Inhaltszusammenfassung zur Seite Nr. 1
036-21103-003 Rev. A (0403)
DESCRIPTION
The HRA Series condensing unit is the outdoor part of a ver-
satile system of air conditioning. It is designed to be custom
matched with one of UPG’s complete line of evaporator sec-
tions, each designed to serve a specific function. Matching
Air Handlers are available for upflow, downflow or horizontal
applications to provide a complete system. Electric Heaters
are available if required. Add-On coils are available for use
with upflow, downflow or hori
Inhaltszusammenfassung zur Seite Nr. 2
036-21103-003 Rev. A (0403) PHYSICAL AND ELECTRICAL DATA - 1 & 3 Phase MODEL H1RA018S78 H1RA024S78 H1RA030S78 H1RA036S78 H1RA036S50 H1RA048S50 H1RA060S50 Unit Supply Voltage 230 – 1 – 50 380/415 – 3 – 50 1 207 to 253 342 to 455 Normal Voltage Range Minimum Circuit Ampacity 9.8 14.6 20.4 20.8 7.3 10.8 13.3 2 15 25 35 35 15 15 20 Max. Qvercurrent Device Amps Compressor Type Recip Recip Recip Recip Recip Recip Recip Rated Load 7.4 11.3 15.2 15.5 5.2 7.2 9.2 Compressor Amps Locked Rotor 5365908239
Inhaltszusammenfassung zur Seite Nr. 3
036-21103-003 Rev. A (0403) Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 & 3 Phase Additional R-22 Charge / Orifice Size for Various Matched Systems Outdoor Unit (H1RA) 018S78 024S78 030S78 036S78 036S50 048S50 060S50 1 51 57 69 71 71 84 Unit Orifice(s) Factory R-22 Charge, lbs-oz 3 - 13 3 - 14 3 - 14 4 - 11 4 - 11 7 - 10 9 - 12 2 Indoor Coil System Orifice + Additional Charge, Oz Coil Orifice G2FD024S14,17 61 51 + 0 G2FD030S17 65 57 + 069 + 0 G2FD036S17 75 6
Inhaltszusammenfassung zur Seite Nr. 4
036-21103-003 Rev. A (0403) COOLING PERFORMANCE AIR TEMP ON CONDENSER SUCT. T/P @ COMPR. MODEL 75°F 95°F 115°F 125°F TEMP. PSIG MBH KW MBH KW MBH KW MBH KW 35 61.5 13.1 1.36 13.1 1.36 10.6 1.46 9.3 1.52 40 68.5 14.8 1.42 14.8 1.42 12.8 1.55 10.6 1.61 H1RA018S78 45 76.0 16.5 1.48 16.5 1.48 13.7 1.62 12.2 1.69 50 84.0 18.4 1.55 18.4 1.55 15.2 1.71 13.7 1.78 35 61.5 21.3 1.59 17.7 1.93 14.7 2.14 13.3 2.23 40 68.5 24.1 1.68 20.1 2.04 16.7 2.27 15.1 2.38 H1RA024S78 45 76.0 26.7 1.77 22.3 2.16 18.9 2
Inhaltszusammenfassung zur Seite Nr. 5
036-21103-003 Rev. A (0403) ACCESSORIES Refer to Price Manual for specific model numbers. SOUND RATINGS Compressor Blanket - Designed to further reduce the nor- SOUND UNIT MODEL RATINGS mal operating sound. DECIBELS Hard Start Kit (Single Phase Units) - provides required 018 76 starting torque for use with thermal expansion valve. 024 78 Outdoor Thermostat - 2TD06700124 - Consists of an 030 82 adjustable outdoor thermostat and relay in a vented enclo- sure. It provides additional second stage co
Inhaltszusammenfassung zur Seite Nr. 6
036-21103-003 Rev. A (0403) TYPICAL FIELD WIRING - 1 PH APPLICATION (018S78 - 036S78) ALLFIELDWIRINGTOBEINACCORDANCEWITHELECTRICCODE(NEC) AND/ORLOCALCODES POWER WIRING POWER WIRING 24 VOLT CONTROL WIRING CONTROL WIRING 230-1-50 MINIMUM 18 GA. WIRE (NEC CLASS 2) FACTORY WIRING FURNACE OR AIR HANDLER TERMINAL BLOCK * TERMINAL W IS ONLY CY R G W REQUIRED ON SYSTEMS WITH HEAT. CONTACTOR TERMINALS GND. LUG * COIL YR G W ROOM THERMOSTAT CONDENSING UNIT ALLOUTDOORWIRINGMUSTBEWEATHERPROOF. USECOPPERCON
Inhaltszusammenfassung zur Seite Nr. 7
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA018S78A INDOOR COIL MODEL NO. G2FD024S17 IDCFM 500 650 800 CONDENSING ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 18.3 18.1 16.5 18.4 18.2 17.2 18.4 18.3 17.8 75 S.C. 10.6 10.8 10.5 11.0 11.6 11.9 11.4 12.4 13.3 K.W 1.55 1.55 1.53 1.71 1.71 1.69 1.68 1.67 1.66 T.C. 17.8 17.2 15.4 18.0 17.5 16.1 18.2 17.8 16.8 85 S.C. 10.6 10.7 10.2 11.3 11.7 11.6 12.0 1
