Inhaltszusammenfassung zur Seite Nr. 1
-
A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-127 Hanning & Kahl
HCS-R
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.00
Document Revision: 9
Inhaltszusammenfassung zur Seite Nr. 2
FS-8700-127 Hanning & Kahl HCS-R Manual Table of Contents TABLE OF CONTENTS 1. HANNING & KAHL HCS-R DESCRIPTION.................................................................... 3 2. DRIVER SCOPE OF SUPPLY ........................................................................................ 4 2.1. Supplied by FieldServer Technologies for this driver.................................................. 4 3. HARDWARE CONNECTIONS........................................................
Inhaltszusammenfassung zur Seite Nr. 3
FS-8700-127 Hanning & Kahl HCS-R Manual Page 3 of 17 1. Hanning & Kahl HCS-R Description The Hanning & Kahl HCS-R driver allows the transfer of data from devices over RS-232 HCS-R protocol. Data is read from HCS-R and current data stored in a specified memory area. The driver can store the data with its loop data status distinct memory areas depending on wheter the data is on loop or from loop. The driver is based on section 10.5 of Hanning & Kahl - part number 40801121. The Fie
Inhaltszusammenfassung zur Seite Nr. 4
FS-8700-127 Hanning & Kahl HCS-R Manual Page 4 of 17 2. Driver Scope of Supply 2.1. Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # FS-8915-10 UTP cable (7 foot) for RS-232 use FS-8700-127 Driver Manual. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Inhaltszusammenfassung zur Seite Nr. 5
FS-8700-127 Hanning & Kahl HCS-R Manual Page 5 of 17 3. Hardware Connections The FieldServer is connected to the Hanning & Kahl HCS-R as shown in connection drawing. Configure the HCS-R according to manufacturer’s instructions HCS-R (Hanning Communication System) RS-232 FS-8917-02 8917-02 WIRE LIST FUNCTION FROM TO Rx RJ45-01 DB9F-03 GND RJ45-04 DB9F-05 Tx RJ45-08 DB9F-02 RTS DB9F-07 CTS DB9F-08 RJ45 CAT 5 Cable (408)-262-2299 FIELDSERVER HANNING KAHL CONNECTION DIAGRAM BASE NAME:
Inhaltszusammenfassung zur Seite Nr. 6
FS-8700-127 Hanning & Kahl HCS-R Manual Page 6 of 17 4. Configuring the FieldServer as a HCS-R Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configu
Inhaltszusammenfassung zur Seite Nr. 7
FS-8700-127 Hanning & Kahl HCS-R Manual Page 7 of 17 4.2. Client Side Connection Descriptions Section Title Connections Column Title Function Legal Values Specify which port the device is 1 Port P1-P8 connected to the FieldServer HCS-R Protocol Specify protocol used HCSR H&K HCS-R Baud* Specify baud rate 9600 (Vendor limitation) Parity* Specify parity None (Vendor limitation) Data_Bits* Specify data bits 8 (Vendor limitation) Stop_Bits* Specify stop bits 1 (Vendor limitation)
Inhaltszusammenfassung zur Seite Nr. 8
FS-8700-127 Hanning & Kahl HCS-R Manual Page 8 of 17 4.4. Client Side Map Descriptors 4.4.1. FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Up to 32 alphanumeric Map_Descriptor_Name Name of this Map Descriptor characters Name of Data Array where data One of the Data Array names Data_Array_Name is to be stored in the from “Data Array” section above FieldServer 0 to maximum specified in Data_Array_Offset Starting location in Data Array “Data Ar
Inhaltszusammenfassung zur Seite Nr. 9
FS-8700-127 Hanning & Kahl HCS-R Manual Page 9 of 17 4.5. Map Descriptor Example: Read Data The CMD_DI Map Descriptor polls HCS-R Node_A (described in Client Side Node Descriptors sections) every 5 seconds. The other Map Descriptors are used to store the data for various loops. Refer to Appendix A for data storage format. Map_Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name Length Scan_Interval CMD_DI_HCSR_01, DA_CURRENT, 0, RDBC, Nod
