Inhaltszusammenfassung zur Seite Nr. 1
Precision Cooling
For Business-Critical Continuity
™
Liebert XDA Air Flow Enhancer
User Manual
Inhaltszusammenfassung zur Seite Nr. 2
Inhaltszusammenfassung zur Seite Nr. 3
TABLE OF CONTENTS 1.0 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Features & Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Pre-Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2.1 Required Tools . . .
Inhaltszusammenfassung zur Seite Nr. 4
ii
Inhaltszusammenfassung zur Seite Nr. 5
1.0 PRODUCT DESCRIPTION The Liebert XDA Air Flow Enhancer increases the airflow through densely populated enclosures, breaking up hot spots within the enclo- sure that can threaten the uptime of your critical systems. Equipment fans often produce insufficient flow to push air through the masses of data communication wiring at the rear of the enclosure. With an XDA placed on the exhaust side of the enclosure (the five high-static fans ensure positive air flow), the heat is moved out of the e
Inhaltszusammenfassung zur Seite Nr. 6
2.0 INSTALLATION The Liebert XDA can be attached to most equipment cabinet doors 60" tall or taller. The unit typically is installed on the outside of a cabi- net’s rear door, generally used to discharge heat generated from the cabinet. If aisle space is insufficient for exterior mounting, and space is avail- able inside the cabinet, the XDA may be installed on the inside of the door. 2.1 Equipment Inspection Immediately after receiving the shipment, remove the XDA and all components from th
Inhaltszusammenfassung zur Seite Nr. 7
2.2.1 Required Tools • Phillips screwdriver • Pliers • Scissors 2.3 Mounting the XDA on the Exterior of the Rear Cabinet Door 2.3.1 Prepare to Install the Unit Nuts on screw 1. Determine the desired mount- visible from front of unit ing position on the door. 2. Attach the mounting bracket to the top of the XDA, positioning the bracket to obtain the desired mounting height. XDA mounting bracket ... 3. Position the hanging support of ... attached to XDA the bracket toward the rear of the
Inhaltszusammenfassung zur Seite Nr. 8
2.3.2 Mount the Unit and Attach it to the Cabinet 1. Lift the unit with bracket attached and hang it on the door, as shown at right. Ensure that the bracket rests safely on top of the top edge of door. 2. Move the unit sideways into the desired position. Ensure that the unit does not interfere with operation of the door latch. 3. Place screws through the middle and lower mounting holes of the XDA mounting angle and then through the door. Place nuts on the screws and tighten them. 4. Remove
Inhaltszusammenfassung zur Seite Nr. 9
2.4 Mounting the XDA on the Interior of the Rear Cabinet Door 2.4.1 Prepare to Install the Unit NOTE For mounting inside the cabinet, the mounting angles must first be reversed, as described in Steps 1 through 4 below. 1. Remove the screws on the Wider side of mounting sides of the XDA that angle with round holes secure the mounting angles fits against XDA to the unit. 2. Remove the mounting angles. 3. Position the angles so their mounting surfaces are near the front of the XDA. (This
Inhaltszusammenfassung zur Seite Nr. 10
2.4.2 Mount the Unit and Attach It to the Cabinet 1. Lift the unit onto the door, placing the two mounting holes on the top end, over the two screws attached to the door and bracket. Place nuts on the screws to hold the unit in place. 2. On the middle and lower mounting holes, place screws through the door and then through the mounting angle. Place nuts on the screws. Tighten all nuts. 3. Remove the nuts from the two top screws (the ones through the bracket and door). 4. Lean the top of th
Inhaltszusammenfassung zur Seite Nr. 11
3.0 POWER CONNECTIONS Connect the power cords to separate power sources (as specified in Specifications on page 9), to keep the XDA operating if there is a power failure on one circuit. Route the power cords under or over the cabinet as needed to the nearest available receptacles. If only one power source is available, connect both power cords to this source. Separate electrical circuits are recommended. Ensure adequate length of the power cords when the door is fully opened. Secure the po
Inhaltszusammenfassung zur Seite Nr. 12
4.0 OPERATION & MAINTENANCE The XDA is activated by turning on the ON/OFF switch on the bottom of the unit, near the power cords. All fans operate continuously to remove the maximum amount of heat from the cab- inet. If a power failure should occur on the primary power source, the XDA will ON/OFF switch operate from the secondary source until (seen from below the XDA) the primary power source is restored. The XDA will continue to operate as long as either of the two power sources is avai
Inhaltszusammenfassung zur Seite Nr. 13
5.0 SPECIFICATIONS Nominal Capacity 1000 CFM @ 60Hz Dimensions 8 x 2.25 x 56 W x D x H, in (mm) (203.2 x 57.2 x 1422.4) Weight, lbs (kg) 25 (11.3) 120V-1-50/60Hz Electrical Specifications 230V-1-50/60Hz 1.5 A @ 120V Amp Draw 0.8 A @ 230V 9
Inhaltszusammenfassung zur Seite Nr. 14
10
Inhaltszusammenfassung zur Seite Nr. 15
Inhaltszusammenfassung zur Seite Nr. 16
Ensuring The High Availability 0f Mission-Critical Data And Applications. Technical Support / Service Locations Web Site United States www.liebert.com 1050 Dearborn Drive Monitoring P.O. Box 29186 800-222-5877 Columbus, OH 43229 monitoring@emersonnetworkpower.com Europe Outside the US: 614-841-6755 Via Leonardo Da Vinci 8 Single-Phase UPS Zona Industriale Tognana 800-222-5877 35028 Piove Di Sacco (PD) Italy upstech@emersonnetworkpower.com +39 049 9719 111 Outside the US: 614