AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS
DATA BOOK
Series : PE(H)
Model Service ref.
PE-7MYC PE-7MYC-EU
Cooling only
PE-8MYC PE-8MYC-EU
PE-10MYC PE-10MYC-EU
PE-15MYC PE-15MYC-EU
PE-20MYC PE-20MYC-EU
Heat pump
PEH-5MYA PEH-5MYA-EU
PEH-7MYA PEH-7MYA-EU
PEH-8MYA PEH-8MYA-EU
PEH-10MYA PEH-10MYA-EU
PEH-15MYA PEH-15MYA-EU
PEH-20MYA PEH-20MYA-EU
Inhaltszusammenfassung zur Seite Nr. 2
CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------5 MECHANICAL SPECIFICATIONS ----------------------------------6 TYPICAL INSTALLATION EXAMPLE ------------------------------6 MODEL-DESIGNATION BREAKDOWN ---------------------------7 SPECIFICATIONS ---------
Inhaltszusammenfassung zur Seite Nr. 3
SAFETY FOR USE Before conducting installation work, please read this ''SAFETY FOR USE'' carefully for correct installation. Since the caution items shown here contain important description relative to safety, please observe them without fail. Erroneous handling gives a high possibility to induce serious results such as Warning death or heavy injury. Erroneous Caution handling may induce serious injury depending on the situati
Inhaltszusammenfassung zur Seite Nr. 4
Caution Arrange the configuration of wiring not to bring up Never install on the place where a combustible the panel and terminal cover, and fasten the panel gas might leak. and terminal cover securely. The gas may ignite or explode when the gas leaks and The poor mounting of the panel or terminal cover may collects in surround of the unit. cause the heat generation of the terminal connection, When the unit is installed at telecommunication a fire or electrical shock. centers or hospitals, tak
Inhaltszusammenfassung zur Seite Nr. 5
A COMPLETE LINE UP PEH-5 PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20 kW 14.4 17.9 22.0 28.8 44.0 57.6 Btu/h 49,150 61,000 75,100 98,300 150,200 196,600 Cooling capacity kcal/h 12,400 15,400 18,900 24,800 37,900 49,600 kW 14.4 18.8 22.0 28.8 44.0 57.6 Heating capacity Btu/h 49,150 64,100 75,100 98,300 150,200 196,600 (PEH only) 12,400 16,200 18,900 24,800 37,900 49,600 kcal/h Note: Cooling & heating capacities are based following conditions. Cooling: Indoor:27 DB, 19 WB; Outdoor:
Inhaltszusammenfassung zur Seite Nr. 6
FEATURES Labour saving installation. High sensible cooling capacity. The sensible cooling capacity has been significantly The unit operation can commence immediately after improved through balanced optimised heat connecting to the power supply, refrigerant piping, exchanger design. drain piping, ducting and control system. Comfort heating. (PEH only) Wide electrical control capability. The PEH series are designed to provide effective All series is flexible mechanical control heating even when
Inhaltszusammenfassung zur Seite Nr. 7
MECHANICAL SPECIFICATIONS General Condenser Coils All units are factory assembled, piped, internally wired. Unnecessary power input due to higher discharge They are also tested and checked under a strict quality pressure is avoided by high performance designs of control system in the factory. cross-finned coil. Exterior surfaces of all units of outdoor unit are Condenser coils are made of 9.52mm OD, 0.35mm phosphatized, zinc-coated steel with powder coating thick seamless copper tubes mecha