Inhaltszusammenfassung zur Seite Nr. 10
FS-8700-127 Hanning & Kahl HCS-R Manual Page 10 of 17 4.6. Map Descriptor Example: Read Data and Keep History This Map Descriptor allows the storage of data history up to HCSR_Data_Stages. Data will be shifted to next Stage only if the data is changed. The driver divides the Data Array into sections corresponding to the number of HCSR_Data_Stages. Current data (stage1) will be stored in the first section and oldest (last stage) data will be stored in the last section in the Data array
Inhaltszusammenfassung zur Seite Nr. 11
FS-8700-127 Hanning & Kahl HCS-R Manual Page 11 of 17 5. Configuring the FieldServer as a HCS-R Server For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configu
Inhaltszusammenfassung zur Seite Nr. 12
FS-8700-127 Hanning & Kahl HCS-R Manual Page 12 of 17 5.2. Server Side Node Descriptors Section Title Nodes Column Title Function Legal Values Up to 32 alphanumeric Node_Name Provide name for Node characters Station address of physical server Node_ID 240 Node HCS-R Protocol Specify protocol used HCSR H&K HCS-R Specifies the time that the FieldServer will reserve the Server Server_Hold_Timeout* side connection while waiting for >1.0s, 2.0s the Client side to update data i
Inhaltszusammenfassung zur Seite Nr. 13
FS-8700-127 Hanning & Kahl HCS-R Manual Page 13 of 17 5.3. Server Side Map Descriptors 5.3.1. FieldServer Specific Map Descriptor Parameters Column Title Function Legal Values Up to 32 alphanumeric Map_Descriptor_Name Name of this Map Descriptor characters Name of Data Array where One of the Data Array names Data_Array_Name data is to be stored in the from “Data Array” section FieldServer above 0 to maximum specified in Data_Array_Offset Starting location in Data Array “Data Ar
Inhaltszusammenfassung zur Seite Nr. 14
FS-8700-127 Hanning & Kahl HCS-R Manual Page 14 of 17 5.3.3. Map Descriptor Example. - SMD_HCSR_01 Map Descriptor to Serve HCS-R clients. // Server Side Map Descriptors Map_Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scada_Hold_Timeout SMD_HCSR_01, DA_HCSR, 0, Server, HCSR_01, 22, 5 One of the Data The starting location One of the Nodes Array name The number of items of data to serve described in described i
Inhaltszusammenfassung zur Seite Nr. 15
FS-8700-127 Hanning & Kahl HCS-R Manual Page 15 of 17 Appendix A. Advanced Topics Appendix A.1. 1. How Client Stores Data: The HCS will be polled by an RDBC Map Descriptor and data will be stored in the DA_Current Data Array in the following fashion if parameter HCSR_Data_Stages >1: • New data is stored as current data. nd nd • If data is changed, last current data is moved to 2 Stage, 2 Stage data is moved rd rd to 3 stage and 3 stage data is lost. Appendix A.1.1. Data_Type is An
Inhaltszusammenfassung zur Seite Nr. 16
FS-8700-127 Hanning & Kahl HCS-R Manual Page 16 of 17 The same data will be stored in a Loop based Data Array which will then have the last known data for each loop Data Array Offset Description Current Data 0 - 18 Data bits ( 0 – 1) 19 Receipt ok ( 0 ), Disturbance ( 1 ) 20 From Loop ( 0 ), On Loop ( 1 ) nd 2 (Previous) Data 21 – 39 Data bits ( 0 – 1) 40 Receipt ok ( 0 ), Disturbance ( 1 ) 41 From Loop ( 0 ), On Loop ( 1 ) rd 3 (Prior to previous) Data 42 – 60 Data bit
Inhaltszusammenfassung zur Seite Nr. 17
FS-8700-127 Hanning & Kahl HCS-R Manual Page 17 of 17 THIS PAGE INTENTIONALLY LEFT BLANK FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com