Inhaltszusammenfassung zur Seite Nr. 1
PCC COMMERCIAL
PACKAGED AIR CONDITIONER
PRODUCT SPECIFICATIONS
The PCC Commercial packaged air conditioner
features combination electric heat/electric cooling
with dual high-effi ciency scroll compressors. This unit
contains totally enclosed, permanently lubricated
outdoor fan motors and is designed for over/under or
downfl ow applications.
Standard Features
• Dual high-effi ciency scroll compressors with internal
motor protection for 2-stage cooling
• Totally enclosed, permanently lubri
Inhaltszusammenfassung zur Seite Nr. 2
PRODUCT SPECIFICATIONS NOMENCLATURE PCC 120 3 A 1, 2, 3 4 5 6 Unit Type Engineering PCCPackaged Revisions Air Conditioner Nominal Capacity Electrical 090 90,000 BTU/h 3 208-230/3/60 120 120,000 BTU/h 4 460/3/60 ACCESSORIES THERMOSTAT (CHT90-120) MANUAL AND MOTORIZED FRESH AIR DAMPERS (PGMD-5 & PGMDM-5) Two-stage cool / two-stage heat thermostat with subbase, Manual damper is fi xed position type for 0% to 25% fresh air. manual changeover, fan-on or auto. Note: A variety of Motorized damper is
Inhaltszusammenfassung zur Seite Nr. 3
PRODUCT SPECIFICATIONS SPECIFICATIONS PCC090-3A PCC090-4A PCC120-3A PCC120-4A Cooling Capacity Total BTU/h 86,000 86,000 116,000 116,000 Sensible BTU/h ¹ 63,600 63,600 85,000 85,000 EER ² 10.3 10.3 10.3 10.3 IPLV ³ 10.7 10.7 10.7 10.7 Indoor Blowers (2) Type Belt Belt Belt Belt Wheel (D x W) 12” x 12” 12” x 12” 12” x 15” 12” x 15” Indoor Nominal CFM 3,000 3,000 3,800 3,800 Horsepower 1½ 1½ 3 3 Evaporator Coil (1) Face Area (ft²) 11.2 11.2 14 14 Rows Deep/ Fins per Inch 3/ 16 3/ 16 3/ 16 3/ 16 Tu
Inhaltszusammenfassung zur Seite Nr. 4
PRODUCT SPECIFICATIONS DIMENSIONS
! "!! # # ! " A B C #$# Unit Size $ %& $ ! Height Supply Air Return Air %#& " %' %(# 6 $ PCC090-X 36 12½ 17 /16 & %)# $ % & $ 13 # ! "!! PCC120-X 52 20¼ 25 /16 $ X = Electrical Designation
Inhaltszusammenfassung zur Seite Nr. 5
PRODUCT SPECIFICATIONS DIMENSIONS—ELECTRICAL CONNECTIONS 1. Main power entrance location 2. Control wiring entrance location 3. Optional fi eld installed internal disconnect switch 4. Knockout not used on electric heat units Model A B PCC090-X 6 ⅛ 7⅞ PCC120-X 22 ⅛ 23⅞ X = Electrical Designation SS-GPCC www.goodmanmfg.com 5
Inhaltszusammenfassung zur Seite Nr. 6
PRODUCT SPECIFICATIONS COMPONENT PRESSURE DROPS Electric Medium EFF. Economizer Return Model CFM Wet Coil Heat Filters Air Damper 2,600 0.06 0.03 0.03 0.14 PCC090-X 3,000 0.06 0.04 0.04 0.14 3,400 0.07 0.05 0.05 0.18 3,600 0.05 0.05 0.03 0.14 PCC120-X 4,000 0.05 0.06 0.04 0.14 4,400 0.05 0.08 0.04 0.14 COOLING CAPACITY DATA — PCC090-X @ 3,000 CFM 75 ˚F DB 80 ˚F DB 85˚F DB 90 ˚F DB EVAP. AMB. ˚F EAT KW MBHT MBHS KW MBHT MBHS KW MBHT MBHS KW MBHT MBHS 61 WB 7.6 83.8 72.1 7.6 85.7 84.8 7.7 90.6 90
