Inhaltszusammenfassung zur Seite Nr. 1
ReSidential and OutdOOR W OOdbuRning FiReplace
OWneR’S OpeRatiOn and inStallatiOn Manual
MOdelS S36, S36H, S36R, S36RH, VS36(1) and VS36H(1)
SAVE THIS BOOK
This book is valuable. In addition to instructing you
on how to install and maintain your appliance, it also
contains information that will enable you to obtain re-
placement parts or accessory items when needed. Keep
it with your other important papers.
This fireplace is approved for use as a wood burning
fireplace or for use with a vent
Inhaltszusammenfassung zur Seite Nr. 2
WARNING: Improper installation, adjustment, altera- tion, service or maintenance can cause injury, property damage or loss of life. Refer to this manual for assis- tance or additional information. Consult a qualified installer or local distributor. t able OF cOntentS Safety Information ............................................... 2 Operation and Maintenance Guidelines ............ 12 Specifications ...................................................... 3 Technical Service...................
Inhaltszusammenfassung zur Seite Nr. 3
SpeciFicatiOnS 1" AIRSPACE ELECTRICAL OUTLET TO COMBUSTIBLE RIGHT SIDE GAS LINE 0" TO MATERIAL KNOCK OUTS TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE 8.125" 2.5" 7.092" 8.717" 11.217" AIR KIT KNOCK OUT LEFT SIDE GAS LINE COMBUSTIBLE KNOCK OUTS WALL BOARD 3/4" AIR SPACE BACK AND SIDES 10.435" 8.125" 2.5" NOT LESS THAN 12" TO PERPENDICULAR SIDEWALL OUTSIDE AIR 8.717" (LEFT SIDE ONLY) 14.437" HEARTH EXTENSION 66" X 20" 12" 0" TO EACH SIDE BOTTOM 29" 22" 14.25" 21 12.5" 32.5" 0.625" 41" ROUND TOP T
Inhaltszusammenfassung zur Seite Nr. 4
FRAMING FiRelp ace inStallati On 1. Frame the opening for the fireplace using the SELECTING LOCATION dimensions shown in Figures 1 and 2. To determine the safest and most efficient location 2. If the fireplace is to be installed directly on for the fireplace, you must take into consideration carpeting, tile (other than ceramic) or any the following guidelines: combustible material other than wood floor- 1. The location must allow for proper clearances ing, the fireplace must be installed u
Inhaltszusammenfassung zur Seite Nr. 5
MANTELS FiRelp ace inStallati On A mantel may be installed if desired (see Figure Continued 4). Woodwork such as wood trims, mantels or DRAIN PAN (DP36) any other combustible material projecting from For outdoor installations, the fireplace enclosure the front face must not be placed within 12" of must allow for adequate drainage and fresh air the fireplace opening. Combustible materials 1 ventilation. It is recommended that a sealed, corro- above 12" and projecting more than 1 / " from t
Inhaltszusammenfassung zur Seite Nr. 6
Venting inStallatiOn LINEAL GAIN PART NO. DESCRIPTION GAIN OPTIONAL OUTSIDE AIR KIT 36" Fireplace 40" (MODEL AK4/AK4F) 12-8DM Pipe Section 10 / " 8 The installation of an outside air kit should be per- 12-8HT formed during the rough framing of the fireplace 18-8DM Pipe Section 16 / " 8 due to the nature of it's location. Outside combus- 18-8HT tion air is accessed through a vented crawl space 24-8DM (AK4F) or through a sidewall (AK4). Pipe Section 23 / " 8 24-8HT 36-8DM Pipe Section 3
Inhaltszusammenfassung zur Seite Nr. 7
Venting inStallatiOn OFFSET RISE CHIMNEY LENGTH A B 48" 36" 24" 18" 12" Continued 3 3 4 /8" 16 /8" ELBOW SET ONLY Continue to assemble chimney sections as outlined, 3 1 9 /4" 2 /2" 1 making sure that both the inner and outer pipe sec- 3 3 12 / " 30 / " 1 4 4 tions are locked together. When installing double 3 1" 34 / " 1 4 wall snap-lock chimney together, it is important 18" 40" 1 1 to assure the joint between the chimney sections 1 1 21 / " 46 / " 1 4 4 is locked. Check by pulling chimney
Inhaltszusammenfassung zur Seite Nr. 8
Existing Venting inStallatiOn Ceiling Continued Frame See Detail A Firestop 2" Min. Spacer Screws or Staples (Min. of 8) Straps Figure 10 - Firestop Spacer with Living Straps Space Above Ceiling Detail B See Detail B Angle Firestop Screws or Staples Firestop (Min. of 8) Spacer Existing Ceiling Straps Straps Frame Detail A Return Elbow Figure 8 - Ceiling Support Pipe 12S-8DM Figure 11 - Firestop Spacer with Attic Space Above Ceiling PENETRATING THE ROOF To maintain a 1" clearance to
Inhaltszusammenfassung zur Seite Nr. 9
