Resumen del contenido incluido en la página 1
Opal Pro to Mod TCP
Opal Pro MS6 SERIES
AB Ethernet IP Interface Users Manual
Revision 1.00
Page 1
Resumen del contenido incluido en la página 2
Opal Pro to Mod TCP Page 2
Resumen del contenido incluido en la página 3
Opal Pro to Mod TCP FOR YOUR SAFETY Only qualified personnel should install this equipment, after first reading and understanding all the information in this manual. All instructions should be strictly adhered to. The user should consult Brock Solutions or a SAF OPAL Starters supplier for clarification of the contents of this manual should any doubt or questions arise. The installation of this equipment must be conducted in accordance with all national, regional and loc
Resumen del contenido incluido en la página 4
Opal Pro to Mod TCP Page 4
Resumen del contenido incluido en la página 5
Opal Pro to Mod TCP Table of Contents INTRODUCTION ..............................................................................................6 HARDWARE ....................................................................................................6 JUMPER SETTINGS........................................................................................6 LED INDICATORS ...........................................................................................7 OPAL PRO PARAMETE
Resumen del contenido incluido en la página 6
Opal Pro to Mod TCP Opal Pro to Mod TCP Introduction The Opal Pro can be monitored and controlled over an Ethernet communication network using the AB Ethernet IP protocol. The Opal Pro connects to the Ethernet network through and optional Ethernet card that is mounted on the main Opal Pro control card (CA530). Access is gained to the Ethernet card via the communication opening on the right side of the Opal Pro. The Opal Pro is a AB Ethernet IP slave and is mapped as I/O through an Et
Resumen del contenido incluido en la página 7
Opal Pro to Mod TCP LED Indicators Two bi-colour (red/green) LED indicators are mounted beside the network connector. The upper LED indicates the Ethernet interface card status. LED State Ethernet Interface Card Status OFF No power Flashing Red Recoverable configuration fault (card is not configured, contact Brock Solutions for support) Solid Red Hardware Error (contact Brock Solutions for support) Flashing Green No errors client interface is not open ( check software firmware ver
Resumen del contenido incluido en la página 8
Opal Pro to Mod TCP Opal Pro Parameter Settings The parameters in the Opal Pro used to configure the Ehernet interface card (group 14) are only accessible if a Ethernet interface card is installed. The parameter settings are as follows: Opal Pro Setting Description Parameter 2.02 Comm Module Ethernet Type of interface card installed (read only) 10.01 Start/Stop Comm This allows the Opal Pro to be Module started and stopped over the communication link 10.04 Iref Source Comm If this
Resumen del contenido incluido en la página 9
Opal Pro to Mod TCP 15.04 Comm Fault Enable Enable – Opal Pro trips out on a Disable communication fault Disable – Nothing happens on a communication fault 15.05 Comm Fault 0.1 to 5.0 This is the time setting that the Opal Time secs Pro uses to detect a communication fault. Bit 15 of the command word must change state twice with in the time set in this parameter. If parameters in group 14 are modified the changes do not take effect until the control power for the Opal Pro is turn
Resumen del contenido incluido en la página 10
Opal Pro to Mod TCP I/O Configuration The Opal Pro supports 4 input words and 51 output words. Their description is as follows: Input AB Name Description Words Ethernet (Polled) IP Word 1 Output Command Bit 0 – Run Command Word 0 Bit 1 – Jog Command Bit 2 – Reverse Command Bit 3 – Reset Command Bit 4 – DCI/Soft Stop Enable Bit 5 – Reserved Bit 6 – Reserved Bit 7 – Reserved Bit 8 – Reserved Bit 9 – Reserved Bit 10 – Reserved Bit 11 – Reserved Bit 12 – Reserved Bit 13 –
Resumen del contenido incluido en la página 11
Opal Pro to Mod TCP Output AB Ethernet Name Description Words IP (Polled) Word 1 Input Word 0 Status Bit 0 – Ready to Run (drive is enable and has 3 phase power) Bit 1 –Running (start is regulating) Bit 2 – Full On (starter is phased fully on) Bit 3 – Up to Speed (started is phased fully on and the current is below 105% of nameplate current as set in 13.01) Bit 4 – Reverse Bit 5 – Jogging Bit 6 – DC Injecting Bit 7 – Faulted Bit 8 – IOC Fault Bit 9 – MOL Fault Bit 10 – Pha
Resumen del contenido incluido en la página 12
Opal Pro to Mod TCP 1.07 Input Word 9 Relay Status Status of the Relay Outputs Bit 0 – Running Bit 1 – By-Pass Bit 2 – Shorted SCR Bit 3 – Reverse Bit 4 – Faulted 1.08 Input Word Analog Output Analog Output value in Volts X 100 10 2.01 Input Word Stack Size Opal Pro Stack Size in Amps 11 2.02 Input Word Comm 0 – None 12 Module Type 2 – Ethernet 2.03 Input Word Firmware Opal Pro Firmware Version x 100 13 Version 10.01 Input Word Start/Stop 4 = 2 Wire 14 Control 5 = 3 Wire 6
Resumen del contenido incluido en la página 13
Opal Pro to Mod TCP 12.01 Input Word Analog Output 16 = Current Reference 27 17 = Current Feedback 18 = Overload level 19 = Phase Angle 13.01 Input Word Motor Amps Motor nameplate current in Amps 28 13.02 Input Word Motor Volts Motor nameplate volts in Volts 29 13.03 Input Word Service Motor nameplate service factor x 100 30 Factor 14.01-14.06 Input Word Reserved 31- Input Word 36 14.07 Input Word Node Number 1 – 254 37 14.08 Input Word IP Address 1 0 – 255 38 14.09 Input Wo
Resumen del contenido incluido en la página 14
Opal Pro to Mod TCP NOTE: The Opal Pro must have firmware version 1.70 or higher. Page 14