Inhaltszusammenfassung zur Seite Nr. 1
QA6ADP QA Conversion
Adapter Module
User’s Manual
QA6ADP
Thank you for buying the Mitsubishi general-purpose programmable
logic controller MELSEC-Q Series
Prior to use, please read both this manual and detailed manual
thoroughly and familiarize yourself with the product.
MODEL QA6ADP-U-JE
MODEL
13JY50
CODE
IB(NA)-0800402-B(0803)MEE
© 2007 MITSUBISHI ELECTRIC CORPORATION
Inhaltszusammenfassung zur Seite Nr. 2
Revisions * The manual number is noted at the lower right of the top cover. Print Date *Manual Number Revision Aug., 2007 IB(NA)-0800402-A First printing Mar., 2008 IB(NA)-0800402-B Partial correction Section 2.2, 6.1 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi electric Corporation cannot be held responsible for any proble
Inhaltszusammenfassung zur Seite Nr. 3
CONTENTS 1. OVERVIEW....................................................................................................3 1.1 Overview...............................................................................................3 1.2 Included Parts .......................................................................................3 2. SYSTEM CONFIGURATION .........................................................................4 2.1 System Configuration .......................
Inhaltszusammenfassung zur Seite Nr. 4
1. OVERVIEW 1.1 Overview This user’s manual describes the specifications, configuration device, part names and setting, and implementation and installation of the QA6ADP QA conversion adapter module. For contents that are not described in this manual such as safety precautions, EMC and low voltage directives, or error code list, refer to QCPU User’s Manual (Hardware Design, Maintenance and Inspection) (SH-080483). The QA6ADP is the adapter module connecting the A (large type) serie
Inhaltszusammenfassung zur Seite Nr. 5
2. SYSTEM CONFIGURATION 2.1 System Configuration This section describes the system configuration and restrictions when the QA6ADP is used. (1) The QA6ADP+A5 B/A6 B is only applicable for the High Performance model QCPU (Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU). (2) Mount the Q5 B/Q6 B, QA6 B, and QA6ADP+A5 B/A6 B in order from the nearest position of the main base unit. The QA6ADP cannot be used in combination with the QA1S6 B. (3) The number of slots of the QA6ADP+A5 B/
Inhaltszusammenfassung zur Seite Nr. 6
2.2 Configuration Device List (1) Extension base unit mountable on the QA6ADP The following shows extension base units that can be mounted on the QA6ADP. Product name Model Remarks Extension base unit A52B, A55B, A58B, (Power supply module not A55B-UL, A58B-UL ---- mounting type) Extension base unit A62B, A65B, A68B, (Power supply module A65B-UL, A68B-UL ---- mounting type) (2) Module mountable on the extension base unit where the QA6ADP is mounted The following shows modules t
Inhaltszusammenfassung zur Seite Nr. 7
Product name Model Remarks High-speed counter AD61, AD61S1 *1 module A/D converter module A68AD, A68AD-S2, A68ADN, ---- A616AD D/A converter module A62DA, A62DA-S1, A68DAV, ---- A68DAI-S1, A616DAV, A616DAI Temperature-digital A68RD3N, A68RD4N, A616TD, ---- converter module A60MX, A60MXRN, A60MXTN Interrupt module AI61, AI61-S1 *2 Positioning module AD70, AD72 ---- AD75M1, AD75M2, AD75M3, *1 AD75P1-S3, AD75P2-S3, AD75P3-S3 A-A1S module conversion A1ADP-XY, A1ADP-SP *3 *4 adap
Inhaltszusammenfassung zur Seite Nr. 8
3. SPECIFICATIONS 3.1 General Specifications This section describes general specifications of the QA6ADP. Item Specifications Operating ambient 0 to 55 temperature Storage ambient -20 to 75 temperature Operating ambient 10 to 90 % RH, No-condensing humidity Storage ambient 10 to 90 % RH, No-condensing humidity Accelera Sweep Frequency Amplitude -tion count Conforming Under 10 times 10 to 57 Hz ---- 0.075 mm Vibration to intermittent each in 2 57 to 150 Hz 9.8 m/s
Inhaltszusammenfassung zur Seite Nr. 9
3.2 Performance Specifications This section describes performance specifications of the QA6ADP. Item Specifications 5VDC internal current 110 mA consumption 130 mm (5.11 inch) (H) 73.5 mm (2.89 inch) External dimensions *1 (W) 74 (2.91 inch) mm (D) Weight 0.2 kg Adapter mounting screw 0.36 to 0.48 N•m (M3) torque Board fixing screw 0.61 to 0.82 N•m torque *1: The external dimensions show values in a status where the QA6ADP is mounted on the extension base unit. 8
Inhaltszusammenfassung zur Seite Nr. 10
4. PART NAMES AND SETTING 4.1 Part Names This section describes part names of the QA6ADP. 9) 8) 3) 1) 7) 6) 4) 2) 5) 3) No. Name Application Connector for sending/receiving signals to the main Extension cable 1) base unit or the other extension base unit and connector connecting an extension cable. Stage number 2) Connector for setting the number of extension stages. setting connector Adapter module Screw for mounting this adapter module on the 3) mounting screw extension
