Resumen del contenido incluido en la página 1
Rack-Mount Fail-Safe
Transfer Switch
Installation and Operations Manual
• C-8HFx
© 2006-2007 Server Technology, Inc. All rights reserved.
• C-16HFx
Resumen del contenido incluido en la página 2
Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. Dangerous Voltage This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons. Protective Grounding Terminal This symbol indicates a terminal that must be connecte
Resumen del contenido incluido en la página 3
Table of Contents CHAPTER 1: INTRODUCTION 4 Quick Start Guide.............................................................................................................................4 Technical Support ............................................................................................................................4 Equipment Overview........................................................................................................................5 CHAPTER 2: INSTALLATI
Resumen del contenido incluido en la página 4
Chapter 1: Introduction Quick Start Guide The following instructions will help you quickly install and configure your Rack-Mount Fail-Safe Transfer Switch for use on your network. For detailed information on each step, go to the page number listed to the right. 1. Mount the Rack-Mount Fail-Safe Transfer Switch ....................................................................7 2. Optimize the transfer thresholds..........................................................................
Resumen del contenido incluido en la página 5
Equipment Overview 1. The Voltage Selector switch configures the Rack-Mount Fail-Safe Transfer Switch for the installed operational voltage. NOTE: This configures the brownout/over-voltage switching points. 2. The power inlets connect the Rack-Mount Fail-Safe Transfer Switch to the electrical power sources. 3. LEDs display the input feeds power status. 1 2 3 Figure 1. Sentry Rack-Mount Fail-Safe Transfer Switch Views Rack-Mount Fail-safe Transfer Switch Introduction • 5 Installat
Resumen del contenido incluido en la página 6
Chapter 2: Installation Before installing your Rack-Mount Fail-Safe Transfer Switch, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other items required for proper installation. Standard Accessories • Mounting hardware: Two removable flanges with M4 screws. • Outlet retention clips (208-240V models). Additional items for Cx-xxx-C20 models: • Separate power input cords. • Power input retention bracket hardware (may be installed):
Resumen del contenido incluido en la página 7
Installing the Power Input Retention Bracket For units with a total maximum output <30A, it may be necessary to install the power input retention bracket prior to mounting the unit within the rack. To install the power input retention bracket: 1. Remove the two screws attaching the IEC 60320 C19 inlet to the enclosure. 2. Assemble and attach the retention bracket to the enclosure as shown. Figure 2.1 Retention Bracket assembly Mounting 1. Select the appropriate bracket mounting po
Resumen del contenido incluido en la página 8
Chapter 3: Operations Modes of Operation The Sentry Rack-Mount Fail-Safe Transfer Switch is designed to operate in the following modes: • Normal Infeed A provides power to branches A1 & A2 and Infeed B provides power to branches B1 & B2. Each infeed is monitored individually for voltage and current. • Input Failure The equipment powered by the failed input is transferred to the remaining input. The input current LED display of the failed input will be blank and the remaining display wi
Resumen del contenido incluido en la página 9
Chapter 4: Appendices Appendix A: Technical Specifications Domestic Models Model Rated Voltage Input Cordset and Plug (10’) Outlets 1 C-8HF2-C203 208-240V, 50/60Hz IEC 60320 C20 8 IEC 60320/C19 C-8HF2-L303 208-240V, 50/60Hz 2 x NEMA L6-30P, 30A/208V Locking 8 IEC 60320/C19 1 C-16HF1-C20 100-120V, 50/60Hz IEC 60320 C20 16 NEMA 5-20R C-16HF1-L30 100-120V, 50/60Hz 2 x NEMA L5-30P, 30A/120V Locking 16 NEMA 5-20R 1 C-16HF2-C20 208-240V, 50/60Hz IEC 60320 C20 16 IEC 60320/C13 C-16HF2-L30 20
Resumen del contenido incluido en la página 10
Regulatory Compliance Product Safety Units have been safety tested and certified to the following standards: • USA/Canada UL 60950:2003 and CAN/CSA 22.2 No. 60950-1-03 • European Union EN60950-1:2001 This product is also designed for Norwegian IT power system with phase-to phase voltage 230V. USA Notification Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provid
Resumen del contenido incluido en la página 11
Appendix B: Warranty, Product Registration and Support Warranty For Server Technology Warranty information, please see our website. Product Registration Registration is your key to special offers and services reserved for Registered Users. • Excellent Technical Support Services • Special Update and Upgrade Programs • Warranty Protection • Extended Warranty Service • New Product Information Register your products online today! Technical Support Experience Server Technology's FREE SM
Resumen del contenido incluido en la página 12
Server Technology HEADQUARTERS – NORTH AMERICA EMEA APAC Server Technology, Inc. Server Technology Intl Server Technology, Inc. 1040 Sandhill Drive Sienna Court Singapore Reno, NV 89521 The Broadway +65 (0) 6829 7008 Tel United States Maidenhead +65 (0) 6234 4574 Fax +1.775.284.2000 Tel Berkshire salesint@servertech.com +1.775.284.2065 Fax SL6 1NJ sales@servertech.com United Kingdom www.servertech.com +44 (0) 1628 509503 Tel www.servertechblog.com +44 (0) 1628 509100