Resumen del contenido incluido en la página 1
FPS SERIES 1000W In 1U
Front End Power Supplies
INSTRUCTION MANUAL
This Manual Cover Models:
FPS1000-12 FPS1000-24
FPS1000-32 FPS1000-48
FPS-S1U 19” Rack Single Output
FPS-T1U 19” Rack Triple Output
DWG NO: IA599-04-02-A
Resumen del contenido incluido en la página 2
FPS1000 SERIES INSTRUCTION MANUAL DWG NO: IA599-04-02 A
Resumen del contenido incluido en la página 3
TABLE OF CONTENTS Warranty .................................................................................................................................Pg. 1 FPS1000, FPS-S1U and FPS-T1U rack Safety instructions ................................................. Pg. 2 FPS1000 Power Supply Chapter 1: FPS1000 Series Specifications ............................................................................ Pg. 4 Chapter 2: FPS1000 Series Outline drawings ........................................
Resumen del contenido incluido en la página 4
FPS1000 Instruction Manual WARRANTY This Densei-Lambda product is warranted against defects in materials and workmanship for a period of two years from date of shipment. During the warranty period , Densei-Lambda will, at it's option, either repair or replace products which prove to be defective. LIMITATION OF WARRANTY The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by the buyer, buyer supplied products or interfacing. The warranty shall not ap
Resumen del contenido incluido en la página 5
FPS1000 POWER SUPPLY AND FPS-S1U RACK SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS Operating personnel must not remove the FPS1000, FPS-S1U and the FPS-T1U cover. No internal adjustment or component replacement is allowed by non Densei-Lambda qualified service personnel. Never replace components with power cable connected. To avoid injuries,always disconnect power, discharge circuits and remove external voltage sources before touching components. These products are not authorized for use as
Resumen del contenido incluido en la página 6
FPS1000 Instruction Manual ATTENTION: Risque de choc et de danger e'lectriques. Le de'branchement d'une seule alimenttation stabilise'e ne de'branche uniquement qu'un module "Alimentation Stabilise'e". Pour isoler completement le module en cause, il faut de'brancher toutes les alimentations stabilise'es. SAFETY SYMBOLS CAUTION Risk of Electrical Shock. Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual.
Resumen del contenido incluido en la página 7
CHAPTER 1 FPS1000 SERIES SPECIFICATIONS FPS1000 SERIES SPECIFICATIONS FPS1000-12 FPS1000-24 FPS1000-32 FPS1000-48 1V Rated output voltage 12 24 32 48 2V Output voltage set point 12+/-1% 24+/-1% 32+/-1% 48+/-1% 3V Output voltage range 10.5~13.2 21.5~29 28.8~38.4 43~58 4A Maximum Output Current (Refer to Fig.1) 72 40 31 21 5W Maximum output power 864 960 992 1008 6 (*1) --- 85~265Vac continuous, 47~63Hz, Single phase Input voltage / frequency range 7 Maximum input current (at 100/200Vac) A 12.0/
Resumen del contenido incluido en la página 8
FPS1000 Instruction Manual CHAPTER 2 OUTLINE DRAWINGS 1.2 FPS 1000 SERIES OUTLINE DRAWINGS 5
Resumen del contenido incluido en la página 9
2.2 FPS 1000/P SERIES OUTLINE DRAWINGS 6
Resumen del contenido incluido en la página 10
FPS1000 Instruction Manual CHAPTER 3 FPS1000 POWER SUPPLY INSTALLATION 3.1 GENERAL This chapter contains instructions for initial inspection, preparation for use and repackaging forshipment. NOTE FPS1000 power supplies series generate magnetic field which might affect the operation of other instruments. If your equipment is susceptible to magnetic fields, do not position it adjacent to the FPS1000 unit. 3.2 PREPARATION FOR USE In order to be operational the power supply must be connected
Resumen del contenido incluido en la página 11
3.7 CONNECTING THE LOAD WARNING Turn off the AC input power before making or changing any rear panel connection. Ensure that all connections are securely tightened before applying power. There is a potential shock hazard when using a power supply with a rated output greater than 40V. 3.7.1 Load Wiring. The following considerations should be made to select wiring for connecting the load to the power supply: * Current carrying capacity of the wire (refer to 3.7.2). *Insulation rating of the wire
Resumen del contenido incluido en la página 12