Inhaltszusammenfassung zur Seite Nr. 8
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA024S78A INDOOR COIL MODEL NO. G2FD030S17 IDCFM 650 850 1050 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 26.4 25.3 24.0 26.6 25.7 24.6 26.7 26.1 25.2 75 S.C. 15.4 15.6 15.4 16.2 16.7 16.8 16.9 17.8 18.2 K.W 2.15 2.11 2.08 2.17 2.13 2.10 2.18 2.15 2.12 T.C. 25.4 23.9 21.8 25.7 24.6 22.8 26.1 25.2 23.7 85 S.C. 15.3 15.1 14.4 16.4 16.6 16.2 17.4 1
Inhaltszusammenfassung zur Seite Nr. 9
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA030S78A INDOOR COIL MODEL NO. G2FD030S17 IDCFM 650 850 1050 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 26.4 25.3 24.0 26.6 25.7 24.6 26.7 26.1 25.2 75 S.C. 15.4 15.6 15.4 16.2 16.7 16.8 16.9 17.8 18.2 K.W 2.39 2.35 2.32 2.53 2.49 2.46 2.56 2.53 2.50 T.C. 25.4 23.9 21.8 25.7 24.6 22.8 26.1 25.2 23.7 85 S.C. 15.3 15.1 14.4 16.4 16.6 16.2 17.4 1
Inhaltszusammenfassung zur Seite Nr. 10
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA036S50A INDOOR COIL MODEL NO. G2FD036S17 IDCFM 1100 1250 1400 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 38.6 36.0 33.4 39.0 36.4 33.9 39.4 36.8 34.3 75 S.C. 26.0 25.7 25.3 25.8 26.4 27.1 25.6 27.2 28.8 K.W 3.20 3.12 3.04 3.30 3.34 3.38 2.99 3.15 3.31 T.C. 36.4 33.7 31.0 36.9 34.2 31.4 37.5 34.7 31.9 85 S.C. 24.8 24.5 24.2 25.2 25.5 25.9 25.5
Inhaltszusammenfassung zur Seite Nr. 11
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA036S78A INDOOR COIL MODEL NO. G2FD036S17 IDCFM 1050 1250 1450 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 38.7 36.8 35.0 39.1 34.7 35.6 39.4 32.5 36.2 75 S.C. 23.4 23.5 23.4 24.4 24.8 24.8 25.4 26.1 26.2 K.W 3.30 3.25 3.21 3.59 3.54 3.50 3.48 3.43 3.39 T.C. 37.4 34.8 31.9 37.7 34.1 32.6 38.1 33.4 33.4 85 S.C. 23.5 24.0 22.2 24.7 25.2 23.9 25.9
Inhaltszusammenfassung zur Seite Nr. 12
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA048S50A INDOOR COIL MODEL NO. G2FD048S21 IDCFM 1400 1450 1500 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 66.1 57.0 47.9 63.5 55.8 48.1 61.0 54.6 48.3 75 S.C. 34.2 34.3 34.3 34.7 35.1 35.6 35.1 36.0 36.8 K.W 4.49 4.83 4.70 4.99 5.09 4.96 4.98 4.84 4.70 T.C. 58.8 51.6 44.5 57.7 51.2 44.7 56.5 50.8 45.0 85 S.C. 33.2 33.1 32.9 33.9 34.0 34.1 34.6
Inhaltszusammenfassung zur Seite Nr. 13
036-21103-003 Rev. A (0403) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. H1RA060S50A INDOOR COIL MODEL NO. G*FD060S24A IDCFM 1650 1900 2150 CONDENSER ENTERING AIR ID DB (°F) 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB (°F) 72 67 57 72 67 57 72 67 57 T.C. 65.0 62.4 59.6 65.8 62.8 60.0 66.6 63.3 60.5 75 S.C. 41.8 41.5 41.0 44.7 44.0 43.6 47.5 46.5 46.1 K.W 5.40 5.36 5.28 5.81 5.76 5.69 5.62 5.56 5.50 T.C. 63.9 60.7 56.5 64.7 61.4 57.5 65.4 62.1 58.5 85 S.C. 41.8 41.1 39.8 44.7 43.7 42.5 47.
Inhaltszusammenfassung zur Seite Nr. 14
036-21103-003 Rev. A (0403) MATCHING INDOOR COMPNENTS ADD-ONCOILS-FORFURNACEAPPLICATION G2FD* MULTI-POSITION (UPFLOW, HORIZONTAL AND DOWNFLOW) AIRHANDLERS F2RP FAN COIL UNITS (UPFLOW, HORIZONTAL) N1AH MODULAR BLOWER G2FD* COIL P6UH FURNACE 14 Unitary Products Group
Inhaltszusammenfassung zur Seite Nr. 15
036-21103-003 Rev. A (0403) NOTES Unitary Products Group 15
Inhaltszusammenfassung zur Seite Nr. 16
Subject to change without notice. Printed in U.S.A. 036-21103-003 Rev. A (0403) Copyright © by York International Corp. 2003. All rights reserved. Supersedes: 036-21103-002 Rev. A (1101) Unitary 5005 Norman Product York OK Group Drive 73069