This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite SmartOnline UPS Systems. UPS Location Warnings Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight. Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit. Only operate your UPS at indoor temperatures between 32" F and 104" F (between 0" C and 40"
Inhaltszusammenfassung zur Seite Nr. 3
Familiarize yourself with the location and function of the front and rear panel features before installing and operating your UPS. FRONT PANEL 0 0 0 0 UPS SYSTEM , 5 1. "ON/OFFn Switch: This momentary rocker switch turns the UPS System's inverter ON and OFF. 2. "SELECT" Button: This button performs two functions: it allows you to browse through different power readings on the LCD Display by momentarily pressing the button; it also allows you to silence the UPS alarm by pressing and hol
Inhaltszusammenfassung zur Seite Nr. 4
SUBP
Inhaltszusammenfassung zur Seite Nr. 5
REAR PANELS 1. Manual Bypass Switch: This red and yellow dial is used in one step of putting the UPS in "BYPASS" mode, which must be done before performingany maintenance on the UPS with the connected load supported. (See page 12 for step-by-step instructions for going into "BYPASS.") While this switch is on "BYPASS." connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout. 2. Input Terminal Block: Use these terminals to conne
Inhaltszusammenfassung zur Seite Nr. 6
INVERTER OPERATION DIP SWITCH SETTINGS (SUIOKPM SHOWN) Using a small tool, set the four Inverter Opera- tion DIP Switches (located on the rear panel of your UPS, see pg. 4-5 for location) to match your input voltage, input frequency and desired operational mode. InDut Voltage Selection (D~P switch& # 1 ~r #2) (Input Voltage Select Terminal Block) These DIP switches and the Input Terminal Select Block must BOTH be set to match your input voltage. Your UPS WILL NOT CONVERT the voltage
Inhaltszusammenfassung zur Seite Nr. 7
UPS LOCATION Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external battery packs. INPUTAND OUTPUT CONNECTION WIRING SELECTION Choose appropriate cabling (depending on current carried; see chart below) to connect your UPS to an AC power supply and your equipment to your UPS: OUTPUT MODEL RATED INPUT RATED OUTPW RATED OUE'UT PROTECnON CURRENT CURRENT CURRENT CIRCurr 2
Inhaltszusammenfassung zur Seite Nr. 8
EXTERNAL BATTERY PACK CONNECTION (SUGK: Optional; SU1OK: Required) Since SUGK models contain internal batteries, connecting external battery packs (to extend runtime) is optional. SUlOKPM models, however. do not have internal batteries and require an external battery pack connection to a SUlOKBP or a SUBP. Using the supplied battery connection cable, insert one end into the External Battery Connector on the rear panel of your UPS and the other end into the Battery Output Connector on the
Inhaltszusammenfassung zur Seite Nr. 9
BA77ERY CONDITION VERIFICATION When the UPS is operating from battery power, the alarm and LCD Display will both alert you to the UPS battery's charge condition. Batterv Charge Condition Alarm ED Dis~lav FULL Short Beep (every 2 seconds) ON BAlTERY BA'IT = XXV Wo LOW Short Beep (every 1/2 second) BA'ITERY LOW BAT = XXV Wo UNDER Continuous Beep BA'ITERY UNDER SHUT DOWN INITIAL BAVERY CHARGING (OPTIONAL) Your UPS System's battery is fully charged prior to shipping. However, if your UPS
Inhaltszusammenfassung zur Seite Nr. 10
