Inhaltszusammenfassung zur Seite Nr. 1
Combination FIRE SMOKE DAMPERS
Model FSD-M211
Steel 3V Blades
Application
Model FSD-M211 is a combination fire smoke damper with 3V style UL 555S Leakage Class I
1
blades. The FSD-M211 has been qualified to 10.2 m/s and 1 kPa for
UL555 1 ⁄2 Hour Fire Resistance Rating
operation and dynamic closure in emergency fire smoke situations.
4 Hour Fire Resistance Rating (BS476)
Model FSD-M211 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and lea
Inhaltszusammenfassung zur Seite Nr. 2
Pressure Drop Data FSD-M211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 3 data has been corrected to represent standard air at a density of 1.201 kg/m . Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system. AMCA Tes
Inhaltszusammenfassung zur Seite Nr. 3
5D 6D Figure 5.3 AMCA 5.2 Pressure Drop FSD-M211 5D 4 (W) (H) = D 3.14 Figure 5.2 Figure 5. 5 305mm x 1219mm 1219mm x 305mm 305mm x 305mm 610mm x 610mm 914mm x 914mm Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) 2.5 3 2.5 8 2.5 10 2.5 5 2.6 3 5.1 15 5.1 27 5.1 35 5.2 17 5.1 10 7.6 32 7.7 57 7.7 80 7.8 42 7.6 22 10.3 57 10.3 105 10 135 10.3 72
Inhaltszusammenfassung zur Seite Nr. 4
AMCA 5.3 Pressure Drop FSD-M211 5D 6D Figure 5.3 5D 4 (W) (H) = D 3.14 Figure 5.2 Figure 5. 5 305mm x 305mm 610mm x 610mm 914mm x 914mm 305mm x 1219mm 1219mm x 305mm Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) 2.4 5 2.5 3 2.5 3 2.5 3 2.5 5 5.1 22 5 10 5.1 8 5.1 10 5.1 20 7.8 52 7.7 22 7.6 15 7.7 25 7.6 40 10.3 92 10.3 40 10.1 27 10.3 42 10.1
Inhaltszusammenfassung zur Seite Nr. 5
5D 6D 5D 4 (W) (H) D 3.14 AMCA 5.5 Pressure Drop FSD-M211 VELOCITY VS. PRESSURE DROP 1000 305mm x 305mm 610mm x 610mm 914mm x 914mm 305mm x 1219mm 1219mm x 305mm 100 10 2 5 10 30 FACE VELOCITY- METERS/SECOND AMCA 5.5 305mm x 305mm 610mm x 610mm 914mm x 914mm 305mm x 1219mm 1219mm x 305mm Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure Velocity Pressure (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) (m/s) Drop (Pa) 2.5 13 2.5 8 2.5 8 2.6 8 2.5 1 5 55
Inhaltszusammenfassung zur Seite Nr. 6
Damper Sizing Information The following figures show maximum damper section size. 38mm max Single Section W 95mm 152mm . H Varies 137mm 127mm . 127mm A A * 305mm Sleeve Length Damper Sleeve Dimensional Data The drawings below and corresponding table show the position of the FSD-M211 damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of retaining angles and duct connections. Th