Inhaltszusammenfassung zur Seite Nr. 1
ED6000T & ED6200T
Parallel Redundant
ON-LINE SERIES
User’s Manual
Para Systems, Inc.
1455 LeMay Drive
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Internet: minutemanups.com
UPS Sizing: sizemyups.com
PN – 34000355 R2
Inhaltszusammenfassung zur Seite Nr. 2
Table of Contents 1 Important Safety Instructions...................................................2 1.1 An Important Notice...............................................................2 1.2 Life Support Policy ................................................................3 1.3 FCC Notice............................................................................3 2 Product Introduction .................................................................4 2.1 System Ov
Inhaltszusammenfassung zur Seite Nr. 3
1.1.11 SAVE THESE INSTRUCTIONS - This manual contains important 1 Important Safety Instruction instructions that should be followed during the Installation and the Maintenance of the UPS and batteries. 1.1. An Important Notice 1.1.12 CAUTION - A disconnect switch must be provided by the user for the AC 1.1.1 To ensure safety in all applications where a UPS system is hardwired to the output circuit when the UPS’s output is hardwired. To reduce the risk of fire, electrical supply the
Inhaltszusammenfassung zur Seite Nr. 4
2 Product Introduction 2.2.9 The temperature-controlled fans will extend the life of the fans and reduce the annoying noise caused by fans. 2.1. System Overview 2.3. Symbols on the LCD Display Panel This On-Line UPS protects computers, servers, internetworking, and telecommunications equipment from blackouts, brownouts, overvoltages, and Item Symbol Description surges. This On-Line UPS converts the input AC to DC and then back to a True Sine Wave AC output. The True Sine Wave
Inhaltszusammenfassung zur Seite Nr. 5
32 Er06 Output Short Circuit 15 ON and Alarm Silencer Switch 33 Er08 DC Bus high-voltage-level abnormal 16 OFF Switch 34 Er09 DC Bus low-voltage-level abnormal 17 Previous Page or Setting Change 35 Er10 Inverter Over-current 18 Next Page 36 Er11 UPS Overheated 19 Special Function Log in /out 37 Er12 Inverter Overload 20 Enter or Reconfirmed 38 Er13 Charger Failure or Abnormal 21 Utility Input Normal LED 39 Er14 Fan Failure 22 Bypass Input Normal LED 40 Er1
Inhaltszusammenfassung zur Seite Nr. 6
2.4. Controls and Indicators Bypass Input found when running on CVCF 48 Er24 mode (CVCF mode not supported) 2.4.1 UPS Control panel 49 Er26 PFC Over-current The UPS must be operated in normal mode in 50 Er27 parallel system 51 Er28 Bypass Overload Time out and cut off output. 52 Er29 Charger overcharges battery (>300Vdc) 53 Er30 Inverter Balance error The settings of both control board and driver 54 Er31 board are not matched together 55 Er32 Sync S
Inhaltszusammenfassung zur Seite Nr. 7
2.5. Rear Panel 3 Installation and Operation (QUALIFIED SERVICE PERSONNEL ONLY) Be sure to read the Installation Placement and all of the CAUTIONS and the WARNINGS before installing the UPS system. Packages that are crushed, punctured, or torn such that the contents are revealed should be set-aside in an isolated area and be inspected by a qualified person. If the package is deemed to be not usable, immediately contact the freight carrier and the place of purchase. USE CAUT
Inhaltszusammenfassung zur Seite Nr. 8
3.2. Installation Placement 3.4. Installation of the Caster Covers This UPS system is intended to be install in a temperature controlled 3.4.1 Lock the casters so that the unit will not move. 3.4.2 Step 1: There are two A1 cover plates, one for each side of the unit. Insert environment that is free of conductive contaminants. Select a location, which the A1 cover plates into the slots and slide towards the rear of the unit. will provide good air circulation for the UPS at all times. Keep
Inhaltszusammenfassung zur Seite Nr. 9
3.5. Wiring the Input and Output Connections (Qualified Electrical Contractor Only) 3.5.1 A Qualified Electrical Contractor must perform the hardwiring when connecting the Input and Output wires to the terminal block on the ED6000T UPS. Apply 22.1lb-in of torque force when connecting to the terminal blocks. The Input and Output of the UPS MUST be Hardwired. 3.5.1.1.2 Configuration # 1: Output: Two 120VAC 3KVA circuits (3KVA max load per circuit). Total c
Inhaltszusammenfassung zur Seite Nr. 10
3.5.1.1.4 Configuration # 3: 3.5.1.1.6 Configuration # 5: Output: One 208VAC 6KVA circuit. Total output load not to exceed 6KVA. Output: Two 120VAC circuits (3KVA max load per circuit). and one 208VAC 1. Connect a jumper wire from L22 to N21. 6KVA circuit. Total combined output load not to exceed 6KVA. 2. Circuit1 (208VAC): L23 - L1, N22 - L2, G2 - Ground. 1. Connect a jumper wire from L22 to N21. 2. Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground. 3. Circuit2 (120VAC): L21 -
Inhaltszusammenfassung zur Seite Nr. 11
