resumen del contenido incluido en la página 4
PRODUCT DESIGN GPH13 (M Series) Package Units are designed for outdoor Air for condensing (cooling cycle) or evaporation (heating installations only in either residential or light commercial ap- cycle) is drawn through the outdoor coil by a propeller fan, plications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes. and is discharged vertically out the top of the unit. The out- They are designed for 208/230 volt single phase applications. door coil is designed for .0 static. No additional res
Resumen del contenido incluido en la página 5
PRODUCT DESIGN In installations where the unit is installed above ground level and not serviceable from the ground (Example: roof top in- stallations) the installer must provide service platform for ser- vice person with rails or guards in accordance with local codes or ordinances, or, in their absence, with the latest edition of the Uniform Mechanical Code Section 305. NOTE: Unit can also use roof curb (and platform for leveling, where necessary) to utilize bottom discharge. WARNING TO PREVENT
Resumen del contenido incluido en la página 6
PRODUCT DESIGN GPH13[24-60]M41* HKR ELECTRICAL DATA Circuit #1 Circuit #2 Maximum Maximum Actual Minimum Circuit Minimum Circuit kW & BTU Overcurrent Overcurrent Ampacity Ampacity Protection (amps) Protection (amps) at 240V at 208 / 240V at 208 / 240V at 208 / 240V at 208 / 240V GPH1324M41* HKR05A,CA 24 / 27 30 / 30 ---- ---- 4.75 / 16,200 HKR08A,CA 33 / 28 40 / 40 ---- ---- 7.00 / 23,800 HKR10A,CA 45 / 51 60 / 60 ---- ---- 9.50 / 32,400 GPH1330M41* HKR05A,CA 24 / 27 30 / 30 -- -- 4.75 / 16,200
Resumen del contenido incluido en la página 7
PRODUCT DIMENSIONS GPH13[24-60]M41* 47 51 POWER WIRE ? A ENTRANCE 16 4 1/8 2 1/8 1 3/8 5 ½ 16 6 ½ B 8 2 34 RETURN ? B SUCTION/LIQUID PRESSURE PORT SUPPLY 3 CONDENSATE DRAIN CONTROL 18 7/8 CONNECTION WIRE 3/4” NPT FEMALE ENTRANCE BLOWER ACCESS PANEL MEDIUM CHASSIS GPH1324M41* GPH1330M41* GPH1336M41* GPH1342M41* LARGE CHASSIS GPH1348M41* GPH1360M41* 7
Resumen del contenido incluido en la página 8
PACKAGE HEAT PUMP SPECIFICATIONS GPH13[24-36]M41AB GPH1324M41* GPH1330M41* GPH1336M41* COOLING COOLING CAPACITY, BTUH 24,000 29,000 34600 CAPACITY SEER / EER 13/11 13/10.8 13/10.9 HEATING BTU/h (47°) 23000 28800 34200 RATING BTU/h (17°) 12600 17000 19000 HSPF 7.7 7.7 7.7 UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 ELECTRICAL AMPS 15.8 19.0 21.3 SPECIFICATION MIN CIRCUIT AMPACITY 19.0 23.0 25.4 (1 ) 30 35 40 MAX OVERCURRENT PROTECTION COMPRESSOR TYPE SCROLL SCROLL SCROLL RA
Resumen del contenido incluido en la página 9
PACKAGE HEAT PUMP SPECIFICATIONS GPH13[42-60]M41AB GPH1342M41* GPH1348M41* GPH1360M41* COOLING COOLING CAPACITY, BTUH 40000 46500 56000 CAPACITY SEER / EER 13/11 13/11 13/10.9 HEATING BTU/h (47°) 40000 45500 55500 RATING BTU/h (17°) 21000 26000 31200 HSPF 7.7 8.0 8.0 UNIT VOLTAGE (NAMEPLATE) 208/230-60-1 208/230-60-1 208/230-60-1 ELECTRICAL AMPS 22.4 29.0 35.4 MIN CIRCUIT AMPACITY 26.8 34.5 42.0 SPECIFICATION (1) 40 50 60 MAX OVERCURRENT PROTECTION TYPE SCROLL SCROLL SCROLL COMPRESSOR RATED L
Resumen del contenido incluido en la página 10
ACCESSORIES GPH13[24-60]M41* ACCESSORIES - GPC/GPH****M MODELS Part Number Description OT18-60A Outdoor Thermostat Kit w/Lockout Stat OT/EHR18-60 Emergency Heat Relay Kit HKR Electric Heat Kit PGC101/102/103 Roof Curb PEHH101/102 Horizontal Economizer For Heat Pump, Small and Medium Chassis PEHH103 Horizontal Economizer For Heat Pump, Large Chassis PEHC101/102 Horizontal Economizer For A/C, Small and Medium Chassis PEHC103 Horizontal Economizer For A/C, Large Chassis PGMDD101/102 Manual 25
Resumen del contenido incluido en la página 11
