Inhaltszusammenfassung zur Seite Nr. 1
APC Silcon
480kW 400V UPS
Installation Guide
Copyright 2000 APC Denmark ApS
This manual is subject to change without
notice and does not represent a commitment
on the part of the vendor
Inhaltszusammenfassung zur Seite Nr. 2
Thank You! Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation. The installation and use of this product must comply with national, federal, state, municipal and local codes. Safety Symbols used in this manual WARNING! Indicates a hazard which, if not avoided, could result in injury or death. CAUTION! Indicates a hazard which, if n
Inhaltszusammenfassung zur Seite Nr. 3
Contents 1.0Introduction 5 1.1 Tools and Equipment 5 2.0Unpacking 6 3.0Installation 7 3.1 Requirements on Site 7 3.1.1 Cabinet Dimensions 7 3.2 Footprint 8 3.2.1 1900mm Cabinet for 480kW UPS 8 3.2.2 1600mm Cabinet for 480kW Isolation Transformer 8 4.0 External Connection 9 4.1 Connecting the UPS 9 4.2 System Integration Interface 11 4.2.1 Connections 12 4.3 Parallel Board 13 4.4 Relay Board 16 4.4.1 Relay Board/Relay Functions 17 4.5 Communication Interface Board 19 4.5.1 Connect
Inhaltszusammenfassung zur Seite Nr. 4
6.4.1 Extension of Remote Display Communication Distance 57 6.4.2 Remote Display Installation 59 6.4.3 Remote Display Use 60 6.5 Isolation Transformer 61 6.5.1 Connecting Isolation Transformer 62 6.5.2 Wiring up UPS with External Yyn0 Isolation Transformer at Output 64 6.5.3 Wiring up UPS with External Yyn0 Isolation Transformer at Input 65 6.5.4 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input 66 6.5.5 Wiring up UPS with External Optional Dzn0 Isolation Transf
Inhaltszusammenfassung zur Seite Nr. 5
Introduction 1.0 Introduction Power regulation varies from country to country, and information given in this installation guide can therefore only be of a general nature. Electricians should therefore always refer to national and local electrical codes prior to installing the UPS system. 1.1 Tools and Equipment CAUTION! Heavy equipment. To prevent personal injury or equipment damage,
Inhaltszusammenfassung zur Seite Nr. 6
Unpacking 2.0 Unpacking NOTICE! Unless otherwise specified by the shipping company use a fork lift to unload equipment from pallet 1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates 2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage 3. Copy type label data to label copy below for easy identification of system 4. Use fork lift to transport system to installat
Inhaltszusammenfassung zur Seite Nr. 7
Installation 3.0 Installation 3.1 Requirements on Site All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long as free space is allowed for system doors to open. (Per applicable national and/or local codes.) For ventilation and service purposes allow for free space of minimum 1m above the unit or per n
Inhaltszusammenfassung zur Seite Nr. 8
Installation 3.2 Footprint 3.2.1 1900mm Cabinet for 480kW UPS Rear Com. cable entry Front 3.2.2 1600mm Cabinet for 480kW Isolation Transformer Rear Power cable entry Front 990-4053 8 Installation Guide APC Silcon 480kW 400V UPS Power cable entry
Inhaltszusammenfassung zur Seite Nr. 9
External Connection 4.0 External Connection 4.1 Connecting the UPS Right side view Relay board Please refer to “Relay Board” section Battery Front view System Integration Interface Communication Interface Parallel Controller NOTICE! Check correct phase rotation of mains input voltage!! 2 Max. input/output cables: 3//300 mm . If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required. CAUTION! This UPS unit is an EN 50091-2 product and may cause radio interfere
Inhaltszusammenfassung zur Seite Nr. 10
External Connection CAUTION! At a switch mode load of 100% the neutral must be rated for 200% output phase current. UPS External External External PE Maximum External Input Input Cable Cable External Output Cable Fuses* FM [mm2] [mm2] Output [mm2] [A] 380-415V Fuses* 380-415V [A] 480kW 1000 3//185 185 800 3//150 * DIN gL types NOTICE! All cable dimensions are recommended sizes only. Refer to local legal regulations. UPS External Alarm External System External Battery External
