Inhaltszusammenfassung zur Seite Nr. 1
569J
60Hz AIR COOLED CONDENSING UNIT
PURONr (R--410A) REFRIGERANT
6 TO 20 NOMINAL TONS
Product Data
Bryant’s air-cooled air conditioning split systems:
S provide a logical solution for commercial needs
S have a rugged, dependable construction
S are available in single and circuit scroll compressor
capacity control
S have cooling capability up to 125_F(52_C) ambient
anddownto40_F(4_C) ambient standard
FEATURES / BENEFITS
These dependable outdoor air cooled condensing units
match Bryant’s indoor-a
Inhaltszusammenfassung zur Seite Nr. 2
FEATURES AND BENEFITS (cont.) help to ensure economical performance of the split system Factory-installed options (FIOPs) both now and in the future. Certified and pre--engineered factory-installed options Indoor--air quality (IAQ) features (FIOPs) allow units to be installed in less time, thereby reducing installed cost. FIOPs include: The unique combination of IAQ features in the 524J S low ambient controls which provide cooling operation Series air handlers help to ensure that only clean, fre
Inhaltszusammenfassung zur Seite Nr. 3
FEATURES AND BENEFITS (cont.) Coil flexibility TABLE OF CONTENTS Model 524J direct- expansion coils have galvanized steel PAGE casings; inlet and outlet connections are on the same end. FEATURES / BENEFITS ........................ 1 The coils are designed for use with Puron (R--410A) 3 / -in. diameter copper tubes refrigerant and have 8 MODEL NUMBER NOMENCLATURE ............ 4 mechanically bonded to aluminum sine-wave fins. The coils include matched, factory-installed thermostatic AHRI CAPACITY
Inhaltszusammenfassung zur Seite Nr. 4
MODEL NUMBER NOMENCLATURE 123456789 1011121314151617 5 6 9 J E 1 4 A 0 0 0 G 0 0 A 0 A _____________ ModelType 569J =BryantCondensing Unit PuronrR---410ARefrigerant Voltage Packaging E=460/3/60 A=Standard P =208/230/3/60 B=LTL T=575/3/60 BaseUnitControls NominalTonnage 0=None 07=6Tons 16=15Tons 08=7.5Tons 25=20Tons ElectricalOptions 12=10Tons A=None 14=12.5Tons C =Non---Fused Disconnect RefrigerantCircuit ServiceOptions A=SingleCircuit 0=Electro---MechanicalControls B =SingleCircuitwith LowAmbie
Inhaltszusammenfassung zur Seite Nr. 5
AHRI* CAPACITY RATINGS NOM. NET COOLING TOTAL COOLING CAPACITY CAPACITY POWER UNIT COMPRESSORS EER IEER CIRCUITS (TONS) (MBH) (kW) 569J*07A/524J*07 1 1 6 71.0 6.2 11.5 12.2 569J*08A/524J*08 1 1 7.5 92.0 8.2 11.2 11.8 569J*12A/524J*12 1 1 10 117.0 10.4 11.2 12.0 569J*14A/524J*14 1 1 12.5 148.0 13.5 11.0 12.0 569J*16A/524J*16 1* 2 15 184.0 16.4 11.2 13.2 569J*25A/524J25 1* 2 20 240.0 21.8 11.0 11.2 * Singlecircuitwithtwo(tandem)compressors. Seeapplicationtip#38TIP---10---03forstagingcapabilities.
