Resumen del contenido incluido en la página 1
CAST IRON STOVE AND DIRECT-VENT
(FREESTANDING FIREPLACE HEATER)
BURNER SYSTEM
TM
OWNER’S OPERATION AND INSTALLATION MANUAL
For more information, visit www.desatech.com
For more information, visit www.desatech.com
SCIVFC/PSCIVFC PFC SERIES
SERIES STOVE STOVE
NATURAL GAS BURNER SYSTEM MODEL (F)SDVBNC
PROPANE/LP GAS BURNER SYSTEM MODEL (F)SDVBPC
REMOTE READY
IMPORTANT: This direct-vent burner system must be installed into approved cast iron stove
bodies, models SCIVFC/PSCIVFC series and PFC series
Resumen del contenido incluido en la página 2
TABLE OF CONTENTS 2 SAFETY INFORMATION TABLE OF CONTENTS OPERATING STOVE WITH BURNER SYSTEM ...................... 26 SAFETY INFORMATION ........................................................... 2 INSPECTING BURNERS.......................................................... 28 PRODUCT IDENTIFICATION ..................................................... 3 CLEANING AND MAINTENANCE ............................................ 29 LOCAL CODES ........................................................
Resumen del contenido incluido en la página 3
T ON O L I I P H SAFETY INFORMATION 3 3 PRODUCT IDENTIFICATION SAFETY INFORMATION PRODUCT IDENTIFICATION Continued 7. Do not modify the burner or stove under any circumstances. Any Cast Iron parts removed for servicing must be replaced prior to operating Stove Body stove or burner system. 8. Turn burner system off and let cool before servicing, installing, or repairing. Only a qualified service person should install, service, or repair the stove or burner system. Have burner system inspected Log
Resumen del contenido incluido en la página 4
LOCAL CODES PRODUCT FEATURES 4 Operation Piezo Ignitor GLOSSARY OF TERMS PRE-INSTALLATION PREPARATION Location and Space Requirements LOCAL CODES PRE-INSTALLATION Install and use stove and burner system with care. Follow all local PREPARATION codes. In the absence to local codes, use the current National Fuel Gas Code ANS Z223.1/NFPA 54* (USA) or the current CSA- WARNING: A qualified service person must in- B149[.1 or .2] Installation Codes (Canada). stall stove and burner system. Follow all lo
Resumen del contenido incluido en la página 5
PRE-INSTALLATION PREPARATION 5 Location and Space Requirements (Cont.) 5 CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY Stove Body Assembly (Cont.) PRE-INSTALLATION PREPARATION Continued 1 3. Proper clearances must be maintained, see Figures 3 and 4. 26 /4" 4. This stove is a freestanding unit designed to set directly on the Front floor. If your stove is to be installed directly on carpeting, vi- nyl tile, or any combustible material other than wood, it must be installed on a metal or wo
Resumen del contenido incluido en la página 6
CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY 6 Stove Body Assembly (Cont.) CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY Continued Pallet Front Wood Bolt 6. Remove all contents from inside stove cavity. Contents include: (1) - Stove bottom (Discard - Not used with this application) (4) - Legs with leg leveler bolts Bottom Of Stove Unit (1) - Bottom door (3) - Top grates Pallet Wood (1) - Hardware kit bag with fasteners 7. Carefully lay stove body on back to attach bottom compo
Resumen del contenido incluido en la página 7
CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY 7 Stove Body Assembly (Cont.) 7 CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY Continued 14. Lay the front panel assembly face down on a protected sur- face. Remove the two screws that hold the front plate onto the front surround plate (see Figure 14). Save these screws. Stove Door 15. Optional: Remove the seven screws and washers that hold the Panel screen onto the front surround plate. Discard these screws, wash- Threaded Hole ers,
Resumen del contenido incluido en la página 8
T O ON L I I H P O CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY 8 Installing Direct-Vent Burner System Into Stove Body Installing Optional Blower Accessory CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY Continued Rear Cover Mounting INSTALLING DIRECT-VENT BURNER Hex Screws Screws SYSTEM INTO STOVE BODY 1. Carefully lift burner system and place into stove body from Stove Body the rear of stove. 2. Place the left and right grate tops into the top of stove body. Dis- Hex Screws ca
Resumen del contenido incluido en la página 9
CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY 9 Installing Optional Blower Accessory (Cont.) 9 Installing Rear Cover CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY Continued 4. Thermostat Blower Only: Attach thermal switch and bracket 12. Check to make sure that the power cord is completely clear of the to inside rear cover wall with two hex head screws provided as blower wheel and that there are no foreign objects in blower wheel. shown in Figure 17, page 8. After securing brac
Resumen del contenido incluido en la página 10
CAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY 10 Installing Rear Cover (Cont.) GENERAL VENTING Location of Vent Termination CAST IRON STOVE AND GENERAL VENTING Your stove with burner system is approved to be vented either DIRECT-VENT BURNER through the side wall, or vertically using the following guidelines: SYSTEM ASSEMBLY • Use only venting components or kits specifically approved for Continued use with this stove and burner system (see Parts Lists for Vent- ing Kits and Components, p