Inhaltszusammenfassung zur Seite Nr. 11
External Connection 4.2 System Integration Interface NOTICE! Consistent use of designations (Q001, Q002, Q003, H002, H003) in diagrams simplifies information exchange. System Integration Interface (SII) is the control link between UPS and system main switches as shown in above diagram. The purpose of the SII is to ensure correct operation of switches without losing system output power. Auxiliary contacts on the main switches transmit the SII board inputs. Lamps on Service Bypass Pane
Inhaltszusammenfassung zur Seite Nr. 12
External Connection 4.2.1 Connections Blue Brown 990-4053 12 Installation Guide APC Silcon 480kW 400V UPS
Inhaltszusammenfassung zur Seite Nr. 13
External Connection Terminal Blocks: X003/X004 (Anxiliary Contacts) When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the opposite way from “OFF or 0” to “ON or 1”, the anxiliary contact has to close with a maximum delay of 0.5 seconds from the time the corresponding main
Inhaltszusammenfassung zur Seite Nr. 14
External Connection The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between paralled systems. NOTICE! For reliability reasons, APC recommends separate battery packs in redundant/parallel conigurations. To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power supply to the UPS and connect the ri
Inhaltszusammenfassung zur Seite Nr. 15
External Connection Parallel Board X021:15-pin SUB-D female X020:15-pin SUB-D female External multicore cable with 14 wires + shield to other parallel units UPS 2 UPS 1 UPS 3 External Control Cables External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be connected. Shield is connected to plug cover at both ends. Terminals X020 and X021 for control cables l
Inhaltszusammenfassung zur Seite Nr. 16
External Connection 4.4 Relay Board 1 Maximum load: 8.0A – 250VAC 2 0.3A – 60VDC 3 Minimum load: 0.05A – 6VAC 0.05A – 6VDC Relays All relays are “fail safe”: In alarm modes, relay coil will be de-energized. 990-4053 16 Installation Guide APC Silcon 480kW 400V UPS
Inhaltszusammenfassung zur Seite Nr. 17
External Connection 4.4.1 Relay Board/Relay Functions NOTICE If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure Relay Message Alarm-trigging Events Number 1 ## (X002) Mains outside limits Mains voltage RMS outside limits Mains wave form (fast detector) outside limits Mains frequency outside limits 2 ## (X003) Bypass outside limits Bypass voltage RMS outside limits Bypass wave form (fast detector) outside limits Bypass frequency outside limits 3
Inhaltszusammenfassung zur Seite Nr. 18
External Connection ## Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds. See section 5.2: System configuration NOTICE! Alarm Trigging Events 1-2-3-9-10-11-13 activates the corresponding alarm relay after the delay. Alarm Trigging Events 4-5-6-7-8-12-14-15 activates the corresponding alarm relay momentarily. Common fault relay 16 is activated at the
Inhaltszusammenfassung zur Seite Nr. 19
External Connection 4.5 Communication Interface Board The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply failure. 4.5.1 Connections . . 990-4053 Installation Guide APC Silcon 480kW 400V UPS 19
Inhaltszusammenfassung zur Seite Nr. 20
External Connection 4.6 Connecting of APC Silcon Tripel Chassis The enclosed Triple Chassis must be connected to the serial port on the Communication Interface Board, and to the 24V supply (cables included). Terminal locations shown below. 480 Serial ports X50 X50 is a 24V supply for Triple Chassis. Front view of UPS Cabinet (doors open) Only to be used for this purpose. Not suitable for telephone equipment. Triple Chassis must be connected to both X50 and a serial port. APC Silc