Resumen del contenido incluido en la página 1
Analog-Digital Converter Module User's Manual
Analog-Digital Converter Analog-Digital Converter
Module Module
U
User's Manual User's Manual
MODEL
Q-A/D-U-S-E
MODEL
13JR03
CODE
SH(NA)-080055-C(0106)MEE
Q64AD
HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
Q68ADV
NAGOYA WORKS : 1-14 , YADA-MINAMI 5 , HIGASHI-KU, NAGOYA , JAPAN
Mitsubishi Programmable
Q68ADI
Logic Controller
When exported from Japan, this manual does not require application to the
Min
Resumen del contenido incluido en la página 2
• SAFETY PRECAUTIONS • (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the PLC system, please read the user's manual for the CPU module to use. In this manual, the safety instructions are ranked as "DANGER"
Resumen del contenido incluido en la página 3
[INSTALLATION PRECAUTIONS] ! CAUTION • Use the PLC in an environment that meets the general specifications contained in the user's manual of the CPU module to use. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product. • When installing the module, securely insert the module fixing tabs into the mounting holes of the base unit while pressing the installation lever located at th
Resumen del contenido incluido en la página 4
[STARTING AND MAINTENANCE PRECAUTIONS] ! CAUTION • Do not disassemble or modify the modules. Doing so could cause failure, malfunction injury or fire. • Switch all phases of the external power supply off when mounting or removing the module. Not doing so may cause failure or malfunction of the module. The system that uses the QnPHCPU allows you to change a module online. Note that there are restrictions on the modules that can be changed online and each module has a predetermined changing proc
Resumen del contenido incluido en la página 5
REVISIONS The manual number is given on the bottom left of the back cover. Print Date Manual Number Revision Dec., 1999 SH (NA)-080055-A First printing Oct., 2000 SH (NA)-080055-B Add the contents of the function version B. Correction About the Generic Terms and Abbreviations, Section 2.1, Section 3.1.3, 3.4.1, Section 4.3, 4.4.2, Section 5.2.1, 5.2.2, 5.3.3, 5.6.1 Partial addition Section 1.1, Section 3.1.1, 3.1.2, 3.2, 3.3.1, 3.3.2, Section 4.5, Section 7.2.3, 7.2.4 Addition Section 1.2, Sect
Resumen del contenido incluido en la página 6
Print Date Manual Number Revision Feb., 2003 SH (NA)-080055-F Correction SAFETY PRECAUTIONS, Section 1.2, Section 2.1, Section 3.4.1 to 3.4.3, 3.4.15, Section 4.5, Section 5.1, 5.2.1, 5.2.2, 5.3.2, 5.6.1 to 5.6.3, Section 7.3.1, 7.3.3 to 7.3.6, Appendix 1.1, Appendix 1.2, Appendix 2.2, Appendix 2.3 Addition Section 5.6.4, 5.6.5 May, 2003 SH (NA)-080055-G Correction Section 2.2, Section 3.4.1, 3.4.2, 3.4.3, 3.4.14, 3.4.15, Section 4.5, 4.6, Section 5.3.1 Japanese Manual Version SH-080028-I This m
Resumen del contenido incluido en la página 7
INTRODUCTION Thank you for purchasing the MELSEC-Q series PLC. Before using the equipment, please read this manual carefully to develop full familiarity with the functions and performance of the Q series PLC you have purchased, so as to ensure correct use. Please forward a copy of this manual to the end user. CONTENTS SAFETY PRECAUTIONS..............................................................................................................................A- 1 REVISIONS.....................
Resumen del contenido incluido en la página 8
3.4.12 Maximum and minimum values storage area (buffer memory addresses 30 to 45: Un\G30 to Un\G45) ............................................................ 3-24 3.4.13 Mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159).................... 3-25 3.4.14 Pass data classification setting (buffer memory addresses 200: Un\G200) (Q64AD only)......... 3-25 3.4.15 Industrial shipment settings and user range settings offset/gain values (buffer memory addresses 202 to 233:
Resumen del contenido incluido en la página 9
7.3.1 When industrial shipment setting is used and initial setting was made with GX Configurator-AD ........................................................................................................................................................ 7 - 3 7.3.2 When industrial shipment setting is used and initial setting was made with sequence program. 7 - 8 7.3.3 When user range setting is used and initial setting was made with GX Configurator-AD (other system is available).............