Resumen del contenido incluido en la página 11
V G G V A D E V B L GENERAL VENTING 11 11 GENERAL VENTING Continued N N H C I B Fixed V V Fixed Closed Openable Closed Openable B F V G V J X B B M A V K X TERMINATION CAP G GAS METER RESTRICTED AREA V X AIR SUPPLY INLET (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony I = clearance to service regulator vent outlet [*72 inches (1829mm) [*12 inches (305mm) minimum] minimum] B = clearance to window or door that may be opened J = clearance to non-mechanical air s
Resumen del contenido incluido en la página 12
VENTING INSTALLATION 12 Installation Precautions Installation Planning VENTING INSTALLATION WARNING: Horizontal sections of this vent system WARNING: Read all instructions completely and require a minimum clearance of 2" from the top of the thoroughly before attempting installation. Failure to pipe and 1" minimum to the sides and bottom. Vertical do so could result in serious injury, property damage sections of this system require a minimum of 1" clear- or loss of life. Operation of improperly
Resumen del contenido incluido en la página 13
VENTING INSTALLATION 13 Installation Planning (Cont.) 13 Installation for Horizontal Termination VENTING INSTALLATION Continued Snorkel Installing Vent System in a Chase A chase is a vertical box-like structure built to enclose venting that runs along the outside of a building. A chase is not required for such venting. NOTICE: Treatment of firestops and construction of 12" Minimum the chase may vary from building type to building (305mm) type. These instructions are not substitutes for the requi
Resumen del contenido incluido en la página 14
VENTING INSTALLATION 14 Installation for Horizontal Termination (Cont.) VENTING INSTALLATION Continued 3. Attach vent pipe assembly to the burner system. Set stove in 6. Slide the interior wall firestop over the vent pipe before con- front of it’s permanent location to insure minimum clearances. necting the horizontal run to the vent cap (see Figure 28). Mark the wall for a 10" square hole (for noncombustible ma- 7. Carefully move the stove with vent assembly attached toward 1 terial such as mas
Resumen del contenido incluido en la página 15
VENTING INSTALLATION 15 Installation for Horizontal Termination (Cont.) 15 VENTING INSTALLATION Continued Horizontal Termination Configurations Figures 29 through 31 show different configurations for venting with horizontal termination. Each figure includes a chart with vertical minimum/maximum and horizontal maximum dimensions which must be met. Seal all connections with high temperature silicone sealant (outer pipe only) as specified in the second warning statement on page 12. All horizontal p
Resumen del contenido incluido en la página 16
VENTING INSTALLATION 16 Installation for Vertical Termination VENTING INSTALLATION Continued INSTALLATION FOR VERTICAL Flat Ceiling Installation TERMINATION 1. Cut a 10" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10"x10" (254mm NOTICE: Use rigid pipe only. Flex venting is not to be x 254mm) inside dimensions, as shown in Figure 25 on page used with a vertical termination. 14 using framing lumber the same size as the ceiling joists. If th
Resumen del contenido incluido en la página 17
VENTING INSTALLATION 17 Installation for Vertical Termination (Cont.) 17 VENTING INSTALLATION Continued 7. Twist-lock the vent cap onto the last section of vent pipe and seal outer pipe connection with high temperature silicone seal- ant as specified in the second warning statement on page 12. Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You Non-hardening Mastic may frame and sheetrock the enclosure w
Resumen del contenido incluido en la página 18
VENTING INSTALLATION 18 Installation for Vertical Termination (Cont.) VENTING INSTALLATION Continued Venting with Two 90° Elbows Vertical (V) Horizontal (H ) + 1 Horizontal (H ) 2 5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max. Note: Install restrictor into 4" PA-47 collar of burner system as shown. Note: Install restrictor into 4" collar of burner PA-47 system as shown. Figure 37 - Vertical Venting Configuration Using Two 90° Elbows Venting with Two 90° Elb
Resumen del contenido incluido en la página 19
VENTING INSTALLATION 19 Installation for Vertical Termination (Cont.) 19 High Altitude Installation Parts List for Venting Kits and Components VENTING INSTALLATION Continued Consult your local gas company to help determine the proper orifice for your location. For assistance with any high altitude installation contact DESA International’s Technical Service Department at 1-866-672-6040 PARTS LISTS FOR VENTING KITS AND COMPONENTS Number Description VKG-47-K Ground Floor Vent Kit, Black Includes: H
Resumen del contenido incluido en la página 20
STOVE AND DIRECT-VENT BURNER SYSTEM INSTALLATION 20 Check Gas Type Installing Gas Piping to Stove/Burner System Location STOVE AND DIRECT-VENT BURNER SYSTEM INSTALLATION CAUTION: Use only new, black iron or steel pipe. CHECK GAS TYPE Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of 1/2" Use proper gas type for the burner system unit you are installing. If diameter or greater to allow proper gas volume to you have conflicting gas types, do not i