Inhaltszusammenfassung zur Seite Nr. 6
PHYSICAL DATA Single Circuit Models with NOVATION --- All AluminumCoil Design 569J*07A 569J*08A 569J*12A 569J*14A 569J*16A Refrigeration System #Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scroll 1/1/Scroll 1/2/Scroll R---410A chargeA/B(lbs) 4.4 4.9 6.3 7.3 12.2 Systemchargew/fancoil 8.4 10.2 13.8 18.0 24.6 Meteringdevice TXV TXV TXV TXV TXV High---press.Trip/Reset(psig) 630/505 630/505 630/505 630/505 630/505 Low---press.Trip/Reset(psig) 54/117 54/117 54/117 54/117 54/117 Cond. Coil Material
Inhaltszusammenfassung zur Seite Nr. 7
PHYSICAL DATA (CONT.) Dual Circuit Models with NOVATION --- All AluminumCoil Design 569J*12D 569J*14D 569J*16D Refrigeration System #Circuits/#Comp./Type 2/2/Scroll 2/2/Scroll 2/2/Scroll R---410A chargeA/B(lbs) 3.0 /3.1 3.7/3.9 6.1/6.1 Systemchargew/fancoil 7.4 / 7.4 10.8 / 10.8 12.0/12.0 Meteringdevice TXV TXV TXV High---press.Trip/Reset(psig) 630 / 505 630 / 505 630 / 505 Low---press.Trip/Reset(psig) 54 / 117 54 / 117 54 / 117 Cond. Coil Material(Fin/Tube) Al/Al Al/Al Al/Al Coiltype Novation N
Inhaltszusammenfassung zur Seite Nr. 8
DIMENSIONS C101212A 8 569J
Inhaltszusammenfassung zur Seite Nr. 9
DIMENSIONS (cont.) C101213 9 569J
Inhaltszusammenfassung zur Seite Nr. 10
DIMENSIONS (cont.) STD. UNIT WT. CORNER A CORNER B CORNER C CORNER D CENTER OF GRAVITY UNIT HEIGHT ELECTRICAL UNIT CHARACTERISTICS LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z H 569JA25 (RTPF) 208/230-3-60,460-3-60,575-3-60 978 444 360 163 188 85 147 67 283 128 38 [965.2] 23 [584.2] 17 [431.8] 50-3/8 [1279.2] 569JD25 (RTPF) 208/230-3-60,460-3-60,575-3-60 978 444 360 163 188 85 147 67 283 128 38 [965.2] 23 [584.2] 17 [431.8] 50-3/8 [1279.2] CENTER OF GRAVITY SERVICE VALVE CONNECTIONS CG UNI
Inhaltszusammenfassung zur Seite Nr. 11
OPTIONS AND ACCESSORIES 569J* OPTIONS AND ACCESSORIES ITEM OPTION* ACCESSORY† DisconnectSwitch(non-fused)} X Special---coated CoilProtection X ConvenienceOutlet(115-v)** X LowAmbientTemperature X X MotorMasterIrControl Wired CondenserCoilGrille(Novation 07 ---14modelsonly) X Louvered HailGuard X X ProgrammableThermostats X * Factory-installedoption. † Field-installedaccessory. } Non---fuseddisconnectswitchcannotbeusedwhenunitMOCPelectricalratingexceeds80amps. **Poweredandnon---poweredversionsava
Inhaltszusammenfassung zur Seite Nr. 12
OPTIONS AND ACCESSORIES (cont.) LOW AMBIENT CONTROL (FACTORY-INSTALLED OR FIELD-INSTALLED) FACTORY-INSTALLED COIL PROTECTION OPTIONAL FACTORY-INSTALLED OPTIONAL CONVENIENCE OUTLET FACTORY-INSTALLED (powered and non-powered) DISCONNECT SWITCH C101216 569J* field-installed accessories 524J factory-installed options –20_F (–29_C) low-ambient temperature kit accessory Alternate fan motors and drives are available to provide (MotorMaster Ir) controls outdoor-fan motor operation the widest possible ra
Inhaltszusammenfassung zur Seite Nr. 13