Resumen del contenido incluido en la página 10
Conformation to the EMC Directive and Low Voltage Instruction For details on making Mitsubishi PLC conform to the EMC directive and low voltage instruction when installing it in your product, please see Chapter 3, "EMC Directive and Low Voltage Instruction" of the User's Manual (Hardware) of the PLC CPU to use. The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction. By making this product conform to the EMC directive
Resumen del contenido incluido en la página 11
Product Structure The product structure of this product is given in the table below. Model code Product name Quantity Q64AD Q64AD Model Analog-Digital Converter Module 1 Q68ADV Q68ADV Model Analog -Digital Converter Module 1 Q68ADI Q68ADI Model Analog -Digital Converter Module 1 SW0D5C-QADU-E GX Configurator-AD Version 1 (1-license product) (CD-ROM) 1 SW0D5C-QADU-EA GX Configurator-AD Version 1 (Multiple-license product) (CD-ROM) 1 A - 10
Resumen del contenido incluido en la página 12
1 OVERVIEW MELSEC-Q 1 OVERVIEW 1 This User's Manual describes the specifications, handling and programming methods for the Q64AD analog-digital converter module (hereinafter referred to as the Q64AD), Q68ADV analog-digital converter module (hereinafter referred to as the Q68ADV), and Q68ADI analog-digital converter module (hereinafter referred to as the Q68ADI), which are used in conjunction with MELSEC-Q Series CPUs. In this manual, the Q64AD, Q68ADV, and Q68ADI are collectively referred to
Resumen del contenido incluido en la página 13
1 OVERVIEW MELSEC-Q 1.2 Functions Added to Function Version B and Later 1 (1) Functions added to function version B The functions added by the function version B A/D converter module are listed below. Item Function overview Reference section Multiple PLC system Compatible with a multiple PLC system. A PLC CPU of function version Section 2.1 compatibility B or later are required. The resolution mode can be changed according to the application, and Resolution mode digital-value resolution setti
Resumen del contenido incluido en la página 14
2 SYSTEM CONFIGURATION MELSEC-Q 2 SYSTEM CONFIGURATION 2.1 Applicable Systems This section describes the system configuration for the A/D converter module. 2 (1) Applicable module and the number of modules that can be installed The following are the CPU module and network module (for remote I/O stations) in which the A/D converter module can be installed and the number of modules that can be installed. Number of modules that Applicable module Remarks can be installed Q00JCPU Maximum 16 1 (
Resumen del contenido incluido en la página 15
2 SYSTEM CONFIGURATION MELSEC-Q (4) Compatibility with online module change To make an online module change, use the module of function version C or later. POINT The products of function version C include the functions of the products of function versions A and B. 2 (5) Software packages supported Correspondence between systems which use A/D converter modules and software packages are as shown below. The GX Developer is necessary when using a A/D converter module. Software Version 4 GX Config
Resumen del contenido incluido en la página 16
2 SYSTEM CONFIGURATION MELSEC-Q 2.2 How to Check the Function Version and Software Version This section describes how to check the function version of the A/D converter module and the GX Configurator-AD software version. (1) How to check the function version of the A/D converter module (a) To check the version using the "SERIAL column of the rating plate" located on the side of the module Function version 80M1 IND. CONT. EQ. (b) To check the version using the GX Developer Se
Resumen del contenido incluido en la página 17
2 SYSTEM CONFIGURATION MELSEC-Q REMARK The version indication for the GX Configurator-AD has been changed as shown below from the SW0D5C-QADU-E 50F upgrade product. Previous product Upgrade and subsequent versions SW0D5C-QADU-E 50F GX Configurator-AD Version 1.10L 2 - 4 2 - 4
Resumen del contenido incluido en la página 18
3 SPECIFICATIONS MELSEC-Q 3 SPECIFICATIONS 3.1 Performance Specifications 3.1.1 Performance specifications list Table 3.1 shows the performance specifications of the A/D converter modules. Table 3.1 Performance specifications Model name Q64AD Q68ADV Q68ADI Item 3 Analog input points 4 points (4 channels) 8 points (8 channels) 8 points (8 channels) Voltage –10 to 10 V DC (Input resistance value 1M ) ——— Analog 0 to 20 mA DC 0 to 20 mA DC input Current ——— (input resistance value 250 ) (input re
Resumen del contenido incluido en la página 19
3 SPECIFICATIONS MELSEC-Q Model name Q64AD Q68ADV Q68ADI Item 80 s/channel (When there is temperature drift, the time calculated by adding 160 s will be used Conversion speed regardless of the number of channels used) Absolute maximum input Voltage : ± 15 V Current : ± 30 mA 2 E PROM write count Max. 100 thousand times Between the I/O terminal and PLC power supply : Photocoupler insulation Insulation method Between channels : Non-insulated Dielectric withstand voltage
Resumen del contenido incluido en la página 20
3 SPECIFICATIONS MELSEC-Q (1) Voltage input characteristic (a) Voltage input characteristic in normal resolution mode Figure 3.1 shows a graph of the voltage input characteristic in normal resolution mode. Analog input practical range 4095 4000 3) 4) 2000 2) 1) 0 1 –96 –2000 –4000 –4096 –15 –10 –5 0 5 10 15 Analog input voltage (V) Analog input Maximum 2 Digital output value Number Offset value Gain value range setting resolution 1) 1 to 5 V 1 V 5 V 1.0 mV 0 to 4000 2) 0 to 5 V 0 V 5 V 1.