Storm Collar Installation (SC1 or SC2) Venting inStallatiOn Place storm collar over pipe and slide down until Continued it is snug against the open edge of the flashing (see Figure 14). Use SC1 for all round terminations and 3 14 /8" Min. SC2 for all terminations with slip sections. Apply 30" Min. (365 mm) 1" Min. (762 mm) waterproof caulk around the perimeter of the collar (25 mm) 1" Min. to provide a proper seal. (25 mm) Chimney Waterproof Pipe Caulk 1" Min. (25 mm) Storm Flashing Colla
Inhaltszusammenfassung zur Seite Nr. 10
10 FOOT RULE Venting inStallatiOn All flue gas outlet chimney terminations must Continued extend a minimum of 3 feet in height above the Terminations with 16" slip pipe sections are avail- highest point where it passes through the roof and able. The RTT-8DM and RTTL-8DM are approved must be at least 2 feet above the highest point of for flashing installations. When needed, these the roof that is within a horizontal distance of 10 adjustable terminations may be used in combina- feet (see F
Inhaltszusammenfassung zur Seite Nr. 11
Venting inStallatiOn Continued EFFECTIVE HEIGHT OF EFFECTIVE HEIGHT OF TERMINATION CAP TERMINATION CAP MINIMUM HEIGHT OF 22 FT. (WITH TWO ELBOW SETS) MAXIMUM HEIGHT OF 50 FT. MAXIMUM EFFECTIVE HEIGHT OF EFFECTIVE HEIGHT OF HEIGHT 50 FT. TERMINATION CAP TERMINATION CAP (ANY SYSTEM) 14.5 FT. 14.5 FT. MINIMUM MINIMUM HEIGHT HEIGHT UP TO 6 FT. MAXIMUM UP TO 6FT. MAXIMUM 30E-8DM 30E-8DM Figure 18 - Typical Residential Installations 4. Repack insulation around gas line and into OptiOnal gaS line sl
Inhaltszusammenfassung zur Seite Nr. 12
OptiOnal a g S line WARNING: To avoid the risk of inStallatiOn damaging the fireplace materials Continued and increasing the risk of spread- ing a fire, do not use the fireplace CAUTION: All gas piping to cook or warm food. and connections must be tested for leaks after the installation WARNING: If the fireplace is completed. After ensuring has been used for wood burning, that the gas valve is on, apply the firebox and chimney must be soap and water solution to all cleaned of soo
Inhaltszusammenfassung zur Seite Nr. 13
OPEN CLOSE If you wish to install an unvented (vent-free) gas OpeRatiOn and log set, only unvented gas log sets which have been Maintenance found to comply with the standard for unvented room heaters, ANSI Z21.11.2 are to be installed guidelineS in this fireplace. Continued A fireplace equipped with glass doors operates OUTSIDE AIR AND DAMPER mush differently than a fireplace with an open HANDLE OPERATION front. A fireplace with glass doors has a limited The damper handle, which opens a
Inhaltszusammenfassung zur Seite Nr. 14
illuStRated p aRtS bReakdOWn WOODBURNING FIREPLACE MODELS S36, S36H, S36R, S36RH, VS36(1) AND VS36H(1) 35 29 2 1 21 5 8 15 17 28 20 30 25 9 18 11 19 37/38 7 12 3 36 34 31 4 24 10 32 6 26 33 22 16 13 27 14 16 23 27 14 www.desatech.com 111026-01C
Inhaltszusammenfassung zur Seite Nr. 15
a p R tS liSt WOODBURNING FIREPLACE MODELS S36, S36H, S36R, S36RH, VS32(1) AND VS32H(1) This list contains replaceable parts used in your fireplace. When ordering parts, see Replacement Parts on page 16 of this manual. KEY KEY NO. PART NO. DESCRIPTION QTY. NO. PART NO. DESCRIPTION QTY. 1 106638-01 Insulation Pan 1 22 10777-01 Access Panel 1 2 ** Fireplace Top 1 23 10784-01 Right Refractory Bracket 1 3 106641-01 Fireplace Surround 1 24 10784-02 Left Refractory Bracket 1 4 106642-01 Air R
Inhaltszusammenfassung zur Seite Nr. 16
ReplaceMent p aRtS STANDARD BRICK LINER HERRINGBONE EMBER PROTECTOR Right Side BRICK LINER Rear Bottom GRATE EP-36 PN 111028-01 Front Bottom Left Side See Parts List on page 17 for part numbers. acceSSORieS DOUBLE WALL PIPE OPTIONAL OUTSIDE AIR KIT ADJUSTABLE HOOD 12-8DM 12-8HT REQUIRED WHEN INSTALLING FOR SIDE WALL INSTALLATION 18-8DM 18-8HT A VENT-FREE GAS LOG 24-8DM 24-8HT IN THIS FIREPLACE HEARTH EXTENSION HE-36 ANTIQUE BRASS FINISH GA6053 POLISHED BRASS FINISH GA6052 36-
Inhaltszusammenfassung zur Seite Nr. 17
nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
Inhaltszusammenfassung zur Seite Nr. 18
nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
Inhaltszusammenfassung zur Seite Nr. 19
nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
Inhaltszusammenfassung zur Seite Nr. 20
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com 111026-01 111026 01 Rev. C NOT A UPC 01/06