Inhaltszusammenfassung zur Seite Nr. 1
AFG
Oil
AFG
Burner
Instruction Manual
Types “F” & “M” air tubes
Motor voltage: 120 Vac / 60 Hz
AFG burner with type “F” air tube
Type “L1” head Type “V1” head
Type “M” air tube combinations
Inhaltszusammenfassung zur Seite Nr. 2
Instruction Manual – Model AFG Oil Burner Contents Prepare before installing Verify specifications ............................................................................................. 3 Be aware of hazard definitions ........................................................................... 3 Check certifications/approvals ........................................................................... 3 Notice special requirements............................................................
Inhaltszusammenfassung zur Seite Nr. 3
Instruction Manual – Model AFG Oil Burner Prepare before installing Verify specifications Be aware of hazard definitions Denotes presence of a hazard which, if ignored, will result in se- vere personal injury, death or substantial property damage. Denotes presence of a hazard which, if ignored, could result in severe personal injury, death or substantial property damage. Denotes presence of a hazard which, if ignored, could result in minor personal injury or property damage. Intended to bring sp
Inhaltszusammenfassung zur Seite Nr. 4
Instruction Manual – Model AFG Oil Burner Prepare burner & site Inspect/prepare installation site Inspect/prepare installation site (continued) Chimney or vent Clearances to burner and appliance Inspect the chimney or vent, making sure it is properly sized and in good Provide space around burner and appliance for easy service and mainte- condition for use. nance. For those installations not requiring a chimney, such as through-the-wall vented Check minimum clearances against those shown
Inhaltszusammenfassung zur Seite Nr. 5
Instruction Manual – Model AFG Oil Burner Prepare burner & site Prepare burner Prepare burner (continued) Low firing rate baffle Install burner nozzle (if not already installed) (continued) The AFG Low Firing Rate Baffle (LFRB), item 7, page 11, reduces the air flow Use care when removing and installing oil nozzles: (cfm). The LFRB is sometimes used for firing rates under 1.00 GPH as listed in Inspect the nozzle adapter before installing nozzle. If it is grooved the table below. Refer to the
Inhaltszusammenfassung zur Seite Nr. 6
Instruction Manual – Model AFG Oil Burner Prepare burner & site Check/adjust "Z" dimension - "F" head Figure 2 —“F” heads (plus burner detail for all head styles) (see Table 3 for dimensions) 1. See Figure 2 above. The important "Z" dimension is the distance from the Table 3 — Dimensions for Figures 2, 3 and 4 face of the nozzle to the flat face of the head (or heat shield, if applicable). This distance for F heads is 1 ¹⁄₈" (1 ³⁄₈" if the air tube has a heat shield). The "Z" dimension is fact
Inhaltszusammenfassung zur Seite Nr. 7
Instruction Manual – Model AFG Oil Burner Prepare burner & site Check/adjust "Z" dimension - "L1" head Check/adjust "Z" dimension - "V1" head Figure 3 —“L1” heads (see Table 3 and Figure 2 for dimensions) Figure 4 —“V1” heads (see Table 3 and Figure 2 for dimensions) 1. See Figure 3. The important "Z" dimension is the distance from the leading 1. See Figure 4. The important "Z" dimension is the distance from the leading edge of the head to the end of the air tube. This distance for L1 head
Inhaltszusammenfassung zur Seite Nr. 8
Instruction Manual – Model AFG Oil Burner Adjust, pipe & wire burner Mount burner on appliance Connect fuel lines (continued) Mounting options Fuel line installation — Bolt the burner to the appliance using the factory-mounted flange or an Continuous lengths of heavy wall copper tubing are recommended. Always adjustable flange. use flare fittings. Never use compression fittings. Always install fittings in accessible locations. Fuel lines should not run against Mounting dimensions the appli
Inhaltszusammenfassung zur Seite Nr. 9
Instruction Manual – Model AFG Oil Burner Adjust, pipe & wire burner Figure 6 — Typical wiring, R8184G or equivalent primary control . Disconnect power before servicing. Figure 7 — Typical wiring, R7184 primary control (R7184P shown) . Disconnect power before servicing. Table 5 — R7184 primary control features 9
Inhaltszusammenfassung zur Seite Nr. 10
Instruction Manual – Model AFG Oil Burner Startup & adjust burner Service & maintain burner Startup burner/set combustion Perform annual maintenance Do not attempt to start the burner when excess fuel or vapor has This equipment must be serviced only by a qualified service agency. accumulated in the appliance. Starting the burner under these conditions could The appropriate test instruments must be used. Failure to do so could result in result in a puffback of hot combustion gases, high smoke le
Inhaltszusammenfassung zur Seite Nr. 11
Instruction Manual – Model AFG Oil Burner Service & maintain burner Replacement parts Awaiting new info 11
Inhaltszusammenfassung zur Seite Nr. 12
Instruction Manual – Model AFG Oil Burner Service & maintain burner Owner’s information Owner service and maintenance Properly installed and maintained, your AFG burner will provide years of effi- This burner must be installed, adjusted and started only by a quali- cient, trouble-free operation. Please take care of your equipment by following the — an individual or agency, licensed and experienced fied service agency warnings provided and by doing the following (notify your qualified service ag