Inhaltszusammenfassung zur Seite Nr. 8
MODEL-DESIGNATION BREAKDOWN 1 PE-10 MY C Service reference Design Sequence Electrical Supply Y = 3 phase 380~415V 50Hz 4 wires In case of PE(H)-7 Indoor unit ( ) Y = 1 phase 220~240V 50Hz 2 wires Compressor Horsepower 5 = 5 H P 7 = 7 H P 8 = 7.5 H P 10= 10 H P 15= 15 H P 20= 20 H P Series Number PE = Indoor unit PEH = Indoor unit PU = Outdoor unit PUH = Outdoor unit - 7 -
Inhaltszusammenfassung zur Seite Nr. 9
SPECIFICATIONS Cooling only PE-7~20MYC Model name PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC Service PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU reference Power supply Indoor 1PH 2W220~240V 50Hz 3PH 4W380 ~ 415V 50Hz Outdoor 3PH 4W 380~415V 50Hz 3PH 4W380 ~ 415V 50Hz Total cooling capacity 17.9 22.0 28.8 44.0 57.6 kW 61,100 Btu/h 75,100 98,300 150,200 196,600 15,400 18,900 24,800 37,900 49,600 kcal/h 14.3 17.6 23.0 35.2 46.1 kW Sensible cooling capacity 48,800 60,100 78,500 120,200
Inhaltszusammenfassung zur Seite Nr. 10
PEH-5,7,8MYA Heat pump Model name PEH-5MYA PEH-7MYA PEH-8MYA Service PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU reference 1PH 2W220~240V 50Hz Power supply Indoor 3PH 4W380~415V 50Hz 3PH 4W380~415V 50Hz Outdoor 3PH 4W380~415V 50Hz 3PH 4W380~415V 50Hz 3PH 4W380~415V 50Hz 14.4 17.9 22.0 Total cooling capacity kW Btu/h 49,150 61,100 75,100 kcal/h 12,400 15,400 18,900 17.6 kW 11.5 14.3 Sensible cooling capacity 39,400 48,800 60,100 Btu/h kcal/h 10,000 12,300 15,100 kW 14.4 18.8 22.0 Sensible heating capacit
Inhaltszusammenfassung zur Seite Nr. 11
PEH-10,15,20MYA Heat pump Model name PEH-10MYA PEH-15MYA PEH-20MYA Service PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU reference Power supply Indoor 3PH 4W380 ~ 415V 50Hz Outdoor 3PH 4W380 ~ 415V 50Hz 28.8 44.0 57.6 Total cooling capacity kW Btu/h 98,300 150,200 196,600 kcal/h 24,800 37,900 49,600 kW 23.0 35.2 46.0 Sensible cooling capacity 78,500 Btu/h 120,200 157,000 kcal/h 19,800 30,200 39,600 kW 28.8 44.0 57.6 Sensible heating capacity 98,300 Btu/h 150,200 196,600 kcal/h 24,800 37,800 49,500 Capa
Inhaltszusammenfassung zur Seite Nr. 12
ELECTRICAL DATA PE-7~20MYC-EU Cooling PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU VOLT ITEM PU-7MYC1-EU PU-8MYC1-EU PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU TOTAL INPUT kW 7.2 7.8 10.1 17.6 22.0 TOTAL RUN CURRENT A 14.6 14.2 18.9 29.6 39.1 POWER FACTOR % - 74 74 83 78 PE-7 START CURRENT A 74 83 82 119 140 240V 6.0 6.8 8.6 2X7.65 2X9.2 COMPRESSOR INPUT kW 10.7 12.3 15.9 2X12.45 2X15.95 PE- RUN CURRENT A 8 20 0.8 0.6 1.0 1.7 2.4 INDOOR FAN IN
Inhaltszusammenfassung zur Seite Nr. 13
PEH-5,7,8MYA-EU Cooling PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU VOLT ITEM PUH-5MYE-EU PUH-7MYC1-EU PUH-8MYC1-EU PUH-8MYE-EU TOTAL INPUT kW 5.5 7.2 7.8 7.9 TOTAL RUN CURRENT A 9.5 14.6 14.2 14.7 POWER FACTOR % 80 - 76 75 PEH-7 START CURRENT A 69 74 83 83 240V 4.7 6.0 6.8 6.77 COMPRESSOR INPUT kW 8.1 10.7 12.3 12.3 PEH- RUN CURRENT A 8 20 0.54 0.8 0.6 0.6 INDOOR FAN INPUT kW 415V 0.9 3.2 1.2 1.2 RUN CURRENT A 0.25 0.4 0.4 0.53 OUTDOOR FAN
