Single Duct Air Terminal Zone Controller
VAV Fan Terminal Zone Controller
Secondary Terminal Zone Controller
Installation, Start-Up and
Configuration Instructions
Part Numbers 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM
CONTENTS Service Configuration Selection Screen. . . . . . . . . 37
AIRFLOW SERVICE CONFIGURATION SCREEN
Page
TERMINAL SERVICE CONFIGURATION SCREEN
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
OPTIONS SERVICE CONFIGURATION SCREEN
GENERAL . . . . . . . . . . .
Resumen del contenido incluido en la página 2
the SPT sensor. The Network Service Tool can be used to ad- GENERAL just set points, set operating parameters, and fully configure the The zone controller is a single duct, fan powered, Variable zone controller or any device on the system. Air Volume (VAV) terminal control with a factory-integrated controller and actuator. The zone controller maintains precise Zone Controller Hardware — The zone controller temperature control in the space by operating the terminal fan consists of the following h
Resumen del contenido incluido en la página 3
CCN SYSTEM CCN PRIMARY BUS (BUS 0) MONITORING SOFTWARE CC6400 OR CSAM FULLY EQUIPPED COMPATIBLE NON-CCN AIR HANDLER AIR HANDLER BRIDGE (RECOMMENDED) COMFORTID EQUIPPED AIR TERMINAL SECONDARY BUS (1 OF UP TO 128) ADDRESSED SEQUENTIALLY DATA COLLECTION OPTION LEGEND CCN — Carrier Comfort Network CSAM — Comfort System AirManager Fig. 1 — Typical Carrier Linkage System 3
Resumen del contenido incluido en la página 4
DAMPER ACTUATOR LOW PRESSURE SHAFT CLAMP TUBING ROUTING ASSEMBLY +24V RH/IAQ C US SPT GND GND FAN AC MECHANICAL SECFLOW FAN SAT STOP +10V 24VAC T56 DMPPOS GROMMET N/A GND HEAT3 1 0 GND PAT TEST ® REMOTE GND HF23BJ042 Made in Switzerland ZONE Controller ® by Belimo Automation 35 in-lb (4 Nm) CW 80...110s + COM + LR 92800 COW 3art Number: 33ZCFANTRM S/N: NEMA 2 Bus#: LISTED 94D5 Element#: TENP IND & ANTI- REG. EQUIP. Unit#: ROTATION Class 2 Supply 24VAC/DC TAB J6 50/60 Hz 3VA 2W + 5K COM 1 6 WIP
Resumen del contenido incluido en la página 5
— +24V RH/IAQ C US SPT GND GND FAN AC SECFLOW FAN SAT +10V 24VAC T56 DMPPOS N/A GND HEAT3 1 GND 0 PAT TEST REMOTE ® GND HF23BJ042 Made in Switzerland ZONE Controller ® by Belimo Automation 35 in-lb (4 Nm) 80...110s CW + COM + LR 92800 Part Number: 33ZCFANTRM COW S/N: NEMA 2 Bus#: LISTED 94D5 Element#: TENP IND & REG. EQUIP. Unit#: Class 2 Supply 24VAC/DC J6 50/60 Hz 3VA 2W + 5K COM 1 6 WIP 1 2 3 yel red wht blu ora blk → Fig. 3 — VAV Fan Terminal Zone Controller +24V RH/IAQ C US SPT GND GN
Resumen del contenido incluido en la página 6
® US C GND D FLOW OUT TPUT +10V OV CW 1 0 COM MMON ® CCW CW HF23BJ042 ZONE Controller J1 Made in Switzerland by Belimo Automation 35 in-lb (4 Nm) 80...110s LR 92800 Part Number: 33ZCSECTRM S/N: NEMA 2 LISTED 94D5 TEMP. IND. & U L REG. EQUIP. Unit#: Class 2 Supply 24VAC/DC 50/60Hz J2 3VA 2W 5K COM 1 6 WIP 1 2 3 yel blu ora blk red wht Fig. 5 — Secondary Terminal Zone Controller ALLOW 12” CLEARANCE FOR SERVICE ACCESS TO CONTROL BOX 3” REF. ZONE CONTROLLER END VIEW INLET Fig. 6 — Service Clearance
Resumen del contenido incluido en la página 7
NOTE: Do not run sensor or communication wiring in the same conduit with line-voltage wiring. NOTE: An accessory conduit box (part no. 33ZCCONBOX) is AIR available for conduit wiring connections to the zone controller. FLOW Perform the following steps to connect the power transformer: 1. Install the field-supplied transformer in an electrical enclosure that conforms to NEC and local codes. 2. Connect 24 vac from the transformer as shown in the CW TO OPEN, CCW TO CLOSE applicable wiring diagram (