Inhaltszusammenfassung zur Seite Nr. 11
4.2 Extension Stage Number Setting Set the number of extension stages to both the QA6ADP and the extension base unit. The same stage number should be set to both the stage number setting connector of the extension base unit and that of the QA6ADP. POINT Set any number of 1 to 7 which matches to the number of extension stages for the stage number setting connector setting. If the stage number setting of the QA6ADP and that of the extension base unit is different, the two or more set
Inhaltszusammenfassung zur Seite Nr. 12
5. LOADING AND INSTALLATION 5.1 Mounting/Removal of QA6ADP (1) Mounting of the QA6ADP The following shows procedures for mounting the QA6ADP on the extension base unit. Disconnect the A series extension cable from the extension base unit. A) Remove a base cover from the extension base unit. Set the stage number setting connector of the extension base unit. Set the stage number setting connector of the QA6ADP. (The setting should be same as that of the stage number setting connec
Inhaltszusammenfassung zur Seite Nr. 13
(2) Removal of the QA6ADP The following shows procedures for removing the QA6ADP from the extension base unit. Board fixing screw Disconnect an extension cable form the QA6ADP. Remove the adapter module mounting screws of the QA6ADP at two parts (top Mounting and bottom). Extension guide base unit IN side connector Remove the QA6ADP main body from the Adapter module extension base unit. mounting bracket Remove a board fixing screw and an Adapter module adapter module mounting
Inhaltszusammenfassung zur Seite Nr. 14
5.2 Connection/Disconnection of Extension Cable (1) Precautions for handling an extension cable • Do not step on an extension cable. • When laying an extension cable, the minimum bend radius of the cable should be 55 mm (2.17 inch) or more. If it is less than 55 mm (2.17 inch), malfunction may occur due to characteristic deterioration, wire break etc. • When connecting or disconnecting an extension cable, do not hold ferrite cores mounted at both ends of the cable. In case of connecti
Inhaltszusammenfassung zur Seite Nr. 15
• To connect an extension cable to the QA6ADP, remove a sticker on the IN side connector. Base cover Extension base unit IN side QA6ADP Sticker • To connect an extension cable to the OUT side connector of the QA6ADP, remove the portion (lid) under the characters "OUT" by tools such as a flathead screwdriver (5.5 75, 6 100). Extension base unit Base cover Cutting one OUT side thin-walled part QA6ADP Flathead screwdriver 14
Inhaltszusammenfassung zur Seite Nr. 16
• Hold the connector part of an extension cable when connecting the extension cable to the QA6ADP. Extension base unit QA6ADP Connector Extension cable • Make sure to tighten fixing screws of the extension cable connector after connecting the extension cable. (Tightening torque: 0.20 Nm) Extension base unit Flathead screwdriver QA6ADP Fixing screw (3) Disconnection of extension cable When disconnecting an extension cable, hold and pull the connector part of the extension cable aft
Inhaltszusammenfassung zur Seite Nr. 17
6. PRECAUTION FOR USING QA6ADP 6.1 Current Consumption of QA6ADP Since 5VDC is supplied to the QA6ADP from the power supply module of the main base unit, take the current consumption of the QA6ADP into consideration when selecting the power supply module for the main base unit. Current consumption of CPU Current consumption Current consumption Current consumption and I/O of main base unit of I/O of Q5 B of I/O of A5 B of QA6ADP n n: Quantity of QA6ADP in system*1 *1The quant
Inhaltszusammenfassung zur Seite Nr. 18
6.2 Voltage Drop of Extension Cable Since 5VDC is supplied to the QA6ADP from the power supply module mounted on the main base unit, the voltage drop will be caused in the extension cable. If the specified voltage (4.75VDC or more) is not supplied to the IN side connector of the QA6ADP+A5 B/A6 B, wrong input/output may occur. When using the QA6ADP, check that the IN side connector of the QA6ADP+A5 B/A6 B has 4.75VDC or more. The following shows an example regarding how to calculate the
Inhaltszusammenfassung zur Seite Nr. 19
7. COMPATIBLE MODELS LIST This chapter describes external dimensions of the QA6ADP. A series extension base unit that you have already had 2 6-M4 screw 4- 6mounting hole QA6ADP QA conversion (for mounting module) (M5 mounting screw) adapter module Handle POWER I/O I/O I/O I/O I/O 74 (2.91) 73.5 (2.89) Power supply module, Extension cable Power supply module Extension cable 121 (4.76) Unit: mm (inch) 172 (6.77) 18 130 (5.11) 250 (9.84) 9 (0.35) 200 (7.87)
Inhaltszusammenfassung zur Seite Nr. 20
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties. For safe use This product has been manufactured as a general-purpose part for general industries, and has not been designed o