B10 SERIES BOILER
B3-B9
Boiler Manual And Installation
Instructions for Atmospheric Venting
Please Read Instructions Carefully
Save for Future Reference
WARNING
If the information in this manual is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of
life.
DANGER
WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance
· Do not touch any electric switch; do not use any phone in your
building
· Immediately call your
Resumen del contenido incluido en la página 2
Dear Customer: Thank you for buying a QHT BIASI B10 Series Boiler. The QHT BIASI B10 Series Boiler is a cast iron, oil or gas fired hot water boiler, using the famous BIASI B10 (3-pass) design. The boiler is light, compact, simple, rugged and engineered for maximum home heating efficiency. We realize that it is not possible to answer all questions about the VEGA B10-series boiler system in this manual. Reading this installation manual does not make the reader an expert in all aspe
Resumen del contenido incluido en la página 3
TABLE OF CONTENTS QHT BIASI B10 Series Section Page Important Information & Warnings 4,5,6 General Information 1 7 Boiler Block Assembly & Explosion Diagram 2 8 Boiler Location 3 9 Installation of Boiler Trim Kit Components 4 10,11 Piping the Boiler 5 12 Intake Venting 6 13,14 Exhaust Venting 7 15 Common Exhaust Venting 7.1 15,16 Blocked Flue Switch 7.2 16 Gas Venting 7.3 17 Burner Setup
Resumen del contenido incluido en la página 4
IMPORTANT INFORMATION Please read this page carefully. • ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES AND ORDINANCES, AS WELL AS THE REGULATIONS OF THE SERVING ELECTRICAL, WATER AND GAS UTILITIES. • All systems should be designed by competent contractors, and only persons knowledgeable in the layout and installation of heating systems should attempt the installation of any boiler. It is the responsibility of the i
Resumen del contenido incluido en la página 5
WARNING Any appliance that burns natural gas, propane gas, fuel oil, or coal is capable of producing carbon monoxide (CO). Carbon Monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic. CO is lighter than air and thus may travel throughout the building. BRIEF EXPOSURE TO HIGH CONCENTRATIONS OF CO, OR PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY RESULT IN CARBON MONOXIDE POISONING. EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT
Resumen del contenido incluido en la página 6
Homeowner Information for Gas TO START UP THE APPLIANCE 1. STOP! Read the safety information on the side of the boiler. DO NOT START THE BOILER UNLESS ALL CLEANOUT DOORS ARE SECURED AND SEALED. (Skip to step 9 for oil burning boilers) 2. Set thermostat to lowest setting 3. Turn off all electric power to the appliance 4. Do not attempt to light the burner by hand 5. Turn the manual shut off on the combination gas valve clockwise to the off position. 6. Wait five minutes to clear out
Resumen del contenido incluido en la página 7
1. General Information The BIASI B 10-series boilers are wet base design, sectional, cast-iron boilers for forced hot water heating systems. The boilers are shipped pre-assembled from the factory in lengths from three to nine sections. They are designed for firing with oil or gas power burners, which are packed separately along with the jacket and controls for shipping purposes. When the boiler is received, check the contents to ensure that there is no shortage or damage to any part o
Resumen del contenido incluido en la página 8
2. Boiler Block Assembly All QHT BIASI B10 Series Boilers are shipped from the factory in assembled boiler blocks. If, however, the block needs to be split into sections for ease of delivery, please read the following: To assemble split blocks, move sections into parallel and facing each other. Sections may be slid along boards placed underneath the sections. Inspect nipple ports for damage or burrs. Remove any burrs by scraping the port very lightly. Wipe the push nipples and nipple p
Resumen del contenido incluido en la página 9
3. Boiler Location The following are the minimum clearance to construction or combustible materials: 9” 1. 9” from the top, sides, 24” and rear of the boiler. 9” 2. 18” from the flue pipe in any direction. 3. 24” from the front of the boiler. DANGER The boiler must be located on a non-combustible floor. A smooth, level concrete floor is recommended. Locate the boiler as close as possible to the chimney. If boiler is installed on combustible flooring, consult local authorit
Resumen del contenido incluido en la página 10
4. Installation of Boiler Trim Components Trim Kit Components 1 - Honeywell L4006A or 7248U 1– ¼” X ½” Bushing aquastat 2 – ¾” Plugs 1 – Combo pressure/temp gauge 1 – ¾” 90° Elbow 1 – ¾” X 3” Nipple 1 – Immersion well 1 – 30 PSI pressure relief valve 1- Double acting barometric 1 – ¾” Boiler drain damper with manual reset spill 1 – Cera-fiber Pad for floor of switch (Gas systems only) combustion chamber USE ONLY THE ULC LISTED BOILER COMPONENTS AND UL/CSA LISTED
Resumen del contenido incluido en la página 11
