Resumen del contenido incluido en la página 1
WTI Part No. 13762
Rev. H
MPC Series
Managed Power Controllers
Models Covered:
MPC-8H-1 MPC-20VS20-1 MPC-20VS20-2 MPC-20VS16-3 MPC-20V-1
MPC-8H-2 MPC-20VD20-1 MPC-20VD20-2 MPC-20VD16-3 MPC-20V-2
MPC-16H-1 MPC-20VS30-1 MPC-20VS30-2 MPC-20VS32-3 MPC-DISPLAY
MPC-16H-2 MPC-20VD30-1 MPC-20VD30-2 MPC-20VD32-3
MPC-18H-1
MPC-18H-2
Firmware Version 1.6 and Higher
User's Guide
Resumen del contenido incluido en la página 2
Warnings and Cautions: Installation Instructions Secure Racking If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require further evaluation by Certification Agencies. The following items must be considered. 1. The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air flow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 55°C. Consid
Resumen del contenido incluido en la página 3
Warnings and Cautions Disconnect Power If any of the following events are noted, immediately disconnect the unit from the outlet and contact qualified service personnel: 1. If the power cord becomes frayed or damaged. 2. If liquid has been spilled into the device or if the device has been exposed to rain or water. Two Power Supply Cables Note that some MPC series units feature two separate power circuits, and a separate power supply cable for each power circuit. If your MPC unit includes two
Resumen del contenido incluido en la página 4
Agency Approvals FCC Part 15 Regulation This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interfere
Resumen del contenido incluido en la página 5
Table of Contents 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1. MPC-H Series - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.2. MPC-H Series - Back Panel . . . . . . . . . . . . . . . . . . . .
Resumen del contenido incluido en la página 6
Table of Contents 5. Basic Configuration (continued) 5.6. The Plug Group Directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31 5.6.1. Viewing Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32 5.6.2. Adding Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34 5.6.2.1. Granting User Account Access to Plugs on AUX Units . . . . . . . .
Resumen del contenido incluido en la página 7
Table of Contents 7. Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 7.1. The Over Current Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2 7.1.1. Over Current Alarms - Load Shedding and Auto Recovery . . . . . . . . . . . . . . . 7-5 7.1.1.1. Load Shedding & Auto Recovery Configuration - Text Interface . . . . . . . . . . . . . . . . . . . . .
Resumen del contenido incluido en la página 8
Table of Contents 13. Operation via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.1. MPC SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.2. SNMPv3 Authentication and Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.3. Configuration via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resumen del contenido incluido en la página 9
Table of Contents List of Figures 2.1. MPC-H Series - Front Panel (Model MPC-16H Shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.2. MPC-H Series - Back Panel (Model MPC-16H-1 Shown) . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 2.3. MPC-20V Series - Hardware Description (Model MPC-20VD20-1 Shown) . . . . . . . . . . . . 2-5 5.1. The Plug Status Screen (Text Interface; MPC-20V Shown) . . . . . . . . . . . . . . . . . . . . . . . . 5-2 5.2. The Home Screen (Web Browser
Resumen del contenido incluido en la página 10
1. Introduction WTI’s MPC series Managed Power Controllers allow secure, remote metering and management of AC powered rack mount equipment via SSL, SSH, SNMP, web browser, telnet, external modem or local terminal. The MPC can monitor power to your equipment, and automatically notify you when changes in current levels, temperature, circuit breaker status or other factors exceed user-defined threshold values. The MPC features two separate power circuits with up to 20 Amps input feed handling
Resumen del contenido incluido en la página 11
Introduction Convenient, Durable Design: The MPC is available with an optional remote display panel, which can be used to show the status of MPC units installed in hard-to-reach spots, deep inside equipment racks. When additional outlets are needed, each MPC unit can also be connected to up to three Auxiliary/Remote MPC units, allowing control of up to 80 outlets via a single IP Address . Model Numbers The MPC series includes a variety of horizontal and vertical models to accommodate the p
Resumen del contenido incluido en la página 12
