                        This manual contains important instructions and warnings that should be followed  during the installation, operation and storage of all Tripp Lite SmartOnline UPS  Systems.  UPS Location Warnings  Install your UPS indoors, away from excess moisture or heat, dust or direct  sunlight.  Install your UPS in a structurally sound area. Your UPS is extremely heavy; take  care when moving and lifting the unit.  Only operate your UPS at indoor temperatures between 32" F and 104" F (between  0" C and 40" 
                    
                    Resumen del contenido incluido en la página 3 
                    
                        Familiarize yourself with the location and function of the front and rear panel  features before installing and operating your UPS.  FRONT PANEL  0 0 0 0  UPS SYSTEM  , 5  1. "ON/OFFn Switch: This momentary rocker switch turns the UPS System's inverter  ON and OFF.  2. "SELECT" Button: This button performs two functions: it allows you to browse  through different power readings on the LCD Display by momentarily pressing the  button; it also allows you to silence the UPS alarm by pressing and hol
                    
                    Resumen del contenido incluido en la página 4 
                    
                        SUBP                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                
                    
                    Resumen del contenido incluido en la página 5 
                    
                        REAR PANELS  1. Manual Bypass Switch: This red and yellow dial is used in one step of putting the UPS  in "BYPASS" mode, which must be done before performingany maintenance on the UPS  with the connected load supported. (See page 12 for step-by-step instructions for going  into "BYPASS.") While this switch is on "BYPASS." connected equipment will receive  filtered AC mains power, but will not receive battery power in the event of a blackout.  2. Input Terminal Block: Use these terminals to conne
                    
                    Resumen del contenido incluido en la página 6 
                    
                        INVERTER OPERATION DIP SWITCH  SETTINGS (SUIOKPM SHOWN)  Using a small tool, set the four Inverter Opera-  tion DIP Switches (located on the rear panel of  your UPS, see pg. 4-5 for location) to match  your input voltage, input frequency and  desired operational mode.  InDut Voltage Selection  (D~P switch& # 1 ~r #2)  (Input Voltage Select Terminal Block)  These DIP switches and the Input Terminal  Select Block must BOTH be set to match your  input voltage. Your UPS WILL NOT CONVERT  the voltage
                    
                    Resumen del contenido incluido en la página 7 
                    
                        UPS LOCATION  Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the  stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external  battery packs.  INPUTAND OUTPUT CONNECTION  WIRING SELECTION  Choose appropriate cabling (depending on current carried; see chart below) to connect  your UPS to an AC power supply and your equipment to your UPS:  OUTPUT  MODEL RATED INPUT RATED OUTPW RATED OUE'UT  PROTECnON  CURRENT CURRENT CURRENT  CIRCurr  2
                    
                    Resumen del contenido incluido en la página 8 
                    
                        EXTERNAL BATTERY PACK CONNECTION  (SUGK: Optional; SU1OK: Required)  Since SUGK models contain internal batteries, connecting external battery packs (to  extend runtime) is optional. SUlOKPM models, however. do not have internal batteries  and require an external battery pack connection to a SUlOKBP or a SUBP. Using the  supplied battery connection cable, insert one end into the External Battery Connector  on the rear panel of your UPS and the other end into the Battery Output Connector on  the 
                    
                    Resumen del contenido incluido en la página 9 
                    
                        BA77ERY CONDITION VERIFICATION  When the UPS is operating from battery power, the alarm and LCD Display will both alert  you to the UPS battery's charge condition.  Batterv Charge Condition Alarm ED Dis~lav  FULL Short Beep (every 2 seconds) ON BAlTERY  BA'IT = XXV Wo  LOW Short Beep (every 1/2 second) BA'ITERY LOW  BAT = XXV Wo  UNDER Continuous Beep BA'ITERY UNDER  SHUT DOWN  INITIAL BAVERY CHARGING (OPTIONAL)  Your UPS System's battery is fully charged prior to shipping. However, if your UPS 
                    
                    Resumen del contenido incluido en la página 10 
                    
                        SELF-TESTING  When you turn the UPS ON, it will perform a brief (about 25 second) self-test. See figure  below for display sequence.'  'Note: ~startingfiom battery, the BATIERY LED will be Ut and the I/P and BYPASS LED5 wlll MI. TheJInd LCD dlsplay In (he  diagram below appears when the LlPS b operating normally under utfllty-supplled AC Input power.  SELECT  FREQ OUT . XXHz  Sltll~lOlllll~ ,,,,  UPS SYSTEM  A  SELECT  INPUT AC OK  UPS SYSTEM  $!  OFF  UPS SYSTEM UPS SYSTEM  UPS SYSTEM  UPS SYST
                    