4. Installation of Boiler Trim Components Cont. 1. Install L4006A aquastat in upper left or right rear tapping using 3/4” immersion well. All tapings and joints should be sealed with piping compound. The L4006A o can be adjusted up to 220 F, and should be set to the desired temperature by the installer. The differential is also adjustable between 5 and 30 degrees. It should be set as close to 30 degrees as possible to prevent short cycling of the boiler. If you are installing a 7248
Resumen del contenido incluido en la página 12
5. Piping the Boiler All piping must conform to state and local codes. Page 11 shows the location and size of the boiler tappings. It is recommended to install unions and gate valves at the inlet and outlet of the boiler, so it may be readily isolated for service. For Canadian installations, a low water cut off is required if the boiler is installed above the level of radiation. Even if the boiler is installed below the level of radiation it is strongly recommended that a low water
Resumen del contenido incluido en la página 13
6. Intake Venting 1. Be certain adequate air is available for combustion and ventilation. a.) Boiler located in unconfined space: Installation in large areas, such as basements, can usually be assumed to provide sufficient air. b.) Boiler located in confined space : (See Figure A.) If all air for combustion and ventilation is to come from within the building: Two (2) openings shall be provided with one (1) opening commencing within 12 inches of the ceiling and one (1) o
Resumen del contenido incluido en la página 14
6. Intake Venting Cont. c.) Boiler located in a room under negative pressure: If the boiler is to be installed within a home where the operation of exhaust fans, attic fans, kitchen ventilation systems, clothes dryers or fireplaces may create severe negative vent pressures causing unsatisfactory combustion and venting, special provisions should be made for additional make-up air to supply the other air requirements. If building is of tight construction, combustion air requirements may
Resumen del contenido incluido en la página 15
7. Exhaust Venting The B10 boiler is a high efficiency unit that requires proper venting. The boiler must be vented to the outdoors by means of a tile lined masonry or a approved pre-fabricated chimney of the size and height recommended by the manufacturer or by a listed "power venting" unit which provides draft by mechanical means. In many installations, particularly older interior and most exterior chimneys, a corrosion resistant liner should be installed and may be required by cod
Resumen del contenido incluido en la página 16
7.1 Common Exhaust Venting Cont. 3.Insofar as practical, close all building doors and windows and all doors between the space in which the appliance remaining connected to the common venting system is located and other spaces of the building . Turn on any appliance not connected to the common vent system. Turn on all exhaust fans except for summer exhaust fans. Close the fireplace damper if applicable. 4.Place in operation the appliance being inspected. Follow the lighting instructi
Resumen del contenido incluido en la página 17
7.3 Gas Venting For boilers connected to gas vents or chimneys, vent installations shall be in accordance with part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1 or Section 7, Venting Systems and Air Supply for Appliances, of the CAN/ CGA B149, Installation Codes, or applicable provisions of the local building codes. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under posit
Resumen del contenido incluido en la página 18
8. Burner Setup Good, reliable operation with a minimum of service, starts with attention to the small details: Oil: 1. Setting the nozzle position and electrodes "by the book" using the manufacturer's gauges. 2. Installing a quality micron filter at the burner. 3. Making careful/tight flare connections, without couplings, on oil suction line. 4. Checking fuel pump pressure. 5. Checking draft at the breeching to insure it is adequate to overcome flue gas resistance. (-.02 to –.
Resumen del contenido incluido en la página 19
8.1 Oil Burner Setup This page is only for boilers using an oil burner. If a gas burner is being used, please refer to page 19 for the proper setup of the burner and gas lines. BURNER MANUFACTURER: Beckett NX Boiler Model B-3 B-4 B-5 B-6 Burner Model NEC-1102* NEC-1101* NEC-1101* NEC-1103* Firing Rate 0.55 0.90 1.00 1.20 Insertion Depth 3.50" 6.00" 6.00" 6.00" Nozzle 0.50 X 60 0.65 X 60 0.75 X 60 0.90 X 60 Spray Pattern hollow solid solid W Pump Pressure 180 psi 180 psi 180 psi 180 psi
Resumen del contenido incluido en la página 20
8.2 Gas Burner Setup This page is only for boilers using a gas burner. If an oil burner is being used, please refer to page 18 for the proper setup of the burner. Riello Natural Gas Propane Boiler Model Burner Model Input Man. Pres. Head Air Man. Pres. Head Air (MBH) (W.C.) Setting Gate (W.C.) Setting Gate B-4 R200 110 1.06” 2.2 1 1.32” 2 1 B-5 R200 140 1.20” 2.8 2 1.76” 2.7 2 B-6 R200 175 1.46” 2.8 3 2.34” 2.9 3 B-7 R400 207 1.22” 2 0 1.48” 2 0 B-8 R400 248 1.26” 2.3 1 1