Service Manual
2007
Room Air Conditioners
RAC-Svc-07 (4-07)
Inhaltszusammenfassung zur Seite Nr. 2
TABLE OF CONTENTS Introduction / Typical Unit Components ....................................................................................................................................... 3 Warranty ....................................................................................................................................................................................... 4 Routine Maintenance ..........................................................................................
Inhaltszusammenfassung zur Seite Nr. 3
INTRODUCTION This service manual is designed to be used in conjunction with the installation manuals provided with each air conditioning system component. This service manual was written to assist the professional RAC service technician to quickly and accurately diagnose and repair malfunctions. This manual will deal with subjects in a general nature. (i.e. all text will not pertain to all models). TYPICAL UNIT COMPONENTS Fresh Air Compressor Capillary Tube Liquid Filter Driers Reversing Va
Inhaltszusammenfassung zur Seite Nr. 4
Friedrich Air Conditioning Company P.O. Box 1540 San Antonio, TX 78295 210.357.4400 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor cost for removing inaccessible units and/or charges fo
Inhaltszusammenfassung zur Seite Nr. 5
ROUTINE MAINTENANCE NOTE: Units are to be inspected and serviced by qualifi ed service personnel only. Routine maintenance is required annually or semi-annually, depending upon annual usage. 1. Clean the unit air intake fi lter at least every 250 to 300 fan hours of operation or when the unit’s indicator light is on if so equipped. Clean the fi lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling. 2. The indoor coil (evaporator coil), the outdoor coil (conden
Inhaltszusammenfassung zur Seite Nr. 6
UNIT IDENTIFICATION Model Number Code S S 08 L 1 0 A 8th Digit – Engineering 1st Digit – Function Major change S = Straight Cool, Value Series Y = Heat Pump E = Electric Heat K = Straight Cool 7th Digit – Options R = Straight Cool 0 = Straight Cool & X = Straight Cool Heat Pump Models W = Thru-the Wall, 1 = 1 KW Heat Strip, Normal WallMaster Series 3 = 3 KW Heat Strip, Normal 4 = 4 KW Heat Strip, Normal 5 = 5 KW Heat Strip, Normal 2nd Digit C = Casement Q = Q-Star 6th Digit – Vol
Inhaltszusammenfassung zur Seite Nr. 7
PERFORMANCE DATA *Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity. 7 OPERATING R-22 BREAKER EVAP. AIR TEMP. DEG. F ELECTRICAL RATINGS CONDENSER PRESSURES REF. FUSE PERFORMANCE Discharge Suction Super Sub- TEMPERATURE Voltage DATA* Cooling Temp Temp Heat Cooling Discharge Temp. Amps Amps Locked Charge 60 Hertz DEG. F Suction Discharge Air Drop F. Cool Heat Rotor Amps in OZ. Amps XQ05L10A-B 56 24 119 151 58 13 2
Inhaltszusammenfassung zur Seite Nr. 8
ELECTRICAL DATA Wire Size Use ONLY wiring size recommended for single outlet branch circuit. Fuse/Circuit Use ONLY type and size fuse or HACR Breaker circuit breaker indicated on unit’s rating plate. Proper current protection to the unit ELECTRIC SHOCK HAZARD. is the responsibility of the owner. Turn off electric power before service or installation. Grounding Unit MUST be grounded from branch All electrical connections and wiring MUST be circuit through service cord to unit, or installe
Inhaltszusammenfassung zur Seite Nr. 9
FUNCTIONAL COMPONENT DEFINITIONS MECHANICAL COMPONENTS ELECTRICAL COMPONENTS cont’d ® Bellows condensate valve Temperature-sensitive valve MoneySaver switch When engaged, it sends the power that opens up to drain off condensate water when the outside supply to the fan motor through the thermostat, which allows temperature falls below 40°F and closes when the outside for a cycle-fan operation. temperature reaches 58°F. Fan Motor Dual-shafted fan motor operates the indoor Vent door Allows i
Inhaltszusammenfassung zur Seite Nr. 10
ELECTRONIC CONTROLS TESTING THE ELECTRONIC CONTROL TESTING THE ELECTRONIC CONTROL XQ/WS BOARDS & QME BOARDS ERROR CODE LISTINGS Activating Test Mode: Activate test mode by pressing at E1 SHORT CYCLE SITUATION: Keyboard is fine. the same time the “MODE” button and the temperature Investigate and defi ne short cycling problem. “DOWN” button on XQ & WS models. LEDs for Hour, Start, E2 KEYBOARD STUCK ERROR: If key button(s) are and Stop will blink 1 bps while Test Mode is active. pressed conti
Inhaltszusammenfassung zur Seite Nr. 11
REFRIGERATION SYSTEM SEQUENCE OF OPERATION A good understanding of the basic operation of the refrigera- the liquid refrigerant leaves the metering device entering tion system is essential for the service technician. Without the evaporator coil. As it enters the evaporator coil, the this understanding, accurate troubleshooting of refrigeration larger area and lower pressure allows the refrigerant to system problems will be more diffi cult and time consuming, expand and lower its temperature (h
