Inhaltszusammenfassung zur Seite Nr. 1
LOW BATT
AC LOSS
AC ON
IPGSM-DPC Commercial Fire Communicator
RADIO TROUBLE
IPGSM-DPC
IPGSM-DPC
Commercial Fire Communicator
Commercial Fire Communicator
I In ns st ta alllla at tiio on n a an nd d S Se et tu up p G Gu uiid de e
800-09370 6/11 Rev. A
Inhaltszusammenfassung zur Seite Nr. 2
Contents General Information .......................................................................................................................1 Package Contents .......................................................................................................................1 Compatible Fire Panels ..............................................................................................................1 Operation..............................................................
Inhaltszusammenfassung zur Seite Nr. 3
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide General Information The IPGSM-DPC Commercial Fire Communicator (henceforth referred to as IPGSM-DPC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition, this communicator utilizes a sophisticated power module (PowerBoost1) that monitors and repo
Inhaltszusammenfassung zur Seite Nr. 4
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Operation The IPGSM-DPC replaces the fire panel's POTS communications path. When an event occurs, the fire panel goes off-hook to dial the central station. The IPGSM-DPC detects the off-hook condition and provides the fire panel with a dial tone. When the fire panel detects the dial tone, it begins dialing the central station. The IPGSM-DPC considers the three second period after dialing as the number dialing has be
Inhaltszusammenfassung zur Seite Nr. 5
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Installation ULC Compliance To meet Canadian ULC compliance, ensure the following: IPGSM-DPC must be installed in accordance with Canadian Electrical Code, Part 1. IPGSM-DPC must be mounted in the same room and within 20 feet of the fire panel. The wiring must be routed through conduit. IPGSM-DPC, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall be listed, must be p
Inhaltszusammenfassung zur Seite Nr. 6
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide STEP 3 – Determine the Signal Strength and Select a Location IMPORTANT - Do Not mount this device outdoors. RF Exposure Warning – The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in con- junction with any other antenna or transmitter. When choosing a suitable mounting location, understand that signal s
Inhaltszusammenfassung zur Seite Nr. 7
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide 4. Connect the LED Display board to its connector, then slide the board into the mounting rails. (Refer to the “LED Display Information” topic if a wire is detached from its connector.) 5. Carefully remove the packaging material that surrounds the PowerBoost1. 6. Mount the PowerBoost1 on the three unused standoffs. Use the plastic screw (prevents shorting) to secure the upper right corner of the PowerBoost1 and the tw
Inhaltszusammenfassung zur Seite Nr. 8
IBS GPRS M1 M0 RSSI Data Out IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide ANTENNA 1451-UL9 WIRED WIRES MUST BE TRANSFORMER RUN IN CONDUIT NUT, TO 24 HR BLU FACILITY POWER BLU WASHER 120VAC, 60Hz, 850mA 18 VAC GND POST 72 VA ANTENNA MOUNTING TO Cabinet Ground Post GND ADAPTER BLU TO PowerBoost1 BLU DO NOT REMOVE these knockouts. CABINET DOOR ON 15 2 3 4 RED GREEN Dialer Capture Module FOR EXTERNAL ANTENNA 50 OHM MMCX ONLY 7720P PROGRAMMER PORT NOT FOR TELEPHONE S
Inhaltszusammenfassung zur Seite Nr. 9
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Wiring the 659EN Line Fault Monitor (if required) The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed on page 1 when the model 659EN Line Fault Monitor is installed. 1. Refer to the installation guide for the 659EN. 2. Mount the 659EN on the lower left side of the IPGSM-DPC cabinet. 3. DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper. 4. Complete the interface
Inhaltszusammenfassung zur Seite Nr. 10
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide STEP 5 – Program the Communications Module You must use the 7720P Programming tool to program the IPGSM-DPC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options. (no display) 1. Connect the
Inhaltszusammenfassung zur Seite Nr. 11
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded. Note: If critical configuration changes were made, such as th
Inhaltszusammenfassung zur Seite Nr. 12
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Dialer Capture Module Information LED Indicator STATUS RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. PowerBoost1 communication problem. GREEN – Blinks twice every sec. Communication Module connection is lost. GREEN – Blinks 10 times every sec. PowerBoost1 and Communications Module connection is
Inhaltszusammenfassung zur Seite Nr. 13
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide PowerBoost1 Module Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low battery. TROUBLE (yellow) One or more trouble conditions exist, such as; overload, output supervision, ground fault, or charger failure. Notes: If AC power is lost and the battery vol
Inhaltszusammenfassung zur Seite Nr. 14
IBS GPRS M1 M0 RSSI IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide iGSM Communications Module Information ON – NOT registered with AlarmNet. GRN OFF – Registered with AlarmNet. FAST BLINK – Download session with Compass in progress. SLOW BLINK – In unison with yellow LED, PRIMARY POWER: 9 - 16.5 VAC CURRENT: 900mA PEAK, 70mA STANDBY 7720P BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP registration in progress. Programmer FCC:
Inhaltszusammenfassung zur Seite Nr. 15
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide RF Specifications Transmission Transmit Receive Receive Number Channel Duplex Frequency Power Frequency of Separation Band Sensitivity Spacing Channels (MHz) (dBm) (MHz) (kHz) (dBm) (MHz) GSM 850 824-849 33 869-894 -107 124 200 45 GSM 900 890-915 33 935-960 -107 124 200 45 GSM 1800 1710-1785 30 1805-1880 -106 374 200 95 GSM 1900 1850-1910 30 1930-1990 -105.5 299 200 80 Central Station Messages Alarm Con
Inhaltszusammenfassung zur Seite Nr. 16
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide IPGSM-DPC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DPC, and Telco 2 is used by the IPGSM-DPC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the iGSM Communications module. Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut. iGSM Comm
Inhaltszusammenfassung zur Seite Nr. 17
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 15 –
Inhaltszusammenfassung zur Seite Nr. 18
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 16 –
Inhaltszusammenfassung zur Seite Nr. 19
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 17 –
Inhaltszusammenfassung zur Seite Nr. 20
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 18 –