Inhaltszusammenfassung zur Seite Nr. 14
PEH-10,15,20MYA-EU Cooling PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU VOLT ITEM PUH-10MYC1-EU PUH-10MYE-EU PUH-15MYC1-EU PUH-20MYC1-EU TOTAL INPUT kW 10.1 10.2 16.9 21.8 TOTAL RUN CURRENT A 18.9 19.1 30.9 39.3 POWER FACTOR % 74 74 76 77 PEH-7 START CURRENT A 82 82 119 140 240V 8.57 8.67 2X6.77 2X9.12 COMPRESSOR INPUT kW 15.9 15.9 2X12.2 2X16.1 PEH- RUN CURRENT A 8 20 1.0 1.0 2.3 2.5 INDOOR FAN INPUT kW 415V 2.0 2.0 4.1 4.7 RUN CURRENT A
Inhaltszusammenfassung zur Seite Nr. 15
SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model. Second step, to select the model: To select the model, the following conditions must be known: (1) Total cooling load or sensible cooling load (2) Indoor conditioned temperature (WB*1, DB) (3) Designed outdoor temperature (DB)*2 (4) Designed air flow (5) Designed external static pre
Inhaltszusammenfassung zur Seite Nr. 16
(Step-3) Calculation of net capacity Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages 16~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained in Step-2. Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW) Example: PE-8MYC OUTDOOR DB˚C INDOOR INDOOR 40.0 Condition: DB˚C WB˚C Q kW SHC kW SHF T/I
Inhaltszusammenfassung zur Seite Nr. 17
CAPACITY TABLES - 16 - Cooling Capacity (Standard Air Flow) PEH-5MYE-EU OUTDOOR DB ˚C INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW 15 4.9 5.3 13.9 9.8 0.71 4.4 13.5 9.6 0.71 4.6 13.1 9.4 0.72 12.6 9.1 0.72 12.0 8.8 0.74 5.7 11.3 8.5 0.75 6.1 20 16 5.0 5.3 14.5 9.1 0.63 4.5 14.1 8.9 0.64 4.7 13.6 8.7 0.64 13.0 8.3 0.64 12.4 8.1 0.65 5.8 1
Inhaltszusammenfassung zur Seite Nr. 18
- 17 - Heating Capacity (Standard Air Flow) PEH-5MYE-EU OUTDOOR WB ˚C INDOOR -10.0 -5.0 0.0 DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW 3.4 15 9.2 3.1 10.7 12.4 3.7 3.4 16 9.2 3.1 10.7 12.3 3.7 3.4 17 9.1 10.7 12.3 3.8 3.1 9.1 10.6 3.5 12.3 3.8 18 3.2 9.1 10.6 3.5 12.2 3.8 19 3.2 3.5 20 9.0 3.2 10.5 12.2 3.8 3.5 21 9.0 3.2 10.5 12.2 3.9 3.5 22 8.9 10.4 12.1 3.9 3.2 8.9 10.4 3.6 12.1 3.9 23 3.2 8.8 10.3 3.6 12.0 4.0 24 3.2 3.6 25 8.8 3.2 10.3 12.0 4.1 3.6 26 8.7 3.3 10.2 11.9 4.1 3.7 27 8.7 10.2
Inhaltszusammenfassung zur Seite Nr. 19
- 18 - Cooling Capacity (Standard Air Flow) PE-7MYC-EU , PEH-7MYA-EU OUTDOOR DB ˚C INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW SHF T/I kW 15 16.9 11.7 0.69 5.5 16.5 11.5 0.70 5.8 15.8 11.1 0.70 6.2 15.1 10.8 0.71 6.7 14.3 10.4 0.73 7.2 13.6 10.1 0.74 7.9 20 16 17.7 10.8 0.61 5.6 17.2 10.5 0.61 5.9 16.5 10.2 0.62 6.3 15.8 9.9 0.62 6.8 15 9.5 0.63
Inhaltszusammenfassung zur Seite Nr. 20
- 19 - Cooling Capacity (Standard Air Flow) Heating Capacity (Standard Air Flow) (Use for low ambient cooling parts) PE-7MYC-EU , PEH-7MYA-EU PEH-7MYA-EU OUTDOOR DB ˚C OUTDOOR WB ˚C INDOOR -5.0 0.0 5.0 10.0 15.0 INDOOR -10.0 -5.0 0.0 DB ˚C WB˚ C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW 15 16.9 11.5 0.68 5.0 16.7 11.3 0.68 5.1 16.5 11.9 0.72 5.1 16.1 11.0 0.68 5.3 15.7 10.8