DP3300 Series User's Manual
OMEGA ENGINEERING, INC.,
ONE OMEGA DRIVE, STAMFORD, CT 06907
Inhaltszusammenfassung zur Seite Nr. 2
DP3300 Series User’s Manual SPECIFICATIONS:............................................................................................................................................................................3 DESCRIPTION:..................................................................................................................................................................................4 SAVING PROGRAMMED PARAMETER:...........................................................
Inhaltszusammenfassung zur Seite Nr. 3
DP3300 Series User’s Manual Turning a Channel ON or OFF .....................................................................................................................................................18 MODES OF OPERATION FOR A PULSE INPUT CHANNEL:................................................................................................18 SETUP FOR COUNTER:..............................................................................................................................
Inhaltszusammenfassung zur Seite Nr. 4
DP3300 Series User’s Manual SPECIFICATIONS: (Typical @ 25C and rated supply voltage unless otherwise specified) STANDARD INPUTS • * 4-20ma 10-50ma 0-5Vdc 0-10Vdc • Thermocouple inputs: J,K,T,E,R,S,B • Cold junction compensation error: +/- 1C (10C to 40C) • Open input indication: HELP displayed • Temperature displayable in Degrees C or F • Non standard inputs available --- consult factory. ANALOG TO DIGITAL CONVERSION • 4-1/2 Digit (20,000) Count) A/D Converter • Dual slo
Inhaltszusammenfassung zur Seite Nr. 5
DP3300 Series User’s Manual DESCRIPTION: A highly versatile series, DP3300 offers a unique combination of two analog channels or two pulse input channels or a combination of pulse (square wave) on one channel and an analog signal on the other. This feature allows it to be used as counter, rate, RPM or a frequency monitor along with displaying an analog signal such as 4-20ma loop current, voltage or millivolts or a temperature signal from thermocouples, RTDS etc. For example, flow an
Inhaltszusammenfassung zur Seite Nr. 6
DP3300 Series User’s Manual Table 1. How to Display Parameters TO DISPLAY PERFORM FOLLOWING STEPS 1) Channel 1’s Process value a) Push CH SEL key once. 2) Channel 2's Process a) Push CH SEL key twice. First push selects channel 1 and the Value second push will select and display channel 2's process reading. 3) Channel's high peak a) Select channel whose high peak is desired (push CH SEL key) b) Push HI/LO key once 4) Channel's low peak a) Sele
Inhaltszusammenfassung zur Seite Nr. 7
DP3300 Series User’s Manual RESETTING PEAKS Peaks can be reset to current process value e.g. if channel 1 is reading 200 C, its peaks can be reset to 200. This will allow tracking from the current process reading. To reset high peak, first select the channel whose peak is desired to be reset (by pushing the ‘CH. SEL’ key). Once the channel has been selected, push the ‘HI/LO’ key and keep it pushed. The display will read 'CHx HI' (x=channel #) following which the value of high peak w
Inhaltszusammenfassung zur Seite Nr. 8
DP3300 Series User’s Manual below the limit (minus the relay) deadband. The second mode is manual reset. Once the limits are energized, they will stay energized until manually reset. (NOTE: In the RPM mode, the rate time base must be smaller than the selected filter value. If not, the system will automatically consider the filter value as the time base for rate calculation. Also, a difference of 0.500 is recommended between the filter and time base). FREQUENCY MONITOR: DP3300 moni
Inhaltszusammenfassung zur Seite Nr. 9
DP3300 Series User’s Manual MODES OF OPERATION FOR COUNTER: COUNT UP CONFIGURATION: MODE 0: (Count up with manual reset to zero) In this mode the system counts up from zero. Preset limits energize when the count reaches presets limit values. The unit will continue counting up until manually reset. To reset the count manually, first select a channel by pushing CH SEL key and ,while keeping CH SEL key pushed, simultaneously push the RESET key . The display will read 'RESET' and the
Inhaltszusammenfassung zur Seite Nr. 10
DP3300 Series User’s Manual RESETTING COUNT: The COUNT shown for each channel can be reset to zero or preset for a count down (depending on counter mode) at any time. To reset the count manually, first select a channel by pushing CH SEL key and ,while keeping the CH SEL key pushed, push the RESET key simultaneously. The display will read 'RESET' and then the reset value of zero will be displayed. If the counter is set for count down mode, then the display will preset to the value that w
Inhaltszusammenfassung zur Seite Nr. 11
DP3300 Series User’s Manual the indication of the elapsed time. Maximum time indicated is 999.59.59 hours. To reset the timing and start it all over again, first push the TIME key and while keeping it pushed, press the RESET key. The time will reset and start over from 000.00.00 hours. SETUP: Setup mode provides a means to customize the monitor to suit a particular application. It allows programming such parameters as temperature units, limits, display mode, relay deadband, etc.
