Owner’s Manual — Phoenix 200 MAX
Installation, Operation & Service Instructions
Read and Save These Instructions
The Phoenix 200 MAX is one of the most effective and versatile drying devices available. The 200
MAX removes more water and has more grain depression than other refrigerant dehumidifiers, even
though it only requires 7.4 amps of electricity.
The term LGR (Low Grain Refrigerant) was created to describe the unique drying capa
Resumen del contenido incluido en la página 2
Table of Contents 1 Specifications Introduction ................................................................ Part No. 4024920 1. Specifications ........................................................2 Power 0-20 Vac, 7.4 amps; 85 watts 2. Operation .............................................................2 2. T ransporting the Phoenix 200 MAX ...................2 Water 33 pints/day @ AHAM (80°F, 60%) Removal 240 pints/day @ saturation 2.2 Location .......................
Resumen del contenido incluido en la página 3
• The air inlet on top & the side outlet must be at least 2.8 Hour Meter foot from walls and other obstructions to air flow. The digital hour meter measures the cumulative time that • If the humid area is very large, dehumidification can the unit is turned on to tenths of an hour. It stores its be improved by adding an outlet duct to circulate air to total when the unit is unplugged; the previous total will be stagnant areas (see Sec. 2.5). displayed when the unit is next turned on. It
Resumen del contenido incluido en la página 4
2.10 Low Pressure Control 4 Service If the low side refrigerant pressure drops to 5 PSIG, the low pressure control opens and shuts off the compressor and blower. It is an automatically reset control. Its primary CAUTION: Servicing the Phoenix 200 MAX with its high function is to prevent damage to the compressor if a leak pressure refrigerant system and high voltage circuitry develops in the refrigeration system. It may also open if presents a health hazard which could result in death, t
Resumen del contenido incluido en la página 5
The mixture of gas and liquid refrigerant enter the 5. Defrost timer incorrectly set for conditions (Sec. 2.9 & accumulator after leaving the evaporator coil. The 4.7). accumulator prevents any liquid refrigerant from reaching 6. Defective defrost thermostat (Sec. 4.7) the compressor. The compressor evacuates the cool 7. Low refrigerant charge (Sec. 4.4). refrigerant gas from the accumulator and compresses it to 8. Air leak such as loose front cover. a high pressure and temperature to repeat
Resumen del contenido incluido en la página 6
5. Rotate the blower outlet toward you as you remove it. 9. Disconnect the wires from the capacitor. Set the Use care to avoid hooking wiring, tubing or electrical ohmmeter to the Rx scale; the capacitor is shorted components. and must be replaced if continuity exists across its terminals. If there is no needle movement with the 6. Reassembling with the new blower in the above meter set on the Rx00000 scale, the capacitor is procedure reversed. open and must be replaced. 0. Reconnect t
Resumen del contenido incluido en la página 7
If sludge is evident in the discharge line, it will 4.8 Condensate Pump likely be found in the suction line; this indicates the Condensate is automatically pumped when the water level compressor burned out while running. Sludge and acid in the pump’s reservoir rises to close the float switch or if have been pumped throughout the system. Several the pump purge switch is held in. changes of the liquid and suction filter/driers will To replace the condensate pump: probably be necessary to c
Resumen del contenido incluido en la página 8
5 Wiring Diagram Figure 3: Electrical schematic of 200 MAX Toll-Free 1-800-533-7533 8 www.thermastor.com • sales@thermastor.com
Resumen del contenido incluido en la página 9
6 Service Parts Item Part No. Qty. Description Item Part No. Qty. Description 4022254 Accumulator 9 ***** Wheel/Axle Assembly 402475 Air Filter, Pleated, 2” x 6” x 20” 4026304 2 Wheel, 2” 65% Merv- 4024904 Axle 2 4024682 Air Filter, Pleated, 2” x 6” x 20” 4025454 2 E-Ring 57% MERV-8 (optional) 20 4024078 Wire Duct Collar (Exhaust) 4022489 Air Filter, Pleated, 4” x 6” x 20” 2 4025043 Skid Panel 95% Mini-Pleat MERV-4 (optional) 3 4022037
Resumen del contenido incluido en la página 10
This page intentionally left blank. Toll-Free 1-800-533-7533 0 www.thermastor.com • sales@thermastor.com
Resumen del contenido incluido en la página 11
Phoenix 200 MAX Dehumidifier Limited Warranty Warrantor: Therma-Stor LLC PO Box 8680 Madison, WI 53708 Telephone: -800-533-7533 Who Is Covered: This warranty extends only to the original end-user of the Phoenix 200 MAX dehumidifier, and may not be assigned or transferred. First Year Warranty: Therma-Stor LLC warrants that, for one () year the Phoenix 200 MAX dehumidifier will operate free from any defects in materials and workmanship, or Therma-Stor LLC will, at its option, repair or rep