Inhaltszusammenfassung zur Seite Nr. 1
LIK 8MER
Montage- und
Gebrauchsanweisung
Installation and
Operating Instructions
Instructions d’installation
et d’utilisation
Reversible Reversible Pompe à chaleur
Luft/Wasser- Air-to-Water air-eau réversible
Wärmepumpe für Heat Pump for pour installation
Innenaufstellung Indoor Installation intérieure
o
Bestell-Nr. / Order no. / N de commande : 452160.66.23 FD 8611
Français English Deutsch
Inhaltszusammenfassung zur Seite Nr. 2
English Table of contents 1 Please Read Immediately............................................................................................................. E-2 1.1 Important Information:.............................................................................................................................E-2 1.2 Legal Regulations and Directives ...........................................................................................................E-2 1.3 Energy-Efficient Use of the
Inhaltszusammenfassung zur Seite Nr. 3
1.3 1.2 Legal Regulations and 1 Please Read Directives Immediately The construction and design of the heat pump complies with all relevant EU directives, DIN/VDE regulations (see CE declaration 1.1 Important Information: of conformity). When connecting the heat pump to the power supply, the rele- ATTENTION! vant VDE, EN and IEC standards are to be fulfilled. Any further The device is not suitable for operation with a frequency converter. connection requirements stipulated by local utility comp
Inhaltszusammenfassung zur Seite Nr. 4
English 2 2 Purpose of the Heat 3 Scope of Delivery Pump 3.1 Basic Device The compact heat pump is supplied complete with all of the im- 2.1 Application portant components of the heating circulation system: The air-to-water heat pump is designed for use in existing or Expansion vessel newly built heating systems. Heat circulating pump It is designed exclusively for heating and cooling heating water! Overflow valve and safety components (pressure relief In heating operation, the heat pump is s
Inhaltszusammenfassung zur Seite Nr. 5
4 3.2 Switch Box 4 Transport The switch box is located in the heat pump. It can be accessed ATTENTION! by removing the lower front cover. When transporting the heat pump, ensure that it is not tilted more than The switch box contains the supply connection terminals, as well 45° (in any direction). the power contactors, the soft starter unit and the heat pump manager. Use a wooden pallet for transporting the heat pump to the final in- The heat pump manager is a convenient electronic regulation st
Inhaltszusammenfassung zur Seite Nr. 6
English 5 5Set-UP 6 Installation 5.1 General Information 6.1 General Information The heat pump is designed for installation in a corner. Other in- The following connections need to be established on the heat stallation locations are also possible in combination with an air pump: duct (available as an accessory) on the air outlet side. Fresh and exhaust air The unit must be installed indoors on a level, smooth and hori- Flow and return flow of the heating system zontal surface. The entire base
Inhaltszusammenfassung zur Seite Nr. 7
6.4 An overflow valve is installed in the device for systems in which the heating water flow can be shut off via the radiator or thermo- stat valves. This ensures a minimum heating water flow rate through the heat pump and helps to avoid faults. Once the heating system has been installed, it must be filled, de- aerated and pressure-tested. The integrated expansion vessel has a volume of 24 litres. This volume is suitable for buildings with a living space area to be heated of maximum 200 m². The
Inhaltszusammenfassung zur Seite Nr. 8
English 7 7 Start-UP Heat source Max. temperature spread temperature between heating flow and return flow From To 7.1 General Information -20 °C -15 °C 4 K To ensure that start-up is performed correctly, it should only be -14 °C -10 °C 5 K carried out by an after-sales service technician authorised by the -9 °C -5 °C 6 K manufacturer. This may be a condition for extending the guaran- -4 °C 0 °C 7 K tee (see Warranty Service). Start-up should be carried out in 1 °C 5 °C 8 K heating operation. 6
Inhaltszusammenfassung zur Seite Nr. 9
10 8.3 Cleaning the Air System 8 Maintenance / Cleaning Air ducts, evaporator, ventilator and condensate outflow should be cleaned of contamination (leaves, twigs, etc.) before the heat- 8.1 Maintenance ing period. Do this by opening the left and front sides of the heat To protect the paintwork, avoid leaning or putting objects on the pump. The bottom should be opened first followed by the top. device. External heat pump parts can be wiped with a damp cloth and domestic cleaner. ATTENTION! Befor
Inhaltszusammenfassung zur Seite Nr. 10
English 11 11 Device Information LIK 8MER 1 Type and order code 2Design 2.1 Model Compact 2.2 Degree of protection according to EN 60 529 for compact devices IP 20 and heating components 2.3 Installation location Indoors 3 Performance data 3.1 Operating temperature limits: Heating water flow/return flow °C / °C Up to 58 / above 18 Cooling, flow °C +7 to +20 Air (heating) °C -25 to +35 Air (cooling) °C +15 to +40 3.2 Temperature spread of heating water at A7 / W35 10.0 5.0 1 5.8 / 2.7 5.5 / 2.
Inhaltszusammenfassung zur Seite Nr. 11
Anhang / Appendix / Annexes 1 Maßbilder / Dimension Drawings / Schémas cotés................................................................... A-II 1.1 Wärmepumpe / Heat pump / Pompe à chaleur ......................................................................................A-II 1.2 Einbaumaße / Installation Dimensions / Cotes de montage ..................................................................A-III 2 Diagramme / Diagrams / Diagrammes................................................
Inhaltszusammenfassung zur Seite Nr. 12
Anhang · Appendix · Annexes 1 1 Maßbilder / Dimension Drawings / Schémas cotés 1.1 Wärmepumpe / Heat pump / Pompe à chaleur A-II
Inhaltszusammenfassung zur Seite Nr. 13
1.2 1.2 Einbaumaße / Installation Dimensions / Cotes de montage www.dimplex.de A-III Anhang · Appendix · Annexes
Inhaltszusammenfassung zur Seite Nr. 14
Anhang · Appendix · Annexes 2 2 Diagramme / Diagrams / Diagrammes 2.1 Heizbetrieb / Heating Operation / Mode chauffage A-IV
Inhaltszusammenfassung zur Seite Nr. 15
2.2 2.2 Kühlbetrieb / Cooling Operation / Mode refroidissement www.dimplex.de A-V Anhang · Appendix · Annexes
Inhaltszusammenfassung zur Seite Nr. 16
Anhang · Appendix · Annexes 3 3 Stromlaufpläne / Circuit Diagrams / Schémas électriques 3.1 Steuerung Standardregler / Control of the standard controller / Commande régulateur standard A-VI
Inhaltszusammenfassung zur Seite Nr. 17
3.2 3.2 Steuerung Kühlregler / Control of the cooling controller / Commande régulateur standard www.dimplex.de A-VII Anhang · Appendix · Annexes
Inhaltszusammenfassung zur Seite Nr. 18
Anhang · Appendix · Annexes 3.3 3.3 Last / Load / Charge A-VIII
Inhaltszusammenfassung zur Seite Nr. 19
3.4 3.4 Anschlussplan Standardregler / Terminal diagram for the standard controller / Schéma électrique du régulateur standard www.dimplex.de A-IX Anhang · Appendix · Annexes
Inhaltszusammenfassung zur Seite Nr. 20
Anhang · Appendix · Annexes 3.5 3.5 Anschlussplan Kühlregler / Terminal diagram for the cooling controller / Schéma électrique du régulateur refroidissement A-X