GPH13[24-60]M41* BLOWER PERFORMANCE DATA Dry Coil Data E.S.P (In. of H O) 2 Model Speed Volts 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 CFM 667 596 -------- -------- -------- -------- -------- -------- Low 230 WATTS 153 150 -------- -------- -------- -------- -------- -------- CFM 897 841 784 713 610 -------- -------- -------- Med 230 WATTS 233 229 224 217 207 -------- -------- -------- CFM 1242 1181 1122 1057 982 883 719 617 High 230 WATTS 373 364 354 344 333 318 298 284 CFM 1097 1059 1016 959 901 818 64
Resumen del contenido incluido en la página 12
BLOWER PERFORMANCE DATA 12 BTU OUTPUT vs TEMPERATURE RISE CHART 100 600 CFM 90 700 80 800 900 1000 70 1100 1200 60 1400 1600 50 1800 2000 2200 40 2400 CFM 30 FORMULAS BTU OUTPUT = CFM x 1.08 x RISE BTU OUTPUT 20 RISE = ÷ CFM 1.08 10 100 30 40 50 60 70 80 90 110 120 130 140 150 OUTPUT BTU/HR x 1000 TEMPERATURE RISE
Resumen del contenido incluido en la página 13
COOLING PERFORMANCE DATA GPH1324M41* 13 MODEL: GPH1324M41* COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/- 2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 5963677159 636771 MBh 23.5 24.4 26.7 - 23.0 23.8 26.1 - 22.4 23.2 25.5 - 21.9 22.
Resumen del contenido incluido en la página 14
COOLING PERFORMANCE DATA GPH1324M41* 14 MODEL: GPH1324M41* COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/- 2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 5963677159 636771 MBh 24.3 24.9 26.6 28.4 23.8 24.3 26.0 27.7 23.2 23.7 25.3 27.1
Resumen del contenido incluido en la página 15
COOLING PERFORMANCE DATA GPH1330M41* 15 MODEL: GPH1330M41* EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/- 2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 59636771 59 636771 MBh 28.4 29.5 32.3 - 27.8 28.8 31.5 - 27.1 28.1 30.8 - 26.4 27
Resumen del contenido incluido en la página 16
COOLING PERFORMANCE DATA GPH1330M41* 16 MODEL: GPH1330M41* EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/- 2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 59 6367 7159 6367 7159 63 67 7159 63 67 71 5963 6771 59 63 6771 MBh 29.4 30.1 32.1 34.3 28.7 29.4 31.4 33.5 28.0 28.7 30
Resumen del contenido incluido en la página 17
COOLING PERFORMANCE DATA GPH1336M41* 17 MODEL: GPH1336M41* EXPANDED PERFORMANCE DATA COOLING OPERATION Design Subcooling, 9 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 7+/-2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 59 63 677159 63 6771 MBh 33.9 35.1 38.5 - 33.1 34.3 37.6 - 32.3 33.5 36.7 - 31.5 32.7
Resumen del contenido incluido en la página 18
COOLING PERFORMANCE DATA GPH1336M41* 18 MODEL: GPH1336M41* COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 9 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 7+/-2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 596367 7159 6367 71 MBh 35.1 35.9 38.3 41.0 34.3 35.0 37.4 40.0 33.5 34.2 36.5 39.0 3
Resumen del contenido incluido en la página 19
COOLING PERFORMANCE DATA GPH1342M41* 19 MODEL: GPH1342M41* COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/-2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963 677159 63677159 63 6771 59 63 67 71 5963677159 6367 71 MBh 39.2 40.6 44.5 - 38.3 39.7 43.5 - 37.4 38.7 42.4 - 36.5 3
Resumen del contenido incluido en la página 20
COOLING PERFORMANCE DATA GPH1342M41* 20 MODEL: GPH1342M41* COOLING OPERATION EXPANDED PERFORMANCE DATA Design Subcooling, 10 +/-2 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 10 +/-2 °F @ the compressor suction access fitting connection. Outdoor Ambient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB* Airflow 5963677159 63677159 63 677159 63 67 71 5963677159 636771 MBh 40.6 41.5 44.3 47.3 39.6 40.5 43.3 46.2 38.7 39.5 42.2 45.1