Inhaltszusammenfassung zur Seite Nr. 12
EQUIPMENT REQUIRED H ERMETIC COMPONENT REPLACEMENT cont’d 1. Voltmeter 6. Pressurize system to 30 PSIG with proper refrigerant and boost refrigerant pressure to 150 PSIG with dry nitrogen. 2. Ammeter 7. Leak test complete system with electric halogen leak 3. Ohmmeter detector, correcting any leaks found. 4. E.P.A. Approved Refrigerant Recovery System. 8. Reduce the system to zero gauge pressure. 5. Vacuum Pump (capable of 200 microns or less vacuum.) 9. Connect vacuum pump to high sid
Inhaltszusammenfassung zur Seite Nr. 13
REFRIGERANT CHARGING NOTE: BECAUSE THE RAC SYSTEM IS A SEALED compressor motor. When this occurs, the motor winding SYSTEM, SERVICE PROCESS TUBES WILL HAVE TO BE temperature will increase causing the motor to overheat INSTALLED. FIRST INSTALL A LINE TAP AND REMOVE and possibly cycle open the compressor overload protector. REFRIGERANT FROM SYSTEM. MAKE NECESSARY Continued overheating of the motor windings and/or cycling SEALED SYSTEM REPAIRS AND VACUUM SYSTEM. of the overload will eventually
Inhaltszusammenfassung zur Seite Nr. 14
REFRIGERANT CHARGING cont’d UNDERCHARGED REFRIGERANT SYSTEMS An undercharged system will result in poor performance (low Intermittent frosting and thawing of the evaporator is another pressures, etc.) in both the heating and cooling cycle. indication of a low charge, however, frosting and thawing can also be caused by insuffi cient air over the evaporator. Whenever you service a unit with an under charge of refrigerant, always suspect a leak. The leak must be repaired Checks for an undercharge
Inhaltszusammenfassung zur Seite Nr. 15
REFRIGERANT CHARGING cont’d RESTRICTED REFRIGERANT SYSTEM A quick check for either condition begins at the evaporator. Troubleshooting a restricted refrigerant system can With a partial restriction, there may be gurgling sounds at the be diffi cult. The following proced ures are the more metering device entrance to the evaporator. The evaporator common problems and solutions to these problems. in a partial restriction could be partially frosted or have an ice There are two types of refrigerant
Inhaltszusammenfassung zur Seite Nr. 16
TROUBLESHOOTING TOUCH TEST CHART: TO SERVICE REVERSING VALVES NORMAL FUNCTION OF VALVE NOTES: VALVE OPERATING * TEMPERATURE OF VALVE BODY CONDITION ** WARMER THAN VALVE BODY 1 2 3 4 5 6 POSSIBLE CAUSES CORRECTIONS Cool Hot Normal Cooling Hot Cool *TVB TVB as (2) as (1) Hot Cool Normal Heating Hot Cool *TVB TVB as (1) as (2) MALFUNCTION OF VALVE No voltage to coil. Repair electrical circuit. Check Electrical circuit and coil Defective coil. Replace coil. Low charge. Repair leak, recharge sys
Inhaltszusammenfassung zur Seite Nr. 17
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Action Check voltage at compressor. 115V & 230V units Low voltage will operate at 10% voltage variance Set t-stat to coldest position. Test t-stat & replace T-stat not set cold enough or inoperative if inoperative Hard start compressor. Direct test compressor. If Compressor hums but cuts off on B10 overload compressor starts, add starting components Compressor does not run Open or shorted compressor windings Chec
Inhaltszusammenfassung zur Seite Nr. 18
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Action Replace fuse, reset breaker. If repeats, check Fuse blown or circuit tripped fuse or breaker size. Check for shorts in unit wiring & components Power cord not plugged in Plug it in Unit does not run System switch in "OFF" position Set switch correctly Inoperative system switch Test for continuity in each switch position Loose or disconnected wiring at switch or other Check wiring & connections. Reconnect pe
Inhaltszusammenfassung zur Seite Nr. 19
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Action Check operation of unit. Replace overload if Overload inoperative. Opens too soon system operation is satisfactory Allow a minimum of 2 minutes to allow pressures Compressor restarted before system pressures to equalize before attempting to restart. Instruct equalized customer of waiting period Check voltage with unit operating. Check for other appliances on circuit. Air conditioner should Low or fl uctua
Inhaltszusammenfassung zur Seite Nr. 20
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Action Ensure that foam gaskets are installed in Sublimation: When between window panes & in between the unit & unconditioned saturated, outside air mixes with the sleeve. Also, ensure that fresh air/exhaust conditioned air, condensation forms on the cooler vents (on applicable models) are in the closed surfaces position & are in tact Water "spitting" into room Follow install