Inhaltszusammenfassung zur Seite Nr. 7
PRODUCT SPECIFICATIONS COOLING CAPACITY DATA (CONT.) — PCC120-X @ 4,000 CFM 75 ˚F DB 80 ˚F DB 85 ˚F DB 90 ˚F DB EVAP. AMB. ˚F EAT KW MBHT MBHS KW MBHT MBHS KW MBHT MBHS KW MBHT MBHS 61 WB 10.2 115.9 99.7 10.2 118.6 117.2 10.3 125.3 125.3 10.3 132.0 132.0 64 WB 10.3 122.6 87.6 10.3 122.6 107.8 10.3 125.3 125.3 10.3 132.0 132.0 85 67 WB 10.3 130.7 75.4 10.3 130.7 95.6 10.3 130.7 114.5 10.5 132.0 132.0 70 WB 10.6 138.8 63.3 10.6 138.8 83.5 10.6 138.8 102.4 10.6 138.8 122.6 73 WB 10.6 146.9 51.2 10
Inhaltszusammenfassung zur Seite Nr. 8
PRODUCT SPECIFICATIONS ELECTRIC HEAT AIR TEMPERATURE RISE Heater Model HKCB20 HKCB30 HKCB40 Number of Stages 2 2 2 Output (MBH) 67.9 135.8 135.8 2,600 24.2 36.2 - 2,800 22.5 33.6 - 3,000 21.0 31.4 - 3,200 19.7 29.4 39.3 3,400 18.5 27.7 37.0 3,600 17.5 26.2 34.9 3,800 16.5 24.8 33.1 4,000 15.7 23.5 31.4 4,200 15.0 22.4 29.9 CFM 4,400 14.3 21.4 28.6 4,600 13.7 20.5 27.3 4,800 13.1 19.6 26.2 5,000 12.6 18.8 25.2 5,200 12.1 18.1 24.2 5,400 11.6 17.4 23.3 5,600 11.2 16.8 22.5 5,800 10.8 16.2 21.7 6,0
Inhaltszusammenfassung zur Seite Nr. 9
PRODUCT SPECIFICATIONS FAN PERFORMANCE DATA SS-GPCC www.goodmanmfg.com 9
Inhaltszusammenfassung zur Seite Nr. 10
PRODUCT SPECIFICATIONS WIRING DIAGRAM — PCC24-36*** C R Y O W G XFMR R R XFMR C C G Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date schematic. 10 www.goodmanmfg.com SS-GPCC 230 VOLT W2 W1 C E G W Y R 208 VOLT INSTALLATION HEATER FIE LD C O N NE CT I O N KIT FOR PROPER OPERATION ON 208 VOLT THE 208/2 30 V AC 1 Ø FOLLOWING CHANGE MUST BE MADE: MOVE RD6 WIRE FROM TRANSFORMER GND TR ANS F O RM E R 230 TERMINAL TO 208 TERMINAL. GND COM VT-7 LINE LOA
Inhaltszusammenfassung zur Seite Nr. 11
PRODUCT SPECIFICATIONS WIRING DIAGRAM — PCC42-48*** C R Y O W G XFMR R R XFMR C C G Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date schematic. SS-GPCC www.goodmanmfg.com 11 230 VOLT W2 W1 C E G W Y R HEATER 208 VOLT INSTALLATION FI EL D C ON N EC TI O N KIT FOR PROPER OPERATION ON 208 VOLT THE Ø 20 8/230 V A C 1 FOLLOWING CHANGE MUST BE MADE: MOVE RD6 WIRE FROM TRANSFORMER GND TRA NSFO RM ER 230 TERMINAL TO 208 TERMINAL. GND COM VT-7 LINE RD-6
Inhaltszusammenfassung zur Seite Nr. 12
ADJUST COOL HEAT NORM A A ( + ) B B C C (-) CUT TO TEST D D ENABLE DEHUMIDIFY PRODUCT SPECIFICATIONS WIRING DIAGRAM — PCC60*** C R Y O W G C R Y O W G Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date schematic. Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifi cations or designs without notice or without incurring obligations. © 2008-2009 • Goodman Manufacturing Company, L.P. • Houston, Te