OPTIONS AND ACCESSORIES (cont.) Overhead suspension package includes necessary Condensate drain trap includes an overflow shutoff brackets to support units in horizontal installations. switch that can be wired to turn off the unit if the trap becomes plugged. The kit also includes a wire harness CO sensors can be used in conjunction with the 2 that can be connected to an alarm if desired. The economizer accessory to help meet indoor air quality transparent trap is designed for easy service and r
Inhaltszusammenfassung zur Seite Nr. 14
OPTIONS AND ACCESSORIES (cont.) 524J WITH DISCHARGE PLENUM 524J WITH HOT WATER OR STEAM COIL RETURN-AIR GRILLE AND SUBBASE HOT WATER OR STEAM COIL DISCHARGE PLENUM RETURN-AIR GRILLE SUBBASE FAN COIL FAN COIL UNIT UNIT 524J WITH ECONOMIZER AND UV-C GERMICIDAL LAMPS 524J WITH CONDENSATE TRAP ECONOMIZER UV-C GERMICIDAL LAMPS C09259 14 569J
Inhaltszusammenfassung zur Seite Nr. 15
SELECTION PROCEDURE Combination ratings for 569J* units matched with 524J IV. Determine fan rpm and bhp (brake horsepower). Series air handlers are in this book. If unit is used with an Refer to the 524J Air Handler Catalog -- Fan air handler, use the Bryant Electronic Catalog AHU Performance table. Enter the Air Handler Fan (Air-Handling Unit) selection program to obtain combined Performance table at 524J12 at 4000 cfm and move to ratings. the External Static Pressure (ESP) column. Note that th
Inhaltszusammenfassung zur Seite Nr. 16
TYPICAL WIRING SCHEMATIC C09624 Typical 569J*16 Single Circuit 16 569J
Inhaltszusammenfassung zur Seite Nr. 17
TYPICAL WIRING SCHEMATIC (cont.) C09627 Typical 569J*16 Dual Circuit 17 569J
Inhaltszusammenfassung zur Seite Nr. 18
PERFORMANCE DATA 569J*07A CONDENSER ONLY RATINGS AIR TEMPERATURE ENTERING CONDENSER (_F) SST(_F) 80 85 95 100 105 115 TC 46.7 45.1 41.7 39.8 37.9 33.9 20 kW 4.04 4.27 4.77 5.04 5.32 5.93 SDT 91.6 96.4 105.9 110.6 115.3 124.7 TC 51.8 50.2 46.5 44.6 42.6 38.4 25 kW 4.06 4.29 4.79 5.05 5.33 5.95 SDT 92.7 97.5 106.9 111.6 116.3 125.6 TC 57.0 55.2 51.4 49.4 47.3 42.9 30 kW 4.07 4.30 4.80 5.07 5.35 5.96 SDT 93.9 98.6 108.1 112.7 117.4 126.7 TC 62.7 60.8 56.8 54.6 52.4 47.8 35 kW 4.09 4.32 4.81 5.08 5.
Inhaltszusammenfassung zur Seite Nr. 19
PERFORMANCE DATA (cont.) 569J*12A CONDENSER ONLY RATINGS AIR TEMPERATURE ENTERING CONDENSER (_F) SST(_F) 80 85 95 100 105 115 TC 78.0 75.4 70.1 67.3 64.6 58.9 20 kW 6.03 6.44 7.31 7.76 8.23 9.21 SDT 94.0 98.7 108.2 113.0 117.7 127.2 TC 86.4 83.6 77.9 74.9 72.0 66.0 25 kW 6.11 6.53 7.41 7.87 8.36 9.36 SDT 95.2 100.0 109.4 114.2 118.9 128.2 TC 94.7 91.8 85.6 82.5 79.4 73.0 30 kW 6.20 6.62 7.51 7.98 8.47 9.49 SDT 96.6 101.3 110.7 115.4 120.0 129.2 TC 104.0 100.8 94.3 90.9 87.6 80.7 35 kW 6.30 6.71
Inhaltszusammenfassung zur Seite Nr. 20
PERFORMANCE DATA (cont.) 569J*14A CONDENSER ONLY RATINGS AIR TEMPERATURE ENTERING CONDENSER (_F) SST(_F) 80 85 95 100 105 115 TC 100.8 97.4 90.3 86.6 83.0 75.5 20 kW 8.48 8.97 10.00 10.53 11.07 12.19 SDT 98.0 102.6 111.8 116.4 120.9 130.0 TC 111.8 108.1 100.5 96.6 92.7 84.7 25 kW 8.66 9.15 10.20 10.75 11.31 12.47 SDT 99.6 104.1 113.2 117.7 122.3 131.3 TC 122.9 118.9 110.7 106.6 102.4 93.9 30 kW 8.84 9.35 10.41 10.97 11.55 12.75 SDT 101.3 105.8 114.8 119.3 123.8 132.7 TC 134.9 130.6 121.9 117.4 1