FPS1000 Instruction Manual 3.7.3 Noise and Impedance Effects To minimize the noise pickup or radiation, the load wires and remote sense wires should be twisted-pairs of the shortest possible length. Shielding of the sense leads may be necessary in high noise environments. Even if noise is not a concern, the load and remote sense wires should be twisted-pairs to reduce coupling between them, which might impact the stability of power supply. The sense leads should be separated from the power lea
Resumen del contenido incluido en la página 13
3.7.7 Input/Output connector information The FPS1000 series uses male connector PCIB24W9M400A1, Positronic connector. To mate FPS1000 series to the load circuitry, use female connector PCIB24W9F400A1-S1031, Positronic connector. Refer to Table 3-4 and to the Outline drawing in chapter 2 for the connector pinout description. Pin No Function Description 1,2,4 +V Positive output voltage. Maximum current capacity: 24A/contact. 3,5,6 -V Negative output voltage. Maximum current capacity: 24A/contac
Resumen del contenido incluido en la página 14
FPS1000 Instruction Manual CHAPTER 4 FUNCTIONS AND FEATURES 4.1 Input Voltage Range Input voltage is single phase 85~265Vac (47~63Hz). The power supply can be operated also with a DC input voltage, 120~330VDC but the safety approvals apply to the AC voltage only. Input voltage which is out of the specifications might cause damage to the unit. 4.2 Output voltage trimming The output voltage can be adjusted within the specifications via the V_Trim pin at the In/Out connector. Refer to Fig 4-1 typ
Resumen del contenido incluido en la página 15
4.8 DC_OK signal An open collector output provides a low output voltage detection signal. The open collector output is on when the output voltage is higher than 80%+/-5% of the rated output voltage of the power supply. The open collector output is referenced to the Signals_Return potential and is isolated from the power supply +V and -V terminals The maximum sink current is 10mA and the maximum external voltage is 15V. Refer to Fig 4-3 for typical application. 16 12V aux FPS1000 10KΩ 9 DC_OK 1
Resumen del contenido incluido en la página 16
FPS1000 Instruction Manual 4.11 Remote Sensing The Remote sensing compensates voltage drop on the load wiring. The maximum voltage drop on each wire is 1V, however, it is recommended to minimize the voltage drop on the load wires to improve the response to load current changes. In case that the sensing wires are long, use separate twisted pair wires for the sensing and for the load wires to minimize noise pick-up. It is recommended to connect electrolytic capacitors in the following locations: 1
Resumen del contenido incluido en la página 17
CHAPTER 5 BASIC CONNECTIONS FOR OPERATION 5.1 Connecting single load, Local sensing Local sensing is suitable for applications where load regulation is not critical. Fig 5-1 shows recommended load and sensing connections for applications with a single load. 1,2,4 + +V FPS1000 +S 8 LOAD 13 -S SIGNAL ON/ RTN OFF -V - 3,5,6 10 7 Fig 5-1: single load connection, local sensing In Local sense applications, the +/- sense have to be connected to the * +/-V terminals of the FPS1000 units prior the op
Resumen del contenido incluido en la página 18
FPS1000 Instruction Manual 5.4 Multiple loads connection with distribution terminals If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by a pair of twisted or shielded wires. Each load should be separately connected to the remote distribution terminals (see Fig 5-4). If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most critical load. +V 1,2,4
Resumen del contenido incluido en la página 19
CHAPTER 6 PARALLEL AND SERIES OPERATION 6.1 Parallel operation Up to 8 FPS1000 units of the same output voltage rating can be connected in parallel. By connecting the CS signal between the paralleled units, automatic current balance is achieved, with +/-10% accuracy. Derate the total output current by 10% when using parallel operation to prevent overload condition. The built-in Oring diodes on the main output and the 12V Auxiliary output allow N+1 operation. For input voltages less than 100V
Resumen del contenido incluido en la página 20
FPS1000 Instruction Manual 6.1.3 Signal Return bus at parallel operation The Signal Return of each paralleled unit can be connected together to form a common Signal Return bus. By this way, the control and monitoring signals of the paralleled units can be connected to the same control and monitoring circuitry. The Signal Return bus can be connected to the -V or -S or +V or -S or float. Fig 6-3 shows typical connection of the Signal Return at parallel operation. FPS1000 #1 9, 11, 12 AC_FAIL DC_