Inhaltszusammenfassung zur Seite Nr. 12
DP3300 Series User’s Manual ‘Channel ON/OFF’ Setup After displaying input type, the next step turns a channel ON or OFF. This determines whether a channel is scanned and displayed or not. If for any reason a channel is not being used, it should be turned OFF. This will prevent the unit from spending any time scanning it and also from displaying a 'HELP' message if there is no signal connected to its input. If a channel is OFF, the display will show 'CHx OFF' , and if it is ON the dis
Inhaltszusammenfassung zur Seite Nr. 13
DP3300 Series User’s Manual suppose a flow transducer outputs a 0.130Vdc to 5.000Vdc signal which corresponds to a flow rate of 0 to 40 gal./min. Then to make the 0.130Vdc correspond to a display of 0, set OFFSET =0.130. NOTE: If the input type is CURRENT, the Offset value is entered in milliamps. If the input type is VOLTAGE, the Offset value is entered in millivolts. After pushing SETUP key at the completion of Setup For Low Scale, the display will briefly read 'OFFSEt', and th
Inhaltszusammenfassung zur Seite Nr. 14
DP3300 Series User’s Manual When this parameter is set for "Normally Closed", the relay is closed when readings are below LIMIT, and opens when the channel reading exceeds its LIMIT value. The display will show 'LTx N.O.' (where ‘x’ is the channel number) for a Normally Open setting or 'LTx N.C.' for a 'Normally Closed' setting. Use ^v key to toggle between two settings. Once the desired setting is displayed, push SETUP key to go on to setting up limits 2 and 3 for the channel.
Inhaltszusammenfassung zur Seite Nr. 15
DP3300 Series User’s Manual Display Options On pushing SETUP key while the display is flashing SYS , the display briefly shows 'dSP OPt' (for display option) and then the current Display Option setting. Following display options are selectable. Use ^v key to step thru these options. Once the desired Display Option is shown, push SETUP key to enter the setting and go to set Display Time. Option Display Description SCAN SCAN Scan all channels that are turned on. HIG
Inhaltszusammenfassung zur Seite Nr. 16
DP3300 Series User’s Manual 1. Connect a thermocouple calibration source to the unit. 2. Dial in 1100 degrees centigrade on the calibrator (Note: unit must be programmed for displaying in centigrade). 3. Adjust the gain pot (see diagram of rear view of instrument) on the back of the instrument until the display reads '1100'. 4. Short Channel #1's input with a wire or shorting bar (make sure to disconnect the calibrator so as not to damage it). 5. Push DATA key. The display will read '0002
Inhaltszusammenfassung zur Seite Nr. 17
DP3300 Series User’s Manual FLOW CHART FOR ANALOG INPUT SET UP SYSTEM OR CHANNEL SYSTEM SETUP CHANNEL SETUP Select Channel Voltage or Current Setup Thermocouple / RTD / Thermister Setup Select Display Option 1.Scan Turn Ch On/Off Turn Ch On/Off 2.High point 3.Low point Select Input Type Select Input Type 4.CH 1 – CH 2 5.CH 2 – CH 1 Select Display Units Enter 6.Elapsed Time Degree C/F Decimal Point Enter Display Time Enter High Scale Enter Process Limits (1 thru
Inhaltszusammenfassung zur Seite Nr. 18
DP3300 Series User’s Manual FLOW CHART FOR PULSE INPUT: SET UP Select System or Channel Programming Turn CH On/Off For System Programing Refer to Flow Chart for Analog Input SELECT INPUT TYPE 1. Voltage 2. Current 3. J T/C 4. K T/C 5. T T/C 6. E T/C 7. Pulse Low Freq. High Freq. Rate RPM Counter Scaler Scaler Select Counter Enter Rate Time Select Filter Mode Base Value 0,1,2,3,4,5 Division Factor Division Factor Select Dec.Pt Select Dec.Pt Enter Preset
Inhaltszusammenfassung zur Seite Nr. 19
DP3300 Series User’s Manual SETUP FOR A PULSE CHANNEL: Turning a Channel ON or OFF The very first thing after selecting a channel is to turn it on or off. A channel should be turned off if it is not being used. Use ^v key to select the desired setting. If a channel is OFF, the display will show 'CHx OFF' (where ‘x’ is the channel number) and if it is ON the display is 'CHx ON'. Use ^v key to display the desired ON/OFF setting, and then push SETUP key to go to the next parameter
Inhaltszusammenfassung zur Seite Nr. 20
DP3300 Series User’s Manual FUNCTION DISPLAY SHOWS TO CHANGE active digit flashing. active digit. Division Factor 'dIV FAC' followed by preset Push ^v key to increment or decrement division factor e.g. 12 with active digit. Push key to active digit flashing. change active digit. Limit 1 'CH1 LT1' followed by preset Limit 1 Push ^v key to increment or decrement Limit 2 value e.g. 123.4 with active d