SELF-TESTING When you turn the UPS ON, it will perform a brief (about 25 second) self-test. See figure below for display sequence.' 'Note: ~startingfiom battery, the BATIERY LED will be Ut and the I/P and BYPASS LED5 wlll MI. TheJInd LCD dlsplay In (he diagram below appears when the LlPS b operating normally under utfllty-supplled AC Input power. SELECT FREQ OUT . XXHz Sltll~lOlllll~ ,,,, UPS SYSTEM A SELECT INPUT AC OK UPS SYSTEM $! OFF UPS SYSTEM UPS SYSTEM UPS SYSTEM UPS SYST
Inhaltszusammenfassung zur Seite Nr. 11
LCD DISPLAY SELECT SWITCH Momentarily press the "SELECT" switch on the front panel to browse through different power readings on the LCD Display. The LCD Display will show which one of four operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass. Also, as you press the "SELECT" switch, the LCD Display will browse through load. input, bypass, output and battery conditions. "ON-BATTERY" MODE OPERATION "NORMAL" MODE OPERATION "ECONOMY' MODE OPERATION "ON BYPASS" M
Inhaltszusammenfassung zur Seite Nr. 12
BATERY CHARGE WA RNlNGS Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately. Battery Charge Warning LCD Display Message Battery charge nearly depleted BATTERY LOW AC/DC charger not operating CHARGER FAILURE! OPERATION UNDER SHUTDOWN Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the "Input," "Output" and "Bypass" LEDs
Inhaltszusammenfassung zur Seite Nr. 13
RS-232 INTERFACE This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses RS-232 communications to report UPS status and power conditions. Using this port, Mpp Lite software can monitor and manage network power and automatically save open files and shut down equipment during a blackout. Contact Mpp Lite Customer Support at (773) 869-1233 for informa- tion on available SNMP, network management and connectivity sof
Inhaltszusammenfassung zur Seite Nr. 14
DRY CONTACT INTERFACE: This female DB9 contact-closure port allows your UPS to send contact-closure signals to indicate that it is on battery back-up mode and if its batteries are running low. The port can also receive a remote shutdown signal. Pin assipnment; lmin.U.3mA LOW BATTERY I - REMOTE SHUTDOWN SIGNAL FROM EXTERNAL b COY NC If I C 1 I I I SIGNALFROM COMPUTER .' ! MAXIMUM CAPACITY OF DRY CONTACT: AC250Vn4 DC30vnA DRY CONTACT INTERFACE TABLE UPS Operating Pin 8,3 Pin 1,3
Inhaltszusammenfassung zur Seite Nr. 15
Service Your Smartonline UPS is covered by the 2-year limited warranty period described below. A variety of service contracts is also available from Tripp Lite. including start- up service contracts and 3- to 5-year SafeSure on-site service contracts. For more information, call Tripp Lite Customer Service at (773) 869-1233. 2- Year Limited Warranty TRlPP LlTE warrants tls products tncludtng batteries to be free from defects In materials and workmanship for a period of two years from the d
Inhaltszusammenfassung zur Seite Nr. 16
STATIC MANUAL OUTPUT INPUT - SURGE , ACT0 DC - - OUTPUT * *' DCTOAC - - - - BYPASS BYPASS ACINPUT lSoLATIoN PROTECTOR FILTER FILTER CONVERTER INVERTER BREAKER SW~CH SWITCH XFM I I STANDARD - BAllERIES: -LEDS 240 VDC CPU I CHARGER LCD CONTROLLER dLs -TO RS-232 As400 DRY CONTACT ACCESSORY SLOT SUBP EXTERNAL REP0 POWER BATTERY CABINET(S): - SUPPLY 240 MC dLt 120 VAC INPUT
Inhaltszusammenfassung zur Seite Nr. 17
(Notc: Excludingisolation transformer) Model SU6K SUlOK && Inputvoltage 156V-280VSlngle Phase 156V-280VSinglePhase Input Frequency 50/60 Hz t 3 Hz 50/60 Hz 2 3 Hz (selectable, pg. 7) (selectable. pg. 7) Input Current 32A 50A Inrush Current <150A <200A Power Factor (Full Load) ~0.99 >0.99 Emciency (Full Load/On-Line) >87Oh >88% Circuit Breaker 40A 63A OU~DU~ VA 6000 10000 Watts (Power Factor: 0.7) 4200 7000 Waveform (On-Line) Slnewave Slnewave Waveform (On-Battery) Sinewave Slnewa