3.5.2 A Qualified Electrical Contractor must perform the hardwiring when 3.6. Operation and Setup Instructions connecting the Input and Output wires to the terminal block on the ED6200T UPS. Apply 22.1lb-in of torque force when connecting to the 3.6.1 Startup in the Normal Mode terminal blocks. The Input and Output of the UPS MUST be Hardwired. 3.6.1.1 Switch the Utility power circuit breaker (at the service panel) to the On position. 3.6.1.2 Switch the UPS’s Input circuit brea
Inhaltszusammenfassung zur Seite Nr. 12
3.6.1.6 The UPS will perform another self-test and the LCD display will change 3.6.1.7 The UPS has successfully passed the start-up procedure. The UPS will from drawing C to drawing D. During the self-test the UPS will switch to charge the batteries whenever the UPS is connected to an AC source and the Battery mode for approximately 4-seconds, then the LCD display will there is an acceptable AC voltage present. It is recommended that the change from drawing D to drawing E1. Once the UPS succe
Inhaltszusammenfassung zur Seite Nr. 13
I K * It shows the UPS is providing power to the “load”. * It shows the input frequency from the Bypass Input. 3.6.3 Measured Values detected by UPS 3.6.3.1 If you would like to check the measured values detected by the UPS, L please use the scroll down and scroll up keypads. When you use scroll down keypad, the LCD display will display the drawings in the following order: Drawing C (Voltage from Utility Input)
Inhaltszusammenfassung zur Seite Nr. 14
P R1 * It shows the Internal Temperature of the UPS System. * It shows the Self-test is “Disabled”. 3.6.4 UPS Default Data and Special Function Features 3.6.4.1 Once the UPS has successfully started up, press the Special Function keypad to change the LCD display screen to drawing Q1. R2 * It shows the Self-test is “Enabled”. Q1 S1 * It shows the Buzzer is “Enabled”.
Inhaltszusammenfassung zur Seite Nr. 15
U Y * It shows the Inverter Output Voltage setting. * It shows that this UPS is the first UPS in the parallel systems. 3.6.4.3 Press the scroll up keypad to change the default setting. The settings includes Buzzer ON (as drawing Q1), or Buzzer OFF (as drawing Q2, Alarm silence for UPS Warning) and self-test OFF (as drawing R1) or Self- V1 test ON (as drawing R2). The UPS will execute battery test for 10-seconds. If the Self-test is successf
Inhaltszusammenfassung zur Seite Nr. 16
3.6.7 Turning Off the UPS 3.6.5.10 When all of the setting changes are complete, press the enter keypad to save all the changes. Then the LCD screen will display drawing Z, then the LCD screen will change to drawing AA to confirm the changes. If you 3.6.7.1 Press the Off switch for approximately 5-seconds, the Inverter will turned off, the UPS will transfer to the Bypass mode and the LCD screen do not want to save the changes press the “OFF” keypad for 5- will display drawing B. seco
Inhaltszusammenfassung zur Seite Nr. 17
3.6.8.1.12 Press and hold the On Switch (on the front panel of the UPS) for DC Mode Operation: approximately 3-seconds, then release. The audible alarm will sound 2- While the UPS is in the DC mode apply the short to pin1 and pin2 for beeps. The UPS will perform its normal startup test. Once the startup is approximately 1.0-second. The UPS shuts down, the fans will still be on. In complete the UPS will be in the normal On-Line mode. approximately 1-minute the fans will reduce speed. NOTE:
Inhaltszusammenfassung zur Seite Nr. 18
6 Troubleshooting Guide 7 Replacing the Batteries (QUALIFIED SERVICE PERSONNEL ONLY) If the UPS malfunctions, check the followings: Please read all of the WARNINGS and CAUTIONS before attempting to a. Is the wiring of the input and the output correct? service the batteries. b. Is the input voltage within the acceptable window of the UPS? If items a. and b. above are correct then proceed with the following chart. If the WARNING: This Uninterruptible Power Supply contains potentially h
Inhaltszusammenfassung zur Seite Nr. 19
7.1.10 Looking from the front of the UPS on the right-hand side (FIG. 3), 7.1. Battery Replacement Procedure disconnect the battery positive (Red) wire. Place a piece of electrical tape (QUALIFIED SERVICE PERSONNEL ONLY) over the end of battery positive (Red) wire. This UPS system does not have Hot-swappable batteries. The UPS system 7.1.11 Disconnect battery jumper “A” and place a piece of electrical tape over the must be turned Off to perform the Battery Replacement. end of battery jum
Inhaltszusammenfassung zur Seite Nr. 20
7.1.21 Looking from the front of the UPS on the left-hand side (FIG. 4), disconnect 7.1.32 Back to the right-hand side of the UPS (FIG. 3), remove the piece of the battery negative (Black) wire. Place a piece of electrical tape over the electrical tape from the end of battery positive (Red) wire. Observer polarity. end of battery negative (Black) wire. Reconnect the battery positive (Red) wire. 7.1.22 Disconnect battery jumper “A” and place a piece of electrical tape over the NOTE: Some spark