Introduction Typographic Conventions ^ (e.g. ^X) Indicates a control character. For example, the text "^X" (Control X) indicates the [Ctrl] key and the [X] key must be pressed simultaneously. COURIER FONT Indicates characters typed on the keyboard. For example, /AC or /ON A2. [Bold Font] Text set in bold face and enclosed in square brackets indicates a specific key. For example, [Enter] or [Esc]. < > Indicates required keyboard entries. For Example: /P . [ ] Indicates optional
Resumen del contenido incluido en la página 13
2. Unit Description 2.1. MPC-H Series - Front Panel 1 2 3 4 5 www.wti.com MPC-16H REMOTE AUX 1 AMPS KWATTS A1 A2 A3 A4 B1 B2 B3 B4 VOLTS TEMP A5 A6 A7 A8 B5 B6 B7 B8 8 . 8 . 8 8 . 8 . 8 Managed Power AUDIBLE DISPLAY DEFAULT ALARM SELECTION Controller PLUGS INPUT A INPUT B PLUGS ON AUX 2 AUX 3 CONSOLE PORT 6 7 8 9 Figure 2.1: MPC-H Series - Front Panel (Model MPC-16H Shown) As shown in Figure 2.1, the MPC-H Series Front Panel includes the following components: 1. Power Circuit A - Indicator L
Resumen del contenido incluido en la página 14
Unit Description 5. Power Circuit B - Indicator Lights: Same as Item 1 above, except the LEDs light to indicate On/Off status of Power Circuit B outlets. (Not present on MPC-18H series units.). 6. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up to three other MPC or BPM units, plus the optional MPC-DISPLAY, status display panel. When your MPC unit is linked to other MPC units, this allows control of up to four MPC units (one local unit, plus three remote u
Resumen del contenido incluido en la página 15
Unit Description 1 3 4 3 BUS BUS A A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A ACT LINK ALARM A B BUS BUS B B 10/100 BaseT B-1 B-2 B-3 B-4 B-5 B-6 B-7 B-8 2 6 5 6 7 8 Figure 2.2: MPC-H Series - Back Panel (Model MPC-16H-1 Shown) 2.2. MPC-H Series - Back Panel As shown in Figure 2.2, the MPC-H Series Back Panel includes the following components: 1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to MPC control functions and the Circuit “A” outlets. Also includes cable keeper
Resumen del contenido incluido en la página 16
Unit Description 5. Power Circuit B - Switched Outlets: Same as Item 4 above. (Not present on MPC-18H series units.) 6. Power Circuit B - Circuit Breaker(s): Same as Item 3 above. (Not present on MPC-18H series units.) 7. Alarm Indicator Lights: Two LEDs which light when an alarm condition is detected at the corresponding power circuit. For information on Alarm Configuration, please refer to Section 7. Note that MPC-18H series units include only one Alarm Indicator Light. 8. Network
Resumen del contenido incluido en la página 17
OFF ON I O 20 OFF ON I O 20 OFF ON I O 20 OFF ON I O 20 Unit Description 1 4 AUX AUX 1 3 DEFAULT REMOTE AUX DISPLAY 2 2 5 AUDIBLE ALARM LINK ON Ethernet 10/100 ACT TOTAL A+B DISPLAY SELECTION KWATTS 3 6 AMPS CONSOLE KWATTS AMPS VOLTS TEMP 8 . 8 . 8 8 . 8 . 8 A B 7 8 Managed Power Controller MPC-20V BRANCH BRANCH A1 B1 PLUG A1 PLUG B1 PLUG A2 PLUG B2 PLUG A3 PLUG B3 PLUG A4 PLUG B4 PLUG A5 PLUG B5 9 10 PLUG A6 PLUG B6 PLUG A7 PLUG B7 PLUG A8 PLUG B8 PLUG A9 PLUG B9 PLUG A10 PLUG B10 B
Resumen del contenido incluido en la página 18
Unit Description 5. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP network. Note that the MPC features a default IP address (192.168.168.168). This allows you to connect to the unit without first assigning an IP address. Note that the Network Port also includes two, small LED indicators for Link and Data Activity. For more information on Network Port configuration, please refer to Section 5.9. 6. Console Port: A DB9, RS232 serial port (DTE), which can be u
Resumen del contenido incluido en la página 19
Unit Description 13. Power Inlet(s): The power inlets are configured differently on MPC models, in accordance with the power rating, maximum load and the number of power circuits. Depending on your specific model, the MPC may include either one or two power inlets or either one or two power supply cables. Other MPC models may include either one or two permanently attached power supply cables. For a description of the power input configuration for your specific MPC unit, please refer to
Resumen del contenido incluido en la página 20
Unit Description 4. Enable/Disable Audible Alarm: a) In the default state, the Audible Alarm is Enabled. b) To disable the Audible Alarm, press and hold the Audible Alarm button for three seconds and then release it. To enable the Audible Alarm, press and hold the Audible Alarm button for three seconds again. c) If the optional MPC-DISPLAY unit is installed, and this operation is performed at the MPC-DISPLAY unit, the audible alarm feature on all connected MPC units will also be disabled.