Pole and Ground Mount Standby Power Supply Enclosures
User Manual
990-5517 04/2003
Inhaltszusammenfassung zur Seite Nr. 2
Inhaltszusammenfassung zur Seite Nr. 3
Chapter 1 General Information The CTSLLP/G Standby Power Supply Series Enclosures provide a power source for broadband cable operations. Safety This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment. Changes and modifications to this unit not expressly approved by APC could void the warranty. Failure to
Inhaltszusammenfassung zur Seite Nr. 4
Specifications Environmental Specifications -40º F to 140º F (-40º C to 60º C) Operating Temperature 5% to 95% noncondensing within enclosure Humidity Physical Specifications Characteristic Specification Height x Width x Depth CTSLLGULH110S1 20” x 22” x 7.5” (51cm x 56 cm x 19 cm) CTSLLPULH100S1 14” x 22” x 7.5” (36 cm x 56 cm x 19 cm) CTSLLGECH220S1 20” x 22” x 7.5” (51cm x 56 cm x 19 cm) Weight CTSLLGULH110S1 20 lbs (9 kg) CTSLLPULH100S1 16 lbs (7 kg) CTSLLGECH220S1 20
Inhaltszusammenfassung zur Seite Nr. 5
Chapter 2 Installation Only trained service personnel should install and maintain the power supply. Prior to installation, utility line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, permits and electrical wiring must be adhered to. Do not operate the power supply where the temperature and humidity are outside the specified limits. See Specifications in this manual. Unpacking Inspect the unit upon re
Inhaltszusammenfassung zur Seite Nr. 6
CTSLL Enclosure Installation CTSLLG Enclosure Installation 1. Remove the lid from the battery vault. 2. Position the CTSLLG on the edge of the vault lid. 3. Install two 5/16” (.8 cm) x 1” (2.5 cm) flat head screws through the lid into the holes in the back of the CTSLLG. 4. Install four 5/16” (.8 cm) x 3/4” (2 cm) flat head screws through the lid into the holes in the front and sides of the CTSLLG. 5. Replace the lid with the attached enclosure, onto the vault. See diagram. 6.
Inhaltszusammenfassung zur Seite Nr. 7
CTSLLP Enclosure Installation When wall mounting, use screws that are appropriate for the weight of the unit and the mounting surface material. Refer to Specifications in this manual. Top Hole .75” (2 cm) 11.5” (29 cm) Mounting Bracket is permanently attached to the enclosure. 5/8” (1.5 cm) Pole Bolt and Bottom Hole Square Washer .75” (2 cm) 5
Inhaltszusammenfassung zur Seite Nr. 8
Controls and Indicators CTSLLP/G Bottom View Index Control/Indicator Definition 1 Ground wire lug Provides connection of chassis to earth ground 2 Utility power input Yellow indicator illuminates when line voltage is present indicator lamp (not present on all models) 3 Normal indicator lamp Green indicator illuminates when the unit is operating in normal mode, (output is provided by CTFLM module) 4 Standby indicator Red indicator illuminates when the power supply has transferred
Inhaltszusammenfassung zur Seite Nr. 9
Wiring Install an approved 20 A high-magnetic utility circuit breaker. Ensure the utility circuit breaker is OFF. • Unlock and open the front/top panel on the CTSLLP/G. Refer to the diagram below for wiring details. • Connect the black and white wires from the incoming utility line. • Route the power feed coax to the bottom of the enclosure and attach to the coax cable adapter using a pin connector. • Attach the stinger lug to the pin connector center pin. • Attach suitable solid co
Inhaltszusammenfassung zur Seite Nr. 10
Install the Battery Vault Refer to User Manual 990-1220 packaged with the battery vault for installation instructions. Connect the Batteries in the Battery Vault Refer to User Manual 990-1220 packaged with the Battery Vault for battery connection details. Install the temperature sensor on top of the batteries as shown in the 990-1220 User Manual. Install the CTFLM and the CTSLM Refer to the User Manual 990-5501 packaged with the CTFLM and CTSLM for installation instructions. Conn
Inhaltszusammenfassung zur Seite Nr. 11
Chapter 3 Troubleshooting and Maintenance Troubleshooting Power Supply Failure Problem Possible Cause Solution Power Supply No input voltage detected at connector J1, pins Replace the wiring harness Failure 1 and 2. Input voltage present at connector J1, pins 1 Disconnect power from the and 2. supply No input voltage at the black and white wires Replace the Euro block input lines. Input voltage present at the black and white Replace the wiring harness. wire input lines. No voltage
Inhaltszusammenfassung zur Seite Nr. 12
Routine Maintenance Procedures • Visual Inspection • Check external surfaces, connectors, indicators and wiring/cable assemblies for signs of dirt, wear, and damage. • Cleaning • Brush dust from controls and receptacles using a small paintbrush. • Wipe surfaces with clean, dry cheesecloth. • Clean exterior surface with clean cheesecloth moistened with isopropyl alcohol or a general purpose detergent. NOTE: Do not allow cleaning solution into the interior of the enclosure or into a
Inhaltszusammenfassung zur Seite Nr. 13
• Complete Performance Verification. Refer to Initial Startup in the CTFLM/CTSLM User Manual 990-5501. • Replace/close the enclosure door(s). • Indicator Lamp Replacement Gently pry the lens off the indicator lamp using the tip of a screwdriver. NOTE: Place a hand over the lens as it is loosened to ensure that the lens is not lost during the procedure. • Remove the spent lamp and replace it with a new one. • Snap the lens back into place. Euro Block Replacement • Switch the utility
Inhaltszusammenfassung zur Seite Nr. 14
Chapter 4 Service, Contact and Warranty Information Service APC makes every effort to ensure parts and equipment arrive in working condition. Occasionally, it may be necessary to return parts or equipment that are not in working condition. If the unit requires service do not return it to the dealer. Follow these steps: 1. Contact APC Customer Service through the APC web site, www.apc.com/support. Note the product model number, the serial number, and the date purchased. If you call APC
Inhaltszusammenfassung zur Seite Nr. 15
Limited Warranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportation charges prepaid and must