                    Resumen del contenido incluido en la página 11 
                    
                        LCD DISPLAY SELECT SWITCH  Momentarily press the "SELECT" switch on the front panel to browse through different  power readings on the LCD Display. The LCD Display will show which one of four  operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass.  Also, as you press the "SELECT" switch, the LCD Display will browse through load. input,  bypass, output and battery conditions.  "ON-BATTERY" MODE OPERATION  "NORMAL" MODE OPERATION  "ECONOMY' MODE OPERATION "ON BYPASS" M
                    
                    Resumen del contenido incluido en la página 12 
                    
                        BATERY CHARGE WA RNlNGS  Since your UPS can provide battery backup only for as long as the batteries remain  charged, these warnings should be acted on immediately.  Battery Charge Warning LCD Display Message  Battery charge nearly depleted BATTERY LOW  AC/DC charger not operating CHARGER FAILURE!  OPERATION UNDER SHUTDOWN  Your UPS will shut down and the LCD will display a message if it detects one of the  following conditions. Note: For all conditions, the "Input," "Output" and "Bypass" LEDs  
                    
                    Resumen del contenido incluido en la página 13 
                    
                        RS-232 INTERFACE  This female DB9 port connects your UPS via an RS-232 cable to a workstation or server  equipped with Tripp Lite software. The port uses RS-232 communications to report UPS  status and power conditions. Using this port, Mpp Lite software can monitor and  manage network power and automatically save open files and shut down equipment  during a blackout. Contact Mpp Lite Customer Support at (773) 869-1233 for informa-  tion on available SNMP, network management and connectivity sof
                    
                    Resumen del contenido incluido en la página 14 
                    
                        DRY CONTACT INTERFACE:  This female DB9 contact-closure port allows your UPS to send contact-closure signals  to indicate that it is on battery back-up mode and if its batteries are running low. The  port can also receive a remote shutdown signal.  Pin assipnment; lmin.U.3mA  LOW BATTERY I -  REMOTE SHUTDOWN SIGNAL  FROM EXTERNAL  b  COY NC If I C 1 I  I  I SIGNALFROM  COMPUTER  .' !  MAXIMUM CAPACITY OF DRY CONTACT:  AC250Vn4  DC30vnA  DRY CONTACT INTERFACE TABLE  UPS Operating Pin 8,3 Pin 1,3 
                    
                    Resumen del contenido incluido en la página 15 
                    
                        Service  Your Smartonline UPS is covered by the 2-year limited warranty period described  below. A variety of service contracts is also available from Tripp Lite. including start-  up service contracts and 3- to 5-year SafeSure on-site service contracts. For more  information, call Tripp Lite Customer Service at (773) 869-1233.  2- Year Limited Warranty  TRlPP LlTE warrants tls products tncludtng batteries to be free from defects In materials and workmanship for a period of two years from the  d
                    
                    Resumen del contenido incluido en la página 16 
                    
                        STATIC MANUAL OUTPUT  INPUT  - SURGE , ACT0 DC - - OUTPUT  * *' DCTOAC - - - -  BYPASS BYPASS  ACINPUT lSoLATIoN  PROTECTOR FILTER FILTER  CONVERTER INVERTER BREAKER  SW~CH  SWITCH XFM  I I  STANDARD  -  BAllERIES:  -LEDS  240 VDC CPU  I  CHARGER LCD  CONTROLLER  dLs -TO RS-232  As400  DRY CONTACT  ACCESSORY SLOT  SUBP EXTERNAL  REP0  POWER  BATTERY CABINET(S):  -  SUPPLY  240 MC  dLt  120 VAC INPUT                                                                                                  
                    
                    Resumen del contenido incluido en la página 17 
                    
                        (Notc: Excludingisolation transformer)  Model SU6K SUlOK  &&  Inputvoltage 156V-280VSlngle Phase 156V-280VSinglePhase  Input Frequency 50/60 Hz t 3 Hz  50/60 Hz 2 3 Hz  (selectable, pg. 7) (selectable. pg. 7)  Input Current 32A 50A  Inrush Current <150A <200A  Power Factor (Full Load) ~0.99 >0.99  Emciency (Full Load/On-Line) >87Oh >88%  Circuit Breaker 40A 63A  OU~DU~  VA 6000 10000  Watts (Power Factor: 0.7) 4200 7000  Waveform (On-Line) Slnewave Slnewave  Waveform (On-Battery) Sinewave Slnewa