U P S
Uninterruptible Power System
Line-Interactive Rack-Mount Network UPS
600VA/ 1000VA/ 1200VA
1500VA/ 2200VA/ 3000VA
USER‘S MANUAL
■ ■ ■ ■ ■ ■ ■ ■
Resumen del contenido incluido en la página 2
TABLE OF CONTENTS INTROD UC TI ON……………………………………………………………………..i 1. IMPORTANT SAFETY INSTRUCTIONS………………………………………...……………..………1 2. P ………………...………….……………………,.………………………..…………2 RESENTATION 3. INSTALLATION………………………………………………………………………...……………6 4. OPERATION………………………………………………………………………...………………9 5. S C I ………………………………..…………………………10 OFTWARE AND OMPUTER NTERFACE 6. BATTERY CABINET…………………………………………………………………………………11 APPENDIX A. TROUBLESHOOTING……………………………………………………………………11 APPENDIX B. SPECIFICATIONS……………
Resumen del contenido incluido en la página 3
1. IMPORTANT SAFETY INSTRUCTIONS ● SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions that should be Followed during Installation and Maintenance of the UPS and Batteries. ● Intend for Installation in a Controlled Environment. ● Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. ● When Replacing Battery, Replace With the Same Number and Typ
Resumen del contenido incluido en la página 4
2. PRESENTATION Front Panel (600VA/ 1000VA), 1U size Front Panel (1200VA/ 1500VA), 2U size Front Panel (2200VA/ 3000VA), 3U size 2
Resumen del contenido incluido en la página 5
Back Panel (600VA/ 1000VA), 1U size Back Panel (1200VA/ 1500VA), 2U SIZE (1500VA/110V NO BYPASS OUTPUT) 3
Resumen del contenido incluido en la página 6
Back Panel (2200VA), 3U SIZE Back Panel (3000VA), 3U SIZE 4
Resumen del contenido incluido en la página 7
2.1 “Power On” Indicator Power On indicator illuminates when utility power’s condition is normal. 2.2 “BACKUP” indicator The indicator illuminates when the power is supplied from the batteries. 2.3 “Battery Fault” Indicator This illuminates indicating weak battery. Recharge the battery for at least four hours. If after recharging this still illuminates, replace the battery by following the instructions in the manual.(You can plug out then check battery) 2.4 Power Switch Can be
Resumen del contenido incluido en la página 8
3. INSTALLATION Inspect the UPS upon receipt. The packaging is recyclable; keep it for reuse or disposed of properly. 3.1 Recharge the battery UPS may be used by anyone immediately upon receipt. The battery is fully charged before shipped from the factory. However, user is recommended to recharge the battery at least eight hours before using UPS. Energy loss may occur during shipping or long duration storage. To recharge the battery, simply let UPS be plugged into an AC outlet and switc
Resumen del contenido incluido en la página 9
3.12 Installation with accessories of “Rack-mount” types: Please install the rack-mount type units according to the following illustration. Installation with bottom Installation with bottom Installation with rear plate. bracket. bracket Part Part Part RMB-05 RMB-06 (1U) RMB-01(1U),-02(2U), 1 SET. RMB-07(2U~4U). -03(3U),-04(4U) 2 PCS. 2 PCS. Step 1 Step 1 Step 1 Step 2 Step 2 Step 2
Resumen del contenido incluido en la página 10
Installation with bottom Installation with bottom Installation with rear plate. bracket. bracket Part Part Part RMB-08(1U),-09(2U) RMB-12 RMB-13,-14 ,-10(3U),-11(4U) 2 PCS. 4 PCS. 2 PCS. Step 1 Step 1 Step 1 Step 2 Step 2 Step 2 Step 3 Step 3 Step 3 Step 4 Step 4 Step 4 8
Resumen del contenido incluido en la página 11
4. OPERATION 4.1 Simple test It is recommended that the user perform a simulation test when using UPS for the first time or when adding an additional piece of equipment. Conduct a simulation-test: first, switch on UPS and wait for the power indicator to light up, then simply unplug UPS to simulate the event of utility failure. 4.2 Check the power requirement of your equipment 4.2.1. Make sure the total power of your equipment does not exceed rating capacity. 4.2.2. Also make sure
Resumen del contenido incluido en la página 12
5. SOFTWARE AND COMPUTER INTERFACE 5.1 Power Monitoring Software The UPSMON series software (or other power monitoring software) is applied standard RS-232 interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, UPSMON displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, Battery level and so on. The software is available for DOS, Windows 3.1x, Windows 95/97/2000/ME/XP, Windows NT or
Resumen del contenido incluido en la página 13
6. BATTERY CABINET 6.1 Battery’s life of UPS The battery’s life of UPS is about 3-6 years under normal usage. 6.2 Battery Replacement Once the UPS’s battery is no longer useful and must be replaced. Please call the service personnel to replace it. APPENDIX A TROUBLESHOOTING UPS has a self-protect feature that prevents the UPS from being damaged as a result of overheating. If the temperature is higher than 55°C, wait for a while and let the UPS become cool. Problems Possi
Resumen del contenido incluido en la página 14
APPENDIX B SPECIFICATIONS MODEL KIN- KIN- KIN- KIN- KIN- KIN- 600 1000 1200 1500 2200 3000 AP/RM AP/RM AP/RM AP/RM AP/RM AP/RM INPUT Capacity (UPS 600 1000 1200 1500 2200 3000 outlets) VA/ VA/ VA/ VA/ VA/ VA/ 360W 600W 720W 900W 1320W 1800W 500VA 500VA 500VA 500VA N/A N/A (Bypass (220 outlets) ~240V only) Voltage +/-25% at line input Frequency 50 or 60 Hz +/-10% (auto sensing) OUTPUT Voltage (on Simulated sine wave at 100V or battery) 110V/115V/120Vor 220V/230V/240V +/- 5% F
Resumen del contenido incluido en la página 15
PHYSICAL Net Weight 9.35 11.5 16.3 16.3 28.4 32.7 Kg (lbs) (20.5) (25.3) (35.9) (35.9) (62.6) (71.9) Shipping Weight 11 13 19.3 19.3 31.1 36.3 Kg (lbs) (24.2) (28.6) (42.5) (42.5) (68.5) (80) Dimension 483*362*44 483*357*84 483*35 483*48 (mm) W*D*H (1U) (2U) 1*130 5.5*130 (3U) (3U) ALARM Battery Back-up Slow beeping sound (about 0.47Hz) Battery Low Rapid beeping sound (about 1.824Hz) Overload Continue beeping sound INTERFACE RS-232C port RS-232C Bi-directional communication port Inter