Resumen del contenido incluido en la página 1
www.mgeups.com
AmpMeter PDU
Installation and user
manual
R
E
D
I
V
O
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
E
T
N
I
N
U
E
H
T
Resumen del contenido incluido en la página 2
Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. Dangerous Voltage This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons. Protective Grounding Terminal This symbol indicates a terminal that must be connect
Resumen del contenido incluido en la página 3
Contents GETTING STARTED 4 Quick Start Guide ..........................................................................................................................4 INSTALLATION 5 Standard Accessories ...................................................................................................................5 Additional Required Items ............................................................................................................5 Equipment Overview ...........
Resumen del contenido incluido en la página 4
1. Getting Started Quick Start Guide The following instructions will help you quickly install and configure your AmpMeter PDU for use on your network. For detailed information on each step, go to the page number listed to the right. For your network security, MGE UPS SYSTEMS strongly recommends the removal of the predefined user account prior to attachment to your network. 1. Mount the AmpMeter PDU.........................................................................................
Resumen del contenido incluido en la página 5
2. Installation Before installation, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other required items. Standard Accessories • Mounting hardware - two removable flanges with four M4 screws and two mounting L-brackets with nut plates and four sets of screws and washers. For remote monitoring units only: • RJ45 to RJ45 crossover cable • RJ45 to DB9F serial port adapter (for connection to standard DB9M DTE serial port) Additiona
Resumen del contenido incluido en la página 6
2. Installation Safety Precautions This section contains important safety and regulatory information that should be reviewed before installation and use. For input and output current ratings, see Power Ratings in Technical Specifications. Only for installation and use in a Seulement pour l’installation et Nur zur Installation und Verwendung in Restricted Access Location in l’utilisation dans une Zone Interdite einem Sicherheitsbereich gemäß den accordance with the following conformémen
Resumen del contenido incluido en la página 7
2. Installation Mounting Figure 3. Mounting Horizontal/Rack Vertical/Tower 1. Select the appropriate bracket mounting points 1. Attach the removable flanges to the mount for proper mounting depth within the rack. points on the rear of the enclosure using M4 2. Attach the brackets to these mounting points screws. with two screws for each bracket. 2. Attach the mounting L-brackets to the flanges 3. Install the enclosure into your rack, using the with the supplied screws, washers and nu
Resumen del contenido incluido en la página 8
2. Installation Connecting Devices To avoid the possibility of noise due to arcing: 1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet. 2. Connect devices to the outlets. On 230V units, install a retention clip for each outlet; Pull the prongs out slightly and insert them into holes on the sides, then insert the device’s power cord and snap the clip over the cord. NOTE: 1. MGE UPS SYSTEMS recommends even distribution of attached devices
Resumen del contenido incluido en la página 9
3. Operations INTERFACES 10 Usernames and Passwords 10 HTML INTERFACE 11 Logging In 11 Environmental Monitoring 12 Input Load ...........................................................................................................................12 Sensors ...............................................................................................................................12 Configuration 12 System...........................................................................
Resumen del contenido incluido en la página 10
3. Operations This chapter contains information on commands and abilities available only in models equipped for remote monitoring. Interfaces The AmpMeter PDU has two interfaces: the HTML interface accessed via the HTTP enabled Ethernet connections and the command line for serial and Telnet connections. Usernames and Passwords The AmpMeter PDU has one predefined administrative user account (username/password: admn/admn) and supports a maximum of 128 defined user accounts NOTE: For se
Resumen del contenido incluido en la página 11
3. Operations HTML Interface The HTML interface is constructed of three major components: the System Location bar, the User/Navigation bar and the Control Screen. The System Location bar displays the AmpMeter PDU’s location and IP address as well as the current Control Screen title. The User/Navigation bar displays the current user and privilege level and provides access to all HTML pages. And the Control Screen is used to display current data and allow changes to outlet states or sy
Resumen del contenido incluido en la página 12
3. Operations Environmental Monitoring The Environmental Monitoring section offers access to the Input Load page. This section is available to administrative level users and users with Environmental Monitoring view rights. Input Load The Input Load page displays the AmpMeter PDU (s) absolute and descriptive name and the cumulative input load in amperes of all devices attached to the AmpMeter PDU at the time the page was loaded. This page will refresh automatically every 10 seconds.
Resumen del contenido incluido en la página 13
3. Operations Network The Network configuration page is used for maintenance of the network interface. From this page an administrator may configure the IP address, subnet mask and gateway address as well as view the link status, speed and duplex value. The AmpMeter PDU is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or HTML: • IP address: 192.168.1.254 • Subnet Mask: 255.255.255.0 • Gateway: 192.168.1.1 The init
Resumen del contenido incluido en la página 14
3. Operations Setting the HTTP authentication method: The AmpMeter PDU HTTP server supports two authentication methods for security and validation of the username-password – Basic and MD5 digest. The Basic method utilizes Base64 encoding to encode and deliver the username-password over the network to the HTTP server for decoding and authentication. This basic method is supported by all web browsers and offers a minimum level of security. NOTE: The Base64 algorithm is widely-known and
Resumen del contenido incluido en la página 15
3. Operations Removing a user: Click on the Remove link in the Action column for the user to be removed and press Yes on the subsequent confirmation window. Changing a user password: Click on the Edit link in the Action column for the associated user. On the subsequent User Edit page, enter a password and verify the new password for the new user in the Password and Verify Password fields. For security, password characters are not displayed. Press Apply. Changing a user’s access priv
Resumen del contenido incluido en la página 16
3. Operations Testing the FTP upload configuration: This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware file and verify that the firmware file is valid for this unit. Press Test. SNTP The SNTP configuration page is used for setup and maintenance of SNTP support. Setting the SNTP Server Address: Enter the IP address in the primary and/or secondary address field and press Apply. SNMP The SNMP configuration page is used for
Resumen del contenido incluido en la página 17
3. Operations Tools The Tools section contains access to rebooting the unit, uploading new firmware as well as resetting the unit to factory defaults. This section is available to administrative level users only. Restart Performing a warm boot: Select the Restart from the Action drop-down menu and press Apply. Note: System user/outlet/group configuration or outlet states are NOT changed or reset with this command. Resetting to factory defaults: See To reset to factory defaults from
Resumen del contenido incluido en la página 18
3. Operations Command Line Interface Logging In Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit. Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 BPS) - 8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR). To log in by RS-232 o
Resumen del contenido incluido en la página 19
3. Operations Administrative Command Summary (continued) Set FTP Filename Specifies the file to be uploaded via FTP Set FTP Filepath Specifies the filepath for the file to be uploaded Set FTP Host Sets the FTP Host IP address Set FTP Password Sets the password for the FTP Host Set FTP Username Sets the username for the FTP Host Set Gateway Sets the Gateway Set Infeed Name Specifies a descriptive field for the infeed Set Ipaddress Sets the IP address Set Location Specifies a descrip
Resumen del contenido incluido en la página 20
3. Operations Operations Commands Operations commands provide information about the AmpMeter PDU environment and control session operations. Displaying accessible serial ports The List Ports command displays accessible serial ports for the current user. To display accessible serial ports: At the AmpMeter PDU: prompt, type list ports and press Enter. Example The follow command displays all accessible serial ports for the current user: AmpMeter PDU: list ports Port Por