Resumen del contenido incluido en la página 1
User Manual
English
®
APC Smart-UPS RT – UXI/UXICH
3000/5000/6000 VA 220/230/240 VAC
Tower/Rack-Mount 3U
Uninterruptible Power Supply
990-1392D 12/2005
Resumen del contenido incluido en la página 2
Resumen del contenido incluido en la página 3
Introduction The APC Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discha
Resumen del contenido incluido en la página 4
ATTACH THE BEZEL TO THE UPS 5000/6000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS • Wiring must be performed by a qualified electrician. • Adhere to all national and local electrical codes. • Install a high magnetic 30/32 A utility circuit breaker • Use #10 AWG gauge (5sq. mm) wire. 1. Switch the utility circuit breaker OFF. 2. Remove the input access panel. 3. Remove circular knockout. 4. Run #10 AWG gauge (5sq. mm) wire through the access panel, and connect the wire
Resumen del contenido incluido en la página 5
BASIC CONNECTORS Power management software and interface kits can be used with the UPS. Use only cables approved by APC. serial com Any other interface cable will be incompatible with the UPS connector. Manual bypass enables the user to manually put connected equipment into bypass mode. normal bypass Emergency Power Off terminal allows the user to connect the UPS to the central EPO system. EPO terminal The UPS features a transient voltage surge-suppression (TVSS) sc
Resumen del contenido incluido en la página 6
CONNECT THE EXTERNAL BATTERIES Battery Safety Read and adhere to the following warnings when installing or servicing the external batteries. Failure to observe these warnings may result in serious injury, death or damage to the equipment. WARNINGS • Do not attempt to install or service external batteries alone. A qualified electrician should perform the installation and servicing of external batteries. • Disconnect charging source(s) BEFORE connecting or disconnecting battery term
Resumen del contenido incluido en la página 7
THIRD PARTY BATTERY SOLUTION Batteries must be Sealed Lead-Acid type. Use 50 A, 250 VDC fuses with an Interrupt rating of ≥ 20,000 A. Ensure that the external batteries are wired prior to connecting the batteries to the UPS. If using a non-APC battery pack, a 192 V battery string should be wired to the UPS using the enclosed battery cable assembly. Connect the Ground and Wire the Battery System 1. Connect the ground wire (included), to the battery enclosure ground and the TVSS screw o
Resumen del contenido incluido en la página 8
CONNECT EQUIPMENT AND POWER TO THE UPS 1. Connect equipment to the UPS. 2. 3000 VA models: Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. 3. Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on. 4. Switch the utility circuit breaker on. 5. To power up the UPS press the button on the fro
Resumen del contenido incluido en la página 9
OPERATION SMART-UPS RT FRONT DISPLAY Load Battery Charge Indicator Description The Online LED illuminates when the UPS is drawing utility power and performing Online double conversion to supply power to connected equipment. The UPS is supplying battery power to the connected equipment. On Battery The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility Bypass power is sent directly to connected equipment during bypass mode operation. Bypass mode op
Resumen del contenido incluido en la página 10
Feature Function This is not a normal condition. Cold Start When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment. The UPS will emit two beeps. During the second beep, release the button. Self-Test Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery. Manual: Press and hold
Resumen del contenido incluido en la página 11
USER CONFIGURABLE ITEMS NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE. FACTORY USER SELECTABLE FUNCTION DESCRIPTION DEFAULT CHOICES Automatic Self-Test Every 14 days Every 7 days(168 hours), Set the interval at which the (336 hours) 14 days (336 hours) UPS will execute a self-test. On Startup Only, No Self-Test UPS ID UPS_IDEN Up to eight characters to Uniquely identify the UPS, (i.e. define the U
Resumen del contenido incluido en la página 12
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE. FACTORY USER SELECTABLE FUNCTION DESCRIPTION DEFAULT CHOICES High Bypass Point +10% of +5%, +10%, +15%, Maximum voltage that the UPS output voltage +20% will pass to connected setting equipment during internal bypass operation. Low Bypass Point -30% of output -15%, -20%, -25%, -30% Minimum voltage that the UPS voltage setting will pass to connected equ
Resumen del contenido incluido en la página 13
CONNECT THE EPO (EMERGENCY POWER OFF) OPTION The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to national and local electrical codes when wiring the EPO. Wiring must be performed by a qualified electrician. EPO switch The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers. The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC standard). Both Class 2
Resumen del contenido incluido en la página 14
TERMINAL MODE TO CONFIGURE UPS PARAMETERS 3000/5000 VA models: Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable from the computer to the serial com connector on the back of the UPS. 1. EXIT the PowerChute Business Edition using the following steps: • From the Desktop, go to Start => Settings => Control Panel => Administrative Tools => Services. • Select APC PCBE Server and APC PCBE Agent – right click the mouse and select
Resumen del contenido incluido en la página 15
MAINTENANCE AND SERVICE INFORMATION Battery Replacement See your dealer or contact APC at the Web site, www.apc.com for information on replacement battery modules. Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. • Note the model number of th
Resumen del contenido incluido en la página 16
TROUBLESHOOTING Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com, for assistance with complex UPS problems. PROBLEM AND POSSIBLE SOLUTION CAUSE UPS WILL NOT TURN ON Battery not connected properly. Check that the battery connectors are fully engaged. button not pushed. Press the button once to power the UPS and the connected equipment. UPS not connected to utility Check that the power cable from the UPS to the utility po
Resumen del contenido incluido en la página 17
PROBLEM AND POSSIBLE SOLUTION CAUSE BYPASS LED ILLUMINATES The bypass switch has been If bypass is the chosen mode of operation, ignore the illuminated LED. turned on manually or through If bypass is not the chosen mode of operation move the bypass switch on the an accessory. back of the UPS, to the normal position. FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE The UPS has ceased sending The connected equipment exceeds the specified “maximum load” as defined in
Resumen del contenido incluido en la página 18
REGULATORY AND WARRANTY INFORMATION Regulatory Agency Approvals and Radio Frequency Warnings 220, 230, 240 V MODELS This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installe
Resumen del contenido incluido en la página 19
Declaration of Conformity 17
Resumen del contenido incluido en la página 20
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. • www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. • www.apc.com/support/ Global support searching APC Knowledge Base and using e-suppo