MV100 Electric Controllers
T100, T200 Thermostatic Controllers
and V2000 Radiator Valves
PRODUCT DATA
APPLICATION
THERMOSTATIC CONTROLS
The MV100, T100, T200 Controllers, when paired with V2000
Radiator Valves, provide automatic temperature control by
modulating the flow of steam or hot water through free-
standing radiators, convectors, and other heating units. They
T100M
T100
provide comfort and energy savings at affordable prices.
FEATURES
Continually monitors and adjusts room temperatur
Resumen del contenido incluido en la página 2
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES SPECIFICATIONS Materials: MV100 Electric Controller Body: Industrial grade plastic with low thermal conductivity. Fastening Ring: Plated brass. Dimensions: See Fig. 1. Internal Parts: Brass thermostat capsule, other metals. Thermal Element: Materials: T100A,M: Wax. Body: Industrial grade plastics with low thermal conductivity. T200,T100B,C,F: Liquid Ethyl Acetate (non-toxic, Fastening Ring: Plated brass. fl
Resumen del contenido incluido en la página 3
Braukmann xxxxxxxx xxxxx H MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES T100A TOP T100M TOP 2 (50) 2 (50) T100C 1 (25) 2-1/8 (54) CAPILLARY TUBE LENGTH 2-1/8 (54) 4-1/2 FT (1.4 m) 1-13/16 2-5/32 (46) (55) 3 (77) 3-5/16 (84) 2-31/32 (75) MAX. CAPILLARY TUBE LENGTH 4-1/2 FT (1.4 m) M12927 M12929 M12925A T100B 2-1/8 (54) T100F CAPILLARY TUBE LENGTH 2-1/8 (54) 2 (50) 6-1/2 FT (2m) OR 16 FT. (5m) CAPILLARY TUBE LENGTH 6-1/2 FT (2 m) 1-13/16 3-5/16 2-5/32
Resumen del contenido incluido en la página 4
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 1. T100,T200 Models. Model Control Range Mounting Capillary Description a T100A 43°F to 79°F None Components are in one unit. Direct (6°C to 26°C) T100B 48°F to 79°F Remote One 6-1/2 ft (2 m) Sensor and setpoint dial combined and remote from valve (9°C to 26°C) or 16 ft (5 m) actuator. T100C Remote Two 4-1/2 ft Components mount remotely from each other. (1.4 m) T100F 43°F to 79°F Direct with One 6-1/2
Resumen del contenido incluido en la página 5
5 6 0 MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 3. Valve Dimensions. a Size in A B Max C Valve in. in in. (mm) in in. (mm) in in. (mm) V2040D 1/2 3-3/4 (95) 4-1/16 (104) 3/4 4-3/16 (106) 4-1/16 (104) 1 4-1/2 (114)4-1/2 (114) V2040E 1/2 2-5/16 (58) 3-3/16 (98) 1 (26) 3/4 2-5/8 (66) 3-13/16 (98) 1-1/8 (29) B MAX. A 1 2-15/16 (74) 4-5/16 (110) 1-5/16 (34) V2040A 1/2 2-1/8 (54) 4-1/2 (115) 1-1/8 (28) C 3/4 2-1/2 (64) 5-3/16 (132) 1-3/16 (31
Resumen del contenido incluido en la página 6
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES One complete revolution of the black pre-setting ring equals a Pre-setting and Balancing Flow Through pre-setting of 10 (Fig. 7). Valve Body. Close valve with straight blade screwdriver by turning black pre-setting ring clockwise. M22690 Fig. 7. One complete revolution equals a pre-setting of 10. Table 4. CV Values. Pre- M22687 setting 1 2 3 4 5 6 7 Open 3/8 in. 0.29 0.58 0.87 1.16 1.45 1.68 1.80 2.00 Fig
Resumen del contenido incluido en la página 7
0 MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Typical Applications Table 5. Figure References to Typical Applications. Application Figure No. Controller Valve 8 T100A, T100M, T200, MV100 V2040D 9 T100A, T100M, T200, MV100 V2040A 10 T100A, T100M, T200, MV100 V2040E 11 T100A, T100M, T200, MV100 V2042H M12934 12 T100M, MV100 V2040A 13 T100F, MV100 V2040E Fig. 10. 14 T100F, MV100 V200LD 15 T100F, MV100 V2040D 16 T100F, MV100 V2042H 17 T100B, MV100 V2040
Resumen del contenido incluido en la página 8
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES M4640 M3190 Fig. 14. Fig. 18. M4638 M12936A Fig. 15. Fig. 19. SA123A V2042H T100A M12939 Fig. 20. M11752A Location and Mounting Fig. 16. Because these controls are thermostats that have sensors that measure air temperature in the immediate vicinity, it is critical to select an appropriate installation location. These devices are adversely affected by radiant heat, solar heat or airflow obstruction
Resumen del contenido incluido en la página 9
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES MV100 END SWITCH RED TO CIRCULATOR PUMP MULTIZONE RED 2 PANEL OR BURNER RELAY YELLOW L1 PTC RESISTANCE (HOT) YELLOW HEATER L2 3 T810/T822 1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CORRECT M16272A 2 NORMALLY OPEN END SWITCH CLOSES WHEN MV100 IS POWERED. INCORRECT 3 SUGGESTED HEAT ANTICIPATOR SETTING IS 0.35A. M12947A Fig. 21. Horizontal-body V2000 application. Fig. 22
Resumen del contenido incluido en la página 10
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 6. T100 and T200 Settings and Corresponding Temperatures in °F (°C). 0 * 12 345 6 T100A,F 32 (0) 43 (6) 46 (8) 54 (12) 61 (16) 68 (20) 73 (23) 79 (26) a T100B,C 55 (13) 61 (16) 64 (18) 68 (20) 72 (22) 75 (24) 79 (26) a a T100M 43 (6) 61 (16) 64 (18) 68 (20) 72 (22) 75 (24) 79 (26) T200 43 (6) 52 (11) 57 (14) 63 (17) 68 (20) 73 (23) 79 (26) a Setting not marked on dial. NOTE: Torque cartridge to
Resumen del contenido incluido en la página 11
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES NOTE: NOTE: Install the valve on the boiler side of the condensation takeoff to ensure that the condensation can return to While the T100 is satisfied, the V2042H is closed the boiler. and the radiator remains airlocked. Thus, no steam can enter the radiator. The airlocked 3. Verify that the steam pressure has returned to zero. condition remains until the T100 calls for heat, at which point the system
Resumen del contenido incluido en la página 12
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES TROUBLESHOOTING Refer to Table 6 for troubleshooting details. Table 7. T100/V2000 Troubleshooting. Symptom Possible Cause Solution Not all sections of the Many radiators are oversized and System is operating properly. radiator are heating. not all sections heat to maintain the desired temperature. Underheating Sensor in the wrong location. Change the sensor location or change the control type. See Installa
Resumen del contenido incluido en la página 13
MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES PRESSURIZED VALVE CARTRIDGE REPLACEMENT B The VA8200A001 Valve Cartridge Changing Tool enables the user to remove, and clean or replace the valve cartridge while D the valve remains pressurized. Boiler shutdown is not required. A WARNING Severe Scalding Hazard. Contact with hot liquid can lead to severe injury or cause death. M16273 C Exercise extreme caution when working with hot liquid. Fig. 25. Attach
Resumen del contenido incluido en la página 14
62-30482 14
Resumen del contenido incluido en la página 15
15 62-30482
Resumen del contenido incluido en la página 16
Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2006 Honeywell International Inc. 62-30482 G.R. Rev. 02-06