Resumen del contenido incluido en la página 8
303 8 +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT +10V Low Y T56 DMPPOS Bl GND GND Or PAT N/A 0 1 REMOTE GND HF23BJ042 Made in Switzerland By Belimo Automation 35 in-lb(4Nm) 80...110s (+) R (GND) W B (-) Not used 24VAC/DC 50/60Hz CCN comunications Hi 3VA 2W comunications CCN com HEAT1 24VAC HEAT2 W B R 24 VAC Line Voltage Yel Blu Ora Blk Red Wht TRAN TRANSFORMER GROUND TERMINAL GROUND LEGEND CCN — Carrier Comfort Network SAT — Supply-Air Temperature Sensor SPT — Space Temperatu
Resumen del contenido incluido en la página 9
9 303 LEGEND Carrier Comfort Network CCN — HWV — Hot Water Valve SAT — Supply-Air Temperature Sensor Space Temperature Sensor SPT — TRAN — Transformer HWV Field Wiring Factory Wiring *Normally open or normally closed valve may be used. +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT Low +10V Y T56 DMPPOS Bl GND GND Or PAT N/A 0 1 REMOTE GND HF23BJ042 Made inSwitzerland By Belimo Automation 35 in-lb(4Nm) 80...110s (+) R (GND) W (-) B Not used 24VAC/DC 50/60Hz CCN comunications Hi 3V
Resumen del contenido incluido en la página 10
303 10 LEGEND CCN — Carrier Comfort Network HWV — Hot Water Valve SAT — Supply-Air Temperature Sensor SPT — Space Temperature Sensor TRAN — Transformer Field Wiring Factory Wiring HWV *Required for some spring return modulating valves. +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT Low +10V Y T56 DMPPOS Bl GND GND Or PAT N/A 0 1 REMOTE GND HF23BJ042 Made in Switzerland By Belimo Automation 35 in-lb(4Nm) 80...110s (+) R (GND) W (-) B Not used 24VAC/DC 50/60Hz CCN comunications Hi 3
Resumen del contenido incluido en la página 11
11 801 LEGEND CCN — Carrier Comfort Network H — Heater Relay HWV — Hot Water Valve SAT — Supply-Air Temperature Sensor H2 H1 SPT — Space Temperature Sensor TRAN — Transformer Field Wiring Factory Wiring +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT Low +10V Y T56 DMPPOS Bl GND GND Or PAT N/A 0 1 REMOTE GND HF23BJ042 Made in 35 in-lb(4Nm) Switzerland 80...110s By Belimo Automation R (+) (GND) W B (–) Not Used 24VAC/DC 50/60Hz CCN Hi 2W 3VA comunications CCN comunications com Line
Resumen del contenido incluido en la página 12
303 12 LEGEND CCN — Carrier Comfort Network H — Heater Relay SAT — Supply-Air Temperature Sensor SPT — Space Temperature Sensor TRAN — Transformer H3 H2 H1 Field Wiring Factory Wiring NOTE: The VAV fan terminal zone controller is used on single duct air terminals with 3 stages of electric heat. +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT +10V Low Y T56 FAN AC DMPPOS Bl GND GND FAN Or PAT N/A 0 1 24 VAC REMOTE GND Not Used HF23BJ042 Made in Switzerland Automation Heat3 By Belimo
Resumen del contenido incluido en la página 13
13 801 LEGEND CCN — Carrier Comfort Network Fan SPT — Space Temperature Sensor Contactor TRAN — Transformer M Field Wiring Factory Wiring Fan Motor Line Voltage +24V RH/IAQ SPT SPT GND GND SECFLOW SAT Low +10V Y T56 FAN DMPPOS AC Bl GND GND FAN Or PAT N/A 0 1 24 VAC REMOTE GND Not HF23BJ042 Used Made in Switzerland Heat3 35 in-lb(4Nm) By BelimoAutomation 80...110s R (+) CW W (GND) COM Second B (–) Damper Not Used CCW 24VAC/DC CCN 50/60Hz Hi comunications 2W 3VA CCN comunication
Resumen del contenido incluido en la página 14
801 14 LEGEND CCN — Carrier Comfort Network HWV — Hot Water Valve Fan Contactor SAT — Supply-Air Temperature Sensor SPT — Space Temperature Sensor M TRAN — Transformer Field Wiring Factory Wiring Fan Motor HWV Line Voltage +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT +10V Low Y T56 FAN AC DMPPOS Bl GND GND FAN Or PAT N/A 0 1 24 VAC REMOTE GND Not Used HF23BJ042 Switzerland Heat3 Made in 35 in-lb(4Nm) By Belimo Automation 80...110s (+) R CW (GND) W COM Second B (-) Damper Not Use
Resumen del contenido incluido en la página 15
24V* OP CL COM 15 801 LEGEND CCN — Carrier Comfort Network HWV — Hot Water Valve PAT — Primary Air Temperature Sensor Fan Contactor SAT — Supply-Air Temperature Sensor M SPT — Space Temperature Sensor TRAN — Transformer Field Wiring Fan Motor Factory Wiring HWV Line Voltage *Required only on Linkage master if on a non-compatible air source. +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT Low +10V Y T56 FAN AC DMPPOS Bl GND FAN GND PAT* Or PAT N/A 0 1 24 VAC REMOTE GND Not HF23BJ042
Resumen del contenido incluido en la página 16
801 16 Fan Contactor M H3 H2 H1 Fan Motor Line Voltage +24V RH/IAQ SPT SPT GND GND SECFLOW SAT SAT Low +10V Y T56 FAN AC DMPPOS Bl GND FAN GND PAT* Or PAT N/A 0 1 24 VAC REMOTE GND Not Used HF23BJ042 Made in Switzerland Heat3 35 in-lb(4Nm) Automation By Belimo 80...110s R (+) CW (GND) W COM Second B (-) Not Used Damper CCW 24VAC/DC CCN 50/60Hz Hi comunications 3VA 2W CCN comunications com Line W B R HEAT1 24VAC HEAT2 24 VAC Voltage Yel Blu Ora Blk Red Wht TRAN TRANSFORMER GROUND
Resumen del contenido incluido en la página 17
17 303 PRIMARY DAMPER — 33ZCFANTRM +24V RH/IAQ SPT SPT GND GND SECFLOW SAT Low +10V Y T56 FAN AC DMPPOS Bl GND FAN GND Or PAT N/A 0 1 24 VAC REMOTE GND Not Used HF23BJ042 Made in Switzerland Heat3 By Belimo Automation 35 in-lb(4Nm) 80...110s Second R (+) Damper CW (GND) W COM B (-) Not Used CCW 24VAC/DC 50/60Hz CCN Hi comunications 3VA 2W CCN comunications com HEAT1 24VAC HEAT2 LINE W B R 24 VAC VOLTAGE Yel Blu Ora Blk Red Wht TRAN TRANSFORMER GROUND SHIELD TERMINAL GROUND LEGE
Resumen del contenido incluido en la página 18
18 SECONDARY DAMPER — 33ZCSECTRM GND SECFLOW Low +10V CW GND 0 1 CCW HF23BJ042 Made in Switzerland Automation 35 in-lb(4Nm) By Belimo 80...110s 24VAC/DC 50/60Hz Hi 3VA 2W com Or W B R Y Bl Yel Blu Ora Blk Red Wht LEGEND CCN — Carrier Comfort Network SPT — Space Temperature Sensor TRAN — Transformer Field Wiring Factory Wiring Fig. 8J — Zone Controller Wiring — Dual Duct Applications (cont)
Resumen del contenido incluido en la página 19
→ 3. Connect the sensor cable as follows: Install Sensors a. Connect one wire from the cable (RED) to the SPACE TEMPERATURE SENSOR INSTALLATION — SPT terminal on the controller. Connect the other A space temperature sensor must be installed for each zone end of the wire to the left terminal on the SEN ter- controller. There are three types of SPT sensors available from minal block of the sensor. Carrier: the 33ZCT55SPT space temperature sensor with timed override button, the 33ZCT56SPT space tem
Resumen del contenido incluido en la página 20
LOW PRESSURE TUBING 0 1 HF23BJ042 Made in Switzerland H L by Belimo Automation 35 in-lb (4 Nm) 80...110s LR 92800 NEMA 2 LISTED 94D5 U TEMP. IND. & L REG. EQUIP. Class 2 Supply 24VAC/DC 50/60Hz 3VA 2W 5K COM WIP 1 2 3 yel blu ora blk red wht HIGH PRESSURE TUBING NOTE: Minimum length of tubing is 2 ft. Fig. 9 — Airflow Pickup Installation Warm Cool NOTE: Dimensions are in inches. Fig. 10 — Space Temperature Sensor Fig. 11 — Space Temperature Sensor and Wall (P/N 33ZCT56